Page 1
KNX GPS Weather station Electrical/Mechanical characteristics: see product user manual A faire Application software TP device Product reference Product designation Radio device STXE530 TXE530 KNX GPS Weather station 1.x Version TXE530 6LE001714A...
Application Product reference STXE530 TXE530 1.3 Easy tool software appearance This product can also be configured using the TXA100 configuration tool. It is composed of a TJA665 configuration server. It is essential to update the configuration server software version. (Please refer to the TXA100 user manual).
2. General Description 2.1 Installation of the device 2.1.1 Overview presentation KNX shutter control Tasks TXE530 Thermostat KNX Radio switch Shutter/blind output module 24 V = Local server ETHERNET Supply 24 V = Touchscreen Touchpad Smartphone TXE530 6LE001714A...
In order to perform the physical addressing or to check whether or not the bus is connected, press the lighted push button (see chapter 2.1.2 for the button location). Light on = bus connected and ready for physical addressing. Programming mode is activated, until the physical address is transferred from ETS. Pressing the button again, exits programming mode. TXE530 6LE001714A...
Rain, wind and frost alarms 20 s Luminosity 25 s Wind speed measurement Precipitation detection Temperature recordings Shading control 30 s Heat protection and heat recovery The date and time are emitted from the first GPS signal following power failure or downloading. TXE530 6LE001714A...
Wind alarm defined by 3 thresholds (Alarm 1 - 4 m/s, Alarm 2 - 8 m/s, Alarm 3 - 12 m/s) ■ Shading control This function manages up to 4 facades with several levels of shading depending on the angle of slat blinds or shutter closure. TXE530 6LE001714A...
Page 8
Heat protection/recovery deactivation Date and time master Indoor temperature for facade 1 Date and time request Sun protection facade x position % Sun protection facade x slat angle % Shading status facade x Heat protection/recovery deactivation status Heat protection/recovery status TXE530 6LE001714A...
15 - Date and time master - Output (8 Byte - 19.001 DPT_Date_Time) In the first instance, the current date and time can be set via the ETS. The weather station works with this data until a valid GPS signal is received for the first time. * Default value TXE530 6LE001714A...
Page 10
Date and time in Autonomous mode The weather station operates with its own date and time to calculate the azimuth and elevation. No item is sent to or read on the KNX bus. TXE530 6LE001714A...
UTC definition Europe criteria. The time change is carried out through specific settings according to Other countries the criteria in place in the country of installation. There are additional settings that allow configuration for other countries. * Default value TXE530 6LE001714A...
Page 12
Summer/winter time change Parameter Description Value First summer/winter time This setting determines the day of the week on which Sunday* change the time change will take place. Monday Tuesday Wednesday Thursday Friday Saturday Any day * Default value TXE530 6LE001714A...
This setting determines the value of the time difference 60* minutes: -720 to +780 min (in minutes) in relation to Greenwich Mean Time. 3.1.2 Weather data and alarms Note: All of the settings in this tab are set and cannot be modified. * Default value TXE530 6LE001714A...
The "Night" information is activated (bit = 1) if the value measured is less than the threshold value (10 Lux) for one minute. Communication objects: 2 - Luminosity - Output (2 Byte - 9.004 DPT_Value_Lux) 3 - Day/night - Output (1 Bit - 1.011 DPT_State) TXE530 6LE001714A...
To manage shading on a facade with both blinds and shutters, two facades must be registered: one for blinds and one for shutters. Here, facade 2 is for shutters and facade 4 is for blinds. TXE530 6LE001714A...
Page 17
Facade 2: E = 90° Facade 3: S = 180° Facade 4: W = 270° Example 2: Direction: Facade 1: NE = 45° Facade 2: SE = 135° Facade 3: SW = 225° Facade 4: NW = 315° TXE530 6LE001714A...
Page 18
Note: To manage a glazed roof or partially glazed roof, the roof must be declared as one of the facades with the setting (All = 360°). Note: This is intended only for blinds with horizontal slats. * Default value TXE530 6LE001714A...
Page 19
Example of 80% maximum closure (default value): 20 % 40 % 60 % 80 % α Example Shutter position Sun position - Angle between 46° ... 90° 31° ... 45° 16° ... 30° 0° ... 15° TXE530 6LE001714A...
