Eilersen 5024G Options Manual

External module
Hide thumbs Also See for 5024G:
Table of Contents

Advertisement

Quick Links

5024G
5024G LCD weighing terminal
External module option: MCE9637, MCE2035, 2050 or 2070
Software:
StdLim.140630.6v0x
Doc. no.:
StdLim-140630-6v0a-OG-ExtModule-eng
Date:
2021-09-21
Rev.:
6v0a
Options Guide
External Module
Contact:
Eilersen Electric A/S
Kokkedal Industripark 4
DK-2980 Kokkedal
Denmark
www.eilersen.com
info@eilersen.com
Tel: +45 49 180 100
Fax: +45 49 180 200

Advertisement

Table of Contents
loading

Summary of Contents for Eilersen 5024G

  • Page 1 5024G Options Guide External Module 5024G LCD weighing terminal External module option: MCE9637, MCE2035, 2050 or 2070 Contact: Software: StdLim.140630.6v0x Eilersen Electric A/S Doc. no.: StdLim-140630-6v0a-OG-ExtModule-eng Kokkedal Industripark 4 Date: 2021-09-21 DK-2980 Kokkedal Rev.: 6v0a Denmark www.eilersen.com info@eilersen.com Tel: +45 49 180 100...
  • Page 2: Table Of Contents

    Contents ............................2 Introduction ..........................5 Installation of external module ....................5 How to ............................5 – Enable and configure external module on 5024G ..........5 Enable or change Device Type ................6 Set/Read Device Address .................. 6 Set/Read Endian ....................6 Read Status .......................
  • Page 3 Trouble shooting ........................15 Appendices ..........................16 Appendix A – Screens overview ................16 Appendix B – Electrical connection of 5024G to external module ...... 17 RS485 communication connector on 5024G ..........17 Appendix C – MCE2035 Profibus-DP module ............18 MCE2035 Profibus-DP specification ..............
  • Page 4 Appendix I – 2070 Tips for PROFINET configuration ..........36 MAC addresses ....................36 GSDML file ....................... 36 Factory settings ....................36 Setting DeviceName, IP Address etc............... 37 Data sizes ......................37 Revision History ........................38 Contact ............................38 WWW.EILERSEN.COM...
  • Page 5: Introduction

    Introduction This document describes the use of the External Module option on the 5024G Weighing Ter- minal from Eilersen Electric. With the software version stated on the front page and with the External Module option enabled as well as a on RS485 externally connected communications module (MCE2035, 2070, MCE9637 or 2050) from Eilersen Electric the system can communi- cate with an external controller/PLC using Profibus-DP, PROFINET, DeviceNet or Ethernet-IP.
  • Page 6: Enable Or Change Device Type

    MCE9637 DeviceNet module, 2050 Ethernet module and 2070 PROFINET module. If no ex- ternal module is enabled the 5024G display will show “-------” / ”None”. Once a module type is enabled/selected the other settings (see descriptions below) are set to default values, which should normally be used.
  • Page 7: Set/Read Bytes Out

    Set/Read Bytes Out Number of bytes to be sent from the 5024G to the external module and from there to the Profibus-DP/PROFINET/DeviceNet/Ethernet master. This is the number of input bytes in the Profibus-DP/PROFINET/DeviceNet/Ethernet master. The value must be the same as the value in the external module. Normally this is 14.
  • Page 8: Mod

    (MRV) and as Main Actual Value (MAV). Please see below for further information. MDS contains an RS part for selection of Main Reference Value (MRV) and an AS part for selec- tion of Main Actual Value (MAV), as shown in the figure below. WWW.EILERSEN.COM...
  • Page 9: Pcv Description

    RC to inform the master the status of the received 'request' (’response’). The contents of RC has the following function during ’request: REQUEST FUNCTION No request Request parameter value Change parameter value (2 bytes) Change parameter value (4 bytes) Others Reserved for future use The contents of RC has the following function during response: WWW.EILERSEN.COM...
  • Page 10: Pnu

    During communication from the slave to the master, the first two bytes of the PCD part are used as a Status Word (STW). Using the Status Word (STW) it is possible for the master to gain infor- mation on the status of the slave. WWW.EILERSEN.COM...
  • Page 11: Mrv/Mav

    Actual Value Selector Main Actual Value Not used Actual gross weight Actual net weight Others Not used Actual gross weight is the actual gross weight on the 5024G terminal. Actual net weight is the actual net weight on the 5024G terminal. WWW.EILERSEN.COM...
  • Page 12: Ctw - Control Word

