*. Includes blower motor amps of largest fan coil used with heater. Consult Product Data for specific motor amps.
†. For 240V, multiply 230V heater amps by 1.04. Wire sizing and over-current protection may need adjustment per local code requirements.
‡. Copper wire must be used. If other than uncoated (non-plated), 75°C ambient, copper wire (solid wire for smaller, and stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code (ANSI/NFPA 70).
**. Field convertible to 3 phase.
††. Single circuit application of F15 and F20 heaters requires single-point wiring kit accessory.
‡‡. Field convertible to 1 phase, single or multiple supply circuit.
kW
HEATER PART NO.
240V
208V
‡
24
18.0
KFFEH3401F24A
‡
30
22.5
KFFEH3501F30A
*. Includes blower motor amps of largest fan coil used with heater.
†. Copper wire must be used. If other than uncoated (non-plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡. Field convertible to 1 phase, single or multiple supply circuit.
Table 2 – Electric Heater Electrical Data
*
HEATER AMPS
Internal
†
208/230V
Circuit
Protection
Dual Circuit
Single
Circuit
L1,L2
1
None
10.7/11.9
—
1
None
10.7/11.9
—
1
None
17.8/19.7
—
1
Ckt Bkr
17.8/19.7
—
1
None
17.8/19.7
—
1
Ckt Bkr
17.8/19.7
—
1
None
17.8/19.7
—
1
Ckt Bkr
17.8/19.7
—
1
None
28.5/31.5
—
1
Ckt Bkr
28.5/31.5
—
1
None
28.5/31.5
—
1
Ckt Bkr
28.5/31.5
—
1
None
35.6/39.4
—
1
Ckt Bkr
35.6/39.4
—
1
None
35.6/39.4
—
1
Ckt Bkr
35.6/39.4
—
1
None
32.2/35.6
—
3
None
18.6/20.6
—
1
Fuse
53.4/59.1
35.6/39.4
17.8/19.7
1
Ckt Bkr
53.4/59.1
35.6/39.4
17.8/19.7
3
Fuse
30.8/34.1
—
3
None
37.2/41.2
—
1
Fuse
71.2/78.8
35.6/39.4
35.6/39.4
1
Ckt Bkr
71.2/78.8
35.6/39.4
35.6/39.4
3
Fuse
49.3/54.6
—
1
Fuse
85.5/94.5
—
3
Fuse
61.7/68.2
—
1
Fuse
106.8/118.1
—
Table 3 – Field Multipoint Wiring or 24- and 30-kW Single Phase