Table 5.4 Program Functions
Parameter
Date
Time
Monthly Test Date
Monthly Test Time
Yearly Test Date
Yearly Test Time
Load Reduction
Low VAC Alarm
High VAC Alarm
Ambient Temp Alarm DDD(Degrees Centigrade)
Near Low Battery
Near Low Battery Voltage is in VVVV (Volts). The last digit entered is after the decimal
place. I.E. (430 + ENTER) will register 43.0VDC.
Load Reduction Fault is in AAAA (Amps). The last digit entered is after the decimal place.
I.E. (480 + ENTER) will register 48.0 Amps. If the output current under battery power is 1
0 percent below this number, the alarm will be set.
Low AC Voltage Alarm is in VVVV (Volts). The last digit entered is after the decimal
place. I.E. (1200 + ENTER) will register 120.0 Volts. If the Input AC Voltage goes below
this number the alarm will be set.
High AC Voltage Alarm is similar to Low AC Voltage Alarm.
Ambient Temperature Alarm is in DDD (Degrees Centigrade). I.E. (75 + ENTER) will
register 75 deg. C. When the ambient temperature internal to the inverter enclosure goes
above the set point the alarm will be set.
12
Format
MM/DD/YY (Month, Date, Year)
HH/MM (Hours, Minutes)
DD (Date)
HH/MM (Hours, Minutes)
MM (Month)
HH/MM (Hours, Minutes)
AAAA(Amps)
VVVV(Volts)
VVVV(Volts)
VVVV(Volts)
Factory Default
Current Date
Eastern Stand Time
th
15
of the Month
5:00
01
8:00
0.0A
1.0V
999.9V
70°C
43VDC
113904 – System Users Manual