GAS HEAT MODE AND ADJUSTMENTS
When the UI calls for gas heat, the Infinity furnace board performs
a self- -check, verifies the pressure switch is open, and starts the
inducer on high speed.
1. Inducer Pre- -purge Period: When the inducer motor comes
up on high speed, the pressure switch closes, and the
Infinity ignition control on the furnace board begins a 15
second pre- -purge period. If the pressure switch fails to
remain closed, the inducer will remain running. After the
pressure switch re- -closes, the Infinity ignition control will
begin a 15 second pre- -purge period.
2. Trial- -For- -Ignition Sequence: The spark igniter will spark
for 3 seconds. The main gas valve relay contact closes to
energize the gas valve on low stage. After 5 seconds, the
igniter is de- -energized and a 2- -second flame- -proving
period begins. NOTE: The unit always lights on high
speed inducer and low stage gas valve operation.
3. Flame- -Proving: When the burner flame is proved at the
flame- -proving sensor, the furnace control determines what
heating stage to run based on feedback from the UI. If the
UI is asking for low stage gas heat, the ignition control will
change the inducer speed to low speed and keep the gas
valve energized on low stage. If the UI is asking for high
stage gas heat, the ignition control will maintain running the
inducer on high speed and energize the gas valve's high
stage relay to increase gas flow.
If the burner flame is not proved within 2 seconds, the control will
close the gas valve and repeat the ignition sequence up to 3 more
Trials- -For- -Ignition before going to Ignition- -Lockout. Lockout
will reset automatically after 3 hours, by momentarily interrupting
230 VAC power, or by interrupting 24 VAC power at SEC1 or
SEC2 to the furnace board.
If flame is proved when there should be no flame present, control
will lock out of Gas- -Heating mode and operate the inducer motor
until flame is no longer proved.
4. Blower- -On Delay:
approximately 37 seconds after the gas valve is opened the
Indoor Blower is turned on to the appropriate speed for the
gas heating stage.
Simultaneously, the humidifier terminal HUM and electronic air
cleaner terminal EAC- -1 are energized throughout the heating
cycle.
NOTE:
EAC- -2 terminal is common with L2 and will have
115VAC- -to- -ground when unit is powered.
5. Blower- -Off Delay: When the call for gas heat is satisfied,
the gas valve is de- -energized, stopping the flow of gas to
the burners, and de- -energizing the HUM terminal. The
inducer motor will remain on for a 4- -second post- -purge
period. The indoor blower and air cleaner terminal EAC- -1
will remain energized for 90, 120, 150, or 180 seconds
(depending on selection of blower- -off delay selected in the
UI). The factory- -set default is 120- -second blower- -OFF
delay.
CHECK GAS INPUT (NATURAL GAS)
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in component
damage.
Do not redrill an orifice. Improper drilling (burrs,
out- -of- -round holes, etc.) can cause excessive burner noise
and misdirection of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check
orifice hole with a numbered drill bit of correct size.
All manuals and user guides at all-guides.com
If the burner flame is proven,
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screws.
This can result in unregulated manifold pressure and result
in excess overfire and heat exchanger failures.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
If the manifold pressure and/or gas rate is not properly
adjusted on HI and LO stages, excess carbon monoxide can
be produced.
WARNING
!
FIRE AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal
injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure
is outside of the ranges listed in Table 6.
Gas input rates on rating plate are for installations at altitudes up to
2000 ft (610 m). Input rate must be within ± 2% of rating plate
input.
1. Determine the correct gas input rate.
a. The rated gas inputs shown in Table 3 are for altitudes
from sea level to 2000 ft (610 m) above sea level.
These inputs are based on natural gas with a heating
value of 1025 Btu/ft3 at .60 specific gravity.
IN THE U.S.A.:
The input rating for altitudes above 2,000 ft (610 m) must be
reduced by 4 percent for each 1,000 ft (305 m) above sea level.
For installations below 2,000 ft (610 m), refer to the unit rating
plate.
For installations above 2,000 ft (610 m), multiply the input by on
the rating plate by the derate multiplier in Table 5 for the correct
input rate.
IN CANADA:
The input rating for altitudes from 2,000 (610 m) to 4,500 ft (1372
m) above sea level must be derated 10 percent by an authorized
Gas Conversion Station or Dealer.
EXAMPLE:
90,000 Bhuh Input Furnace Installed at 4300 ft (1311 m).
Furnace Input Rate
Derate Multiplier
at Sea Level
X
Factor
Altitude
90,000
X
0.90
24
Furnace Input Rate
=
at Installation
=
81,000