    Registration OK Registration not possible Fine dosing Coarse dosing Not used Registration ready OK – always ON Weight reading not possible is active when the 5024G terminal is unable to determine weight. Zero OK is active when zero was possible.*) WWW.EILERSEN.COM...
  • Page 13: Parameters

    20 - 35 2, R Load cell-Status[x] 40 - 55 4, R Load cell-Gross[x] Others Not used Actual gross weight is the actual gross weight on the 5024G terminal. Actual net weight is the actual net weight on the 5024G terminal. WWW.EILERSEN.COM...
  • Page 14 Decimal point position indicates the number of digits after the decimal point in the display read- ing. It should be used to scale weight indications received/transmitted using the Profibus- DP/PROFINET/DeviceNet/Ethernet-IP communication. Load cell-Status[x] contains the actual status for load cell x. Load cell-Gross[x] contains the actual gross signal (not zeroed) on load cell x. WWW.EILERSEN.COM...
  • Page 15: Trouble Shooting

    Check connection between 5024G and external module is ok (see below). from/to 5024G No connection be- Check the field bus cabling between 5024G and PLC is made correctly. tween PLC and exter- Check possible termination of field bus is made correctly.
  • Page 16: Appendices

    ├── COARSETARE │ │ │ ├── ZEROING │ │ │ ├── CALIBRATION ── CORNER CAL. │ │ │ ├── LINEARIZATION │ │ │ └── DISPLAY │ ├─ DOSING PAR. │ ├─ ETHERNET ──────── PROTOCOLS │ └─ EXT. MODULE ───── DATA WWW.EILERSEN.COM...
  • Page 17: Appendix B - Electrical Connection Of 5024G To External Module

    The following describes the electrical connection of the 5024G terminal to a general external module using a RS485 connection. RS485 communication connector on 5024G The 3 pin RS485 serial communication connector (J4) on the 5024G can be used for RS485 communication with external equipment. This connector has the following connections: J4 pin...
  • Page 18: Appendix C - Mce2035 Profibus-Dp Module

    MCE9601 connection module using the supplied ribbon cable with mounted connectors. Through this bus cable connection of power supply is achieved as well as connection to the 5024G terminal (RS485 master). The MCE9601 module is connected to the 5024G terminal as follows: MCE9601 CONNECTOR CONNECTION B (DATA- ) 5024G J4.1: RS485-B...
  • Page 19: Mce2035 Dip-Switch Settings

    FUNCTION Baudrate on the AUX bus. OFF: Communication at 9600 bps. ON: Communication at 115200 bps. (MUST be in this position for communication with 5024G) (Normally the jumper will be mounted on delivery.) JU2-JU4 Alternative termination of the Profibus-DP. If R17, R21 and R22 are mounted these jumpers can be used to connect the...
  • Page 20: Mce2035 Light Emitting Diodes

    +5VDC (Vout) J1.7 Not used J1.8 RS485-B (negative line) (Siemens designation: A line) J1.9 Not used Note that some companies use different designations for the RS485-A and the RS485-B lines. Therefore the polarity of the lines has been listed. WWW.EILERSEN.COM...
  • Page 21: Appendix D - 2070 Profinet Module

    11. Verify that expected data can be transferred across the PROFINET. 2070 Connection without MCE9601 If the 2070 PROFINET module is connected to the 5024G terminal without an external MCE9601 connection module, the connection is made as described in the following.
  • Page 22: 2070 Connection With Mce9601

    2070 Connection with MCE9601 If the 2070 PROFINET module is connected to the 5024G terminal with an external MCE9601 connection module, the connection is made as described in the following. The green two pole power connector (J2) of the 2070 module is NOT used. The green three pole RS485 connector (J1) of the 2070 module is NOT used.
  • Page 23: 2070 Light Emitting Diodes

    The 2070 device ReaDY LED can be lit/flashing depending on the status of the device. The function of the RDY LED is given below. Reserved for future use (Red) Communication with RS485 master (Green) Toggles when the PROFINET module receives a valid telegram on the RS485 bus. WWW.EILERSEN.COM...
  • Page 24: 2070 Profinet Connector

    RS485 data is transmitted. Power (Green) 3.3 VDC internal power supply is on. 2070 PROFINET connector The front of the 2070 PROFINET module is equipped with two standard Ethernet RJ45 con- nectors (PORT1 and PORT2) for PROFINET connection using Cat5 cables. WWW.EILERSEN.COM...
  • Page 25: Appendix E - Mce9637 Devicenet Module

    MCE9601 connection module using the supplied ribbon cable with mounted connectors. Through this bus cable connection of power supply is achieved as well as connection to the 5024G terminal (RS485 master). The MCE9601 module is connected to the 5024G terminal as follows: MCE9601 CONNECTOR CONNECTION B (DATA- ) 5024G J4.1: RS485-B...
  • Page 26: Mce9637 Dip-Switch Settings

