Page 1
Installation, Operation, & Maintenance Manual IOM 8302 Rev. A 04/21 WSS6 Series “Slim” Vertical Water Source Heat Pump 16 EER...
Page 2
Altering the product or replacing parts with non-authorized factory parts voids all warranty or implied warranty and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning. WSS6 SERIES – IOM (REV. A 4/21)
STARTUP & PERFORMANCE CHECKLIST INSTRUCTIONS PERFORMANCE TABLES WIRING DIAGRAMS 28-31 CIRCUIT SCHEMATIC TROUBLESHOOTING 33-34 SUPPLEMENTAL DATA / TABLES 35-37 SUPPORT MATERIAL PREVENTATIVE MAINTENANCE STARTUP & PERFORMANCE CHECKLIST INDEX OF FIGