Advertisement
Switch the dip switch on the back of the control to either °C or °F.
Note: The other three dip switches are not used.
Press on or
once to see setpoint temperature appear on display. Every subsequent press will change the setpoint temperature by one degree.
Select chosen setpoint temperature by using or
button. Press on
button (2 to 3 seconds) until icon appears on display.
Select chosen setpoint temperature by using or
button. Press on
button (2 to 3 seconds) until icon appears on display.
Adjust the setpoint temperature until heating indicator (flames) appears on display. Press TEST button. The test is conclusive if the warning light (GFCI) on thermostat is ON and power to the load is cut-off (flames remain on display though). If these events do not occur, check the installation. Press on RESET button to reset the GFCI.
Parts included:
One (1) 500500-120 (120 VAC) thermostat
Two (2) 6-32 screws
Four (4) Solderless connectors (for copper wire)
One (1) Temperature sensor with a 15-foot extension
TURN OFF POWER TO THE HEATING SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. KEEP AIR VENTS OF THE THERMOSTAT CLEAN AND FREE OF OBSTRUCTIONS.
This thermostat should be installed by an electrician or experienced technician. The thermostat must be used with a self-protected heating system equipped with a thermal cut-off and circuit breaker or fuse.
This thermostat was designed to control floor electric heating systems. The resistive load must not exceed 1920 watts at 120 VAC (16.0 A). The thermostat is equipped with a ground fault circuit interrupter (GFCI) and therefore the isolation of the line and load is required for operation. The polarity of line connection must be respected. During a ground fault, only the current in the black wire of the load will be cut-off. Connect thermostat as shown on diagram.
Connect the rear thermostat wires to the power supply and to the load using solderless connectors for copper wires. See schematic diagram below.
Push the excess wire back into the electrical box to prevent interference with the thermostat. Secure the thermostat using two (2) 6-32 screws 1-1/4 inches long. Once the thermostat is properly installed, return power to heating system.
Connect the sensor wire to the two lower screws of the terminal block at the back of the thermostat (no polarity need to be respected). The wire must pass outside the electrical box and follow the wall down to the floor. The sensing probe should be placed in a representative heat area for maximum system performance. The sensing probe should be centered between the wires in the mat. The probe wire cannot cross any heater wires and the temperature sensor must not be directly or adjacent to a heating wire.
To power up thermostat:
When power is applied for the first time, the display must show the floor temperature. Other information might show up on the display if installation is defective or does not comply with the instructions. The warning light (GFCI) must be off.
The message L0 will appear on the display if the temperature sensor is not hooked up, is in default or the temperature is below 0°C (32°F). Also, the heating indicator will be present on display and the relays will be close (current going in the load).
The message E1 will appear on the display if the temperature sensor is short-circuited. The message HI will appear on the display if the temperature is higher than (99°F).
If anything else appears on the display, press the button as you press and release the RESET button.
Adjust the setpoint temperature until heating indicator () appears on display. Press TEST button. The test is conclusive if the warning light (GFCI) on the thermostat is ON and power to the load is cut-off. If these events do not occur, check the installation. Press on RESET button to reset the GFCI.
If the GFCI test fails:
Check the load wires. The thermostat must be in heating mode to carry out the test (heating indicator ON).
The GFCI test should be carried out monthly. If the test fails, cut off the electric power to the heating system and call customer service or return the thermostat to your supplier for verification. If the warning light comes on during normal operation, cut off power to the heating system and have an electrician verify the installation.
The thermostat has 4 different buttons to control the floor temperature. The and
buttons increase or decrease the setpoint temperature. The
and
buttons are used to store and recall two temperature settings.
To choose the temperature scale, press the button while pressing and releasing the RESET button. Then release the
button.
Model: | 500500-120 (120 VAC) |
Supply: | 120 VAC, 50/60 Hz |
Load: | 16.0 A maximum (resistive only) |
Power: | 1920 W at 120 VAC |
Ground fault circuit interrupter (GFCI): | Class A (5 MA TRIP LEVEL) |
Approvals: | CSA NRTL/C |
Display range: | 0° to 60°C (32°C to 99°F) |
Setting range: | 10° to 50°C (50°C to 99°F) |
![]() | 30°C (86°F) |
![]() | 10°C (50°F) |
Storage: | –20°C to 50°C (–4°F to 120°F) |
Temperature regulation: | 1°C (2°F) |
Precision: | ±0.5°C (1°F) (1920 W) |
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download SunTouch 500500-120 - Thermostat Quick Start Manual
Advertisement
Need help?
Do you have a question about the 500500-120 and is the answer not in the manual?
Questions and answers