    LSB and Sw2.3 is MSB. Note that these switches are only read during pow- er-on. The baudrate of the MCE9637 module is set according to this table: Sw2.2 Sw2.1 Baudrate 125 kbps 250 kbps 500 kbps Not allowed WWW.EILERSEN.COM...
  • Page 27: Mce9637 Jumper Settings

    Network Status LED (Green/Red The MCE9637 Network Status LED, that can be lit/flashing in different colors LED) depending on the status of the network. The function of the NS LED is given in the table below. WWW.EILERSEN.COM...
  • Page 28: Mce9637 Devicenet Connector

    The MCE9637 module is equipped with a 5 pole connector for connection to DeviceNet. The connection is according to the DeviceNet specification and is made as follows: J2 Connector Function Color J2.1 (Black) (0VDC input) J2.2 CAN_L (Blue) J2.3 SHIELD (Grey) J2.4 CAN_H (White) J2.5 (Red) (24VDC input) WWW.EILERSEN.COM...
  • Page 29: Appendix F - 2050 Ethernet-Ip Module

    8. Verify that none of the D1 or D2 lamps are lit. 2050 Connection without MCE9601 If the 2050 Ethernet module is connected to the 5024G terminal without an external MCE9601 connection module, the connection is made as described in the following.
  • Page 30: 2050 Connection With Mce9601

    5024G J4.3: RS485-GND 2050 Connection with MCE9601 If the 2050 Ethernet module is connected to the 5024G terminal with an external MCE9601 connection module, the connection is made as described in the following. The green two pole power connector (J2) of the 2050 module is NOT used. The green three pole RS485 connector (J1) of the 2050 module is NOT used.
  • Page 31: 2050 Light Emitting Diodes

    The 2050 Network Status LED, that can be lit/flashing in different colors de- pending on the status of the network. The function of the NS LED is given in the table below. Reserved for future use (Red) Reserved for future use (Red) WWW.EILERSEN.COM...
  • Page 32 FUNCTION RS485 RX (Yellow) RS485 data is received. RS485 TX (Green) RS485 data is transmitted. RS232 RX (Yellow) RS232 data is received. RS232 TX (Green) RS232 data is transmitted. Power (Red) 3.3 VDC internal power supply is on. WWW.EILERSEN.COM...
  • Page 33: 2050 Rs232 Connector (J4)

    RS232 communication channel. This RS232 channel is used for setup/configuration of the 2050 Ethernet module from a PC as described below. Connection to this connector is made using a special serial cable supplied by Eilersen Electric A/S. The 4 pole connector (J4) on the 2050 module has the following connections:...
  • Page 34: 2050 Ip Address Setting

    When the 2050 is powered the following will be displayed Eilersen Electric A/S 2050 module. Software version: EthernetIP.111025.1.1 -------------------------------------------------- --- MAIN MENU (1) show Info (2) change Settings (3) reset and switch to Download mode -------------------------------------------------- 2050 IP address setting To get the main menu press “Enter”...
  • Page 35: Appendix H - 2050 Ethernet-Ip Connection To Allen Bradley

    Ethernet-IP communication – Master input Ethernet-IP communication from the 2050 Ethernet module uses a single Assembly consist- ing of 14 bytes data as specified in the EDS file: Assembly: Assem3 Input Assembly instance: (0x67) Connection: Connection1 Exclusive Owner Transfer class Class 1 WWW.EILERSEN.COM...
  • Page 36: Ethernet-Ip Communication - Master Output

    2070 PROFINET module will normally be placed in the follow- ing location of the “Hardware catalog”: Other field devices \ PROFINET IO \ I/O \ Eilersen Electric \ 2x70 AUXSLAVE Factory settings Upon delivery the 2070 PROFINET module contains the following default factory settings:...
  • Page 37: Setting Devicename, Ip Address Etc

    PROFINET masters (PLC’s) point of view. Therefore, the data from the 2070 module to the PLC are referred to as “input” data, while the data from the PLC to the 2070 module are referred to as “output” data. WWW.EILERSEN.COM...
  • Page 38: Revision History

    2021-05-07 Updated references to software ID. 2021-09-21 6v0a Corrected error in Sw2 usage indications for MCE2035 module. Contact With further questions or improvement suggestions please contact us: Eilersen Electric A/S Kokkedal Industripark 4 DK-2980 Kokkedal Denmark www.eilersen.com info@eilersen.com Tel: +45 49 180 100...