Download Print this page

LG MULTI V SE Series Installation Manual page 9

Heat pump indoor unit
Hide thumbs Also See for MULTI V SE Series:

Advertisement

5. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
Align the center of the pipings and sufficiently tighten
the flare nut by hand.
Indoor unit tubing
Tighten the flare nut with a wrench.
Torque
wrench
Indoor
unit tubing
Pipe Size[Torque]
GAS
Ø12.7[5.5kg . m]
Ø15.88[6.6kg . m]
Mount the clamp on the boss with a type "B"
screw.(optional)
Type "B" screw
Clamp
Boss
When extending the drain hose at the indoor
unit, install the drain pipe.
Drain pipe
Vinyl tape(narrow)
Adhesive
6. Wrap the insulation material around the connect-
ing portion.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands
Flare nut Pipings
Spanner (fixed)
Flare nut
Connection
pipe
LIQUID
Ø6.35[1.8kg . m]
Ø9.52[4.2kg . m]
Drain hose
Indoor unit
drain hose
Insulation material
Wrap the area which accommodates the rear pip-
ing housing section with vinyl tape.
Connection
pipe
Wrap with vinyl tape
Vinyl tape
(wide)
Connecting cable
Vinyl tape(narrow)
Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range with-
in which they fit into the rear piping housing sec-
tion.
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
Drain hose
For left rear piping
1. Route the indoor tubing and the drain hose to the
required piping hole position.
2. Insert the piping, drain hose and the connecting
cable into the piping hole.
Installation
Indoor
unit pipe
Pipe
Connecting cable
Drain pipe
Installation Manual 9

Advertisement

loading

This manual is also suitable for:

Multi v s3 series