3.3 Electrical connections

BEWARE: DANGER
a
Before any connection operation,
it is COMPULSORY to disconnect
the power supply.
BEWARE: DANGER
a
Exclusively use double-insulated
wires.
The connection cable and the ul-
tra-low-voltage safety cables (con-
trols, electric lock, antenna, power
supply for auxiliaries) must be sep-
arated (minimum 4 mm in air or
1 mm through supplementa-
ry insulation) from the 230V ~
power supply cables.
Fasten the cables with adequate
cable clamps near the terminal
blocks.
The NET-COM device must be powered us-
ing a power supply suited to the consump-
tion levels indicated in the "Technical data"
paragraph.
We recommend using item 163523.
12 13 14 15 16 17 32 33
(non supplied)
20
Power supply
item 163523
Connecting an external NETLINK
device
It is possible to connect a DEA NETLINK de-
vice using the cable provided:
J7
TTL
1 2 3 4 5 6
g y w
g= green
y= yellow
w= white
Position jumper J7 on TTL.
If NET-COM is installed at more than 3 m
from the device, it is necessary to use the
S-EXTENDER accessory (art. 677650): this sig-
nal amplifier allows for reaching a maximum
distance of 50 m by using a 3x1 mm shielded
cable.
In this configuration, position jumper J7
on 485.
Connection of the receiver for
controlling a generic automation
NET-COM has 2 programmable outputs that
can be activated from DEA remotes.
Connect the normally open contact of the de-
sired output to the input of the control unit
with OPEN or START function.
C NO NC
C NO NC
12 13 14 15 16 17 32
Output1Output2
Open/Start
control
NETLINK
connection
cable
max 3 m
33
Control
unit 2
Control
unit 1