Page 20
(20 to 80 %). If the luminosity level is insufficient (less than 32 Klux for more than 15 minutes) or the sun is not shining on the facade: The shutter is positioned at a fixed value of 0 %. TXE530 6LE001714A...
Page 21
Diffuse daylight, however, can still continue to enter and so provide lighting for the room (daylight use). Sun protection at low sun elevations The slats are automatically closed to an extent where the sun cannot shine directly into the room. Position: 100 % Tilt tracking: 80 % * Default value TXE530 6LE001714A...
Page 22
22 - Sun protection facade 2 slat angle % - Output (1 Byte - 5.001 DPT_Scaling) 23 - Shading facade 2 deactivation - Input (1 Bit - 1.003 DPT_Enable) 24 - Shading deactivation status facade 2 - Output (1 Bit - 1.003 DPT_Enable) * Default value TXE530 6LE001714A...
In winter, heat recovery allows for the blinds to be positioned so as to reheat the room using sunlight, thus benefiting from a free heat source. These two functions result in the full opening or closing of shutters or blinds. Using these functions is recommended when rooms are empty. TXE530 6LE001714A...
Page 24
To save energy, the heat recovery system contributes to heating up the room by using the sun's energy. It depends on: the luminosity on the facade the position of the sun on the facade the outdoor temperature on all of the facades or the indoor temperature on the facade 1 * Default value TXE530 6LE001714A...
Page 25
34 - Heat protection/recovery deactivation status - Output (1 Bit - 1.003 DPT_Enable) 35 - Heat protection/recovery status - Output (1 Bit - 1.011 DPT_State) 36 - Indoor temperature for facade 1 - Input (2 Byte - 9.001 DPT_Value_Temp) * Default value TXE530 6LE001714A...
Input 1 bit Shading deactivation status facade 4 Output 1 bit Heat protection/recovery deactivation Input 1 bit Heat protection/recovery deactivation status Output 1 bit Heat protection/recovery status Output 1 bit Indoor temperature for facade 1 Input 2 byte TXE530 6LE001714A...
Resolution: 1 lux for 0 to 120 lux 2 lux for 121 to 1 046 lux 63 lux for 1 047 to 52 363 lux 423 lux for 52 364 to 150 000 lux For further information, see: Luminosity. TXE530 6LE001714A...
Page 28
10 minutes thereafter. The frost alarm is disabled (bit = 0) if the value measured is greater than 5 °C. It will immediately be transmitted and every 10 minutes thereafter. For further information, see: Temperature measurement. TXE530 6LE001714A...
1 = Monday ... 7 = Sunday (3 bit) Hours Binary 0 to 23 (5 bit) Hours Minutes Binary 0 to 59 (6 bit) Minutes Seconds Binary 0 to 59 (6 bit) Seconds For further information, see: Date and time. TXE530 6LE001714A...
Page 30
0 = time valid or 1 = invalid time (1 bit) Summer/Winter Period (SWP) Binary 0 = standard time or 1 = summertime (1 bit) 0 = no external synchronisation or Clock Accuracy (CA) Binary 1 =external synchronisation (1 bit) For further information, see: Date and time. TXE530 6LE001714A...
Page 31
Byte 1 (LSB) Month Year Fields Code Value Units Binary 1 to 31 (5 bit) Month Binary 1 to 12 (4 bit) Month Year Binary 0 to 99 (7 bit) Year For further information, see: Date and time. TXE530 6LE001714A...
Page 32
1 = Monday ... 7 = Sunday (3 bit) Hours Binary 0 to 23 (5 bit) Hours Minutes Binary 0 to 59 (6 bit) Minutes Seconds Binary 0 to 59 (6 bit) Seconds For further information, see: Date and time. TXE530 6LE001714A...
Page 33
0 = time valid or 1 = invalid time (1 bit) Summer/Winter Period (SWP) Binary 0 = standard time or 1 = summertime (1 bit) 0 = no external synchronisation or Clock Accuracy (CA) Binary 1 =external synchronisation (1 bit) For further information, see: Date and time. TXE530 6LE001714A...
It is used to position the shutter or blind in response to the value that is sent on the KNX bus. Object value: 0 to 255 0 (0 %): slats open. 255 (100 %): slats closed. This object is sent when there is a status change. For further information, see: Shading. TXE530 6LE001714A...
