SunTouch 500500-120 - Thermostat Quick Start Manual

Also See for 500500-120:

Advertisement

SunTouch 500500-120 - Thermostat Quick Start Manual

SUMMARY

TO CHANGE THE TEMPERATURE SCALE FROM °C (CELSIUS) TO °F (FAHRENHEIT) AND BACK

Switch the dip switch on the back of the control to either °C or °F.
Note: The other three dip switches are not used.

TO SET TEMPERATURE

Press on or once to see setpoint temperature appear on display. Every subsequent press will change the setpoint temperature by one degree.

TO RECORD THE (COMFORT) SETPOINT TEMPERATURE

Select chosen setpoint temperature by using or button. Press on button (2 to 3 seconds) until icon appears on display.

TO RECORD THE (ECONOMIC) SETPOINT TEMPERATURE

Select chosen setpoint temperature by using or button. Press on button (2 to 3 seconds) until icon appears on display.

CHECKING GROUND FAULT CIRCUIT INTERRUPTER (GFCI)

Adjust the setpoint temperature until heating indicator (flames) appears on display. Press TEST button. The test is conclusive if the warning light (GFCI) on thermostat is ON and power to the load is cut-off (flames remain on display though). If these events do not occur, check the installation. Press on RESET button to reset the GFCI.

OVERVIEW

INSTALLATION

Parts included:

One (1) 500500-120 (120 VAC) thermostat
Two (2) 6-32 screws
Four (4) Solderless connectors (for copper wire)
One (1) Temperature sensor with a 15-foot extension

TURN OFF POWER TO THE HEATING SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. KEEP AIR VENTS OF THE THERMOSTAT CLEAN AND FREE OF OBSTRUCTIONS.

This thermostat should be installed by an electrician or experienced technician. The thermostat must be used with a self-protected heating system equipped with a thermal cut-off and circuit breaker or fuse.

This thermostat was designed to control floor electric heating systems. The resistive load must not exceed 1920 watts at 120 VAC (16.0 A). The thermostat is equipped with a ground fault circuit interrupter (GFCI) and therefore the isolation of the line and load is required for operation. The polarity of line connection must be respected. During a ground fault, only the current in the black wire of the load will be cut-off. Connect thermostat as shown on diagram.

CONNECTING WIRES AND MOUNTING THERMOSTAT

Connect the rear thermostat wires to the power supply and to the load using solderless connectors for copper wires. See schematic diagram below.
CONNECTING WIRES AND MOUNTING THERMOSTAT

Push the excess wire back into the electrical box to prevent interference with the thermostat. Secure the thermostat using two (2) 6-32 screws 1-1/4 inches long. Once the thermostat is properly installed, return power to heating system.

CONNECTING TEMPERATURE SENSOR WIRE

Connect the sensor wire to the two lower screws of the terminal block at the back of the thermostat (no polarity need to be respected). The wire must pass outside the electrical box and follow the wall down to the floor. The sensing probe should be placed in a representative heat area for maximum system performance. The sensing probe should be centered between the wires in the mat. The probe wire cannot cross any heater wires and the temperature sensor must not be directly or adjacent to a heating wire.
CONNECTING TEMPERATURE SENSOR WIRE

POWER UP

To power up thermostat:

When power is applied for the first time, the display must show the floor temperature. Other information might show up on the display if installation is defective or does not comply with the instructions. The warning light (GFCI) must be off.

The message L0 will appear on the display if the temperature sensor is not hooked up, is in default or the temperature is below 0°C (32°F). Also, the heating indicator will be present on display and the relays will be close (current going in the load).

The message E1 will appear on the display if the temperature sensor is short-circuited. The message HI will appear on the display if the temperature is higher than (99°F).

If anything else appears on the display, press the button as you press and release the RESET button.

CHECKING GROUND FAULT CIRCUIT INTERRUPTER (GFCI)

CHECKING GROUND FAULT CIRCUIT INTERRUPTER

Adjust the setpoint temperature until heating indicator () appears on display. Press TEST button. The test is conclusive if the warning light (GFCI) on the thermostat is ON and power to the load is cut-off. If these events do not occur, check the installation. Press on RESET button to reset the GFCI.

If the GFCI test fails:
Check the load wires. The thermostat must be in heating mode to carry out the test (heating indicator ON).

The GFCI test should be carried out monthly. If the test fails, cut off the electric power to the heating system and call customer service or return the thermostat to your supplier for verification. If the warning light comes on during normal operation, cut off power to the heating system and have an electrician verify the installation.

OPERATION

The thermostat has 4 different buttons to control the floor temperature. The and buttons increase or decrease the setpoint temperature. The and buttons are used to store and recall two temperature settings.

  • Default values
    To erase the recorded setting temperatures ( and ) and replace their values by the default ones, 30°C (86°F) and 10°C (50°F) press the button while pressing and releasing the RESET button. Then release the button.
  • Setting a setpoint temperature
    Press once the or button to see the setpoint temperature on display. Every subsequent press will change the setpoint temperature by one degree.
  • Recording setpoint temperature for (COMFORT) and (ECONOMIC) settings
    By recording two setpoint temperatures you will be able to go from the setting to the setting by simply pressing the or button.
  • Recording a setpoint temperature for the (COMFORT) setting
    Select chosen setpoint temperature by using and buttons. Keep pressing on the button (2 to 3 seconds) until icon appears on display.
  • Recording a setpoint temperature for the (ECONOMIC) setting
    Select chosen setpoint temperature by using and buttons. Keep pressing on the button (2 to 3 seconds) until icon appears on display.
    NOTE: When the temperature setting used is or , you can still use the or buttons to change the setpoint temperature without changing the recorded temperature.
  • Recalling stored setpoint temperatures
    Once stored, both setpoint temperatures can be recalled simply by selecting the or button.

CHOOSING THE TEMPERATURE SCALE IN °C (CELSIUS) OR °F (FAHRENHEIT) TO APPEAR ON DISPLAY

To choose the temperature scale, press the button while pressing and releasing the RESET button. Then release the button.

CHARACTERISTICS

Model: 500500-120 (120 VAC)
Supply: 120 VAC, 50/60 Hz
Load: 16.0 A maximum (resistive only)
Power: 1920 W at 120 VAC
Ground fault circuit interrupter (GFCI): Class A (5 MA TRIP LEVEL)
Approvals: CSA NRTL/C
Display range: 0° to 60°C (32°C to 99°F)
Setting range: 10° to 50°C (50°C to 99°F)
Default setting: 30°C (86°F)
Default setting: 10°C (50°F)
Storage: –20°C to 50°C (–4°F to 120°F)
Temperature regulation: 1°C (2°F)
Precision: ±0.5°C (1°F) (1920 W)

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download SunTouch 500500-120 - Thermostat Quick Start Manual

Advertisement

Need help?

Need help?

Do you have a question about the 500500-120 and is the answer not in the manual?

Questions and answers

Table of Contents