Page 35
Sun protection facade 2 slat angle Output 1 Byte - 5.001 DPT_Scaling C, R, T See object No. 18 Name Function of the Data type Flags object Shading facade 2 deactivation Input 1 Bit - 1.003 DPT_Enable C, W See object No. 19 TXE530 6LE001714A...
Page 36
Input 1 Bit - 1.003 DPT_Enable C, W See object No. 19 Name Function of the Data type Flags object Shading deactivation status Output 1 Bit - 1.003 DPT_Enable C, R, T facade 4 See object No. 20 TXE530 6LE001714A...
If the heat recovery or protection function is activated, a telegram with logical value 1 is sent. If the heat recovery or protection function is disabled, a telegram with logical value 0 is sent. For further information, see: Heat protection, heat recovery. TXE530 6LE001714A...
Page 38
This object is activated when the Use of heat protection automatic control or Use of heat recovery automatic control setting is activated. It receives the indoor temperature, which is transmitted by a thermostat in the room. Object value: -30 °C to +80 °C For further information, see: Heat protection, heat recovery. TXE530 6LE001714A...
The information from these objects may come from 3 different sources, each with its own priority: The domovea system (priority 1 - the highest) The weather station (priority 2 - medium) A clock (priority 3 - the lowest) TXE530 6LE001714A...
Page 41
CONSUMER Date and time 1 Internet Domovea Master Slave Clock (TX022/TX023/TXA022/TXA023) Room controller GPS signal Date and time 2 (TX450/TX460) Weather station (TXE530) Power manager (WKT660) Clock Automatic temperature controller Date and time 3 Master/slave (WUT08/WUT09/WHT730/ (TX022/TX023/ WHT740/WKT510/WKT511 TXA022/ 80440100/80660100)
This automatic link is used for several products. They have a channel that enables the display or use of the outdoor temperature and frost alarm. CONSUMER SUPPLIER Domovea Outdoor temperature Room controller Weather station (TX460/WYT61x/ (TXE530) WYT62x/TX320/TX502) Power manager Outdoor (WKT660) Power manager temperature External (TXA230A/ probe...
Page 43
SUPPLIER CONSUMER Frost alarm Weather station Domovea (TXE530) ■ Group address Outdoor temperature 30/0/000 Frost alarm 30/0/012 TXE530 6LE001714A...
The domovea supervision system also uses this link but only for the slave channel. Products are in slave mode by default. They switch to master mode when a luminosity probe is connected to the product. SUPPLIER CONSUMER Luminosity Weather station Domovea (TXE530) Twilight switch External (TX025/TXA025) Luminosity Twilight switch probe...
Page 45
80141170/80141180/80142170/ SUPPLIER 80142180/8014132x/8014232x/ 8014332x/8014432x/8016177x/ 8016178x/8016277x/8016278x/ Day/night info 8016186x/8016286x/8016377x/ Weather station 8016378x/8016477x/8016478x) (TXE530) Domovea Automatic temperature controller (WUT08/WUT09/WHT730/ WHT740/WKT510/WKT511 80440100/80660100) To control the push button lighting using the day/night information, the FPL function must be set up in the product. To control the push button LEDs using the day/night information, the LED function must be set up in the product.
Page 46
Another possible link: It is possible to use an ON/OFF output (outdoor lighting) from the Day/night function. Inputs Outputs TXE530 - 1 - 1 TXA610 - 1 - 1 Housing Housing - Lighting ■ Group address Luminosity 30/0/002 Day/night 30/0/003...
SUPPLIER CONSUMER Wind speed Domovea Weather station (TXE530) Wind alarm 1, 2 and 3 Automatic links through configuration This link is established depending on the configuration of products. For the wind alarm, please refer to the shutter configuration. TXE530 6LE001714A...
Page 48
CONSUMER SUPPLIER Bi-application output module (TXA604/TXA606/TXA608/ Wind alarm 1, 2 and 3 TXA610/TXM616/TXM620/ Weather station TXB602/TXB692F) (TXE530) Shutter/blind output module (TXA624/TXA628/TXM632/ TXA223/TXA224/TXA225/ TXA226) TXA624 configuration: Parameter Description Value Wind alarm stepping Activates the shutter output on receipt of wind alarms 1,...
This automatic link is used for several products. It has a channel that can display or use the rain alarm. SUPPLIER CONSUMER Rain alarm Weather station Domovea (TXE530) Automatic links through configuration This link is established depending on the configuration of products. For the rain alarm, please see the shutter configuration. TXE530 6LE001714A...
Page 50
CONSUMER SUPPLIER Bi-application output module (TXA604/TXA606/TXA608/ Rain alarm TXA610/TXM616/TXM620/ Weather station TXB602/TXB692F) (TXE530) Shutter/blind output module (TXA624/TXA628/TXM632/ TXA223/TXA224/TXA225/ TXA226) TXA624 configuration: Parameter Description Value Rain alarm Activates the shutter output on receipt of the rain alarm. Yes Position on rain alarm...
To manage shading on a facade with both blinds and shutters, two facades must be registered: one for blinds and one for shutters. Here, facade 2 is for shutters and facade 4 is for blinds. TXE530 6LE001714A...
Page 52
Facade 2: E = 90° Facade 3: S = 180° Facade 4: W = 270° Example 2: Direction: Facade 1: NE = 45° Facade 2: SE = 135° Facade 3: SW = 225° Facade 4: NW = 315° TXE530 6LE001714A...
Page 53
Note: To manage a glazed roof or partially glazed roof, the roof must be declared as one of the facades with the setting (All = 360°). Note: This is intended only for blinds with horizontal slats. * Default value TXE530 6LE001714A...
Page 54
Example of 80% maximum closure (default value): 20 % 40 % 60 % 80 % α Example Shutter position Sun position - Angle between 46° ... 90° 31° ... 45° 16° ... 30° 0° ... 15° TXE530 6LE001714A...
Page 55
(20 to 80 %). If the luminosity level is insufficient (less than 32 Klux for more than 15 minutes) or the sun is not shining on the facade: The shutter is positioned at a fixed value of 0 %. TXE530 6LE001714A...
Page 56
Diffuse daylight, however, can still continue to enter and so provide lighting for the room (daylight use). Sun protection at low sun elevations The slats are automatically closed to an extent where the sun cannot shine directly into the room. Position: 100 % Tilt tracking: 80 % * Default value TXE530 6LE001714A...
Page 57
CONSUMER Position % Facade 2 Bi-application output module Slat position % Facade 2 (TXA604/TXA606/TXA608/ Weather station TXA610/TXM616/TXM620/ (TXE530) TXB602/TXB692F) Position % Facade 3 Shutter/blind output module (TXA624/TXA628/TXM632) Slat position % Facade 3 Position % Facade 4 Slat position % Facade 4...
Page 58
Define the maximum shutter position for shading (20-80%) for each facade. This setting is only valid if shading is established using the shutter position. On the shutter output module: • Define on which facade the shutter is found. This setting triggers the shutter shading function. TXE530 6LE001714A...
Page 59
The shading function is activated by default. Shading activation or deactivation can be established using domovea. This can also be done using the push button, as shown below: Inputs Outputs WST312 - 1 - 1 TXE530 - 1 - 1 Housing Housing - Shutter This link activates shading via the push button. •...
33 °C or the indoor temperature is greater than 28°C on the facade 1: The heat protection is activated. The shutters and blinds close completely. This function is prioritized on the shading control. TXE530 6LE001714A...
Page 61
28 °C or the indoor temperature is greater than 25 °C for facade 1: Heat recovery is disabled. The shutters and blinds close completely. Parameter Description Value Heat recovery Automatic control of heat recovery is: Not active Active * Default value TXE530 6LE001714A...
Page 62
Activate the heat protection and/or heat recovery. A link must be created with the thermostat for the indoor temperature of facade 1. Inputs Outputs WST322 - 1 - 15 TXE530 - 1 - 1 Housing Housing - Shutter Inputs Outputs...
Page 63
The heat protection and heat recovery function is activated by default. Activation or deactivation of heat protection and heat recovery can be established using domovéa. This can also be done using the push button, as shown below: Inputs Outputs WST312 - 1 -1 TXE530 - 1 - 1 Housing Housing - Shutter This link activates heat protection/recovery. •...
5. Appendix 5.1 Specifications 5.2 Characteristics Device TXE530 Max. number of group addresses Max. number of allocations Objects TXE530 6LE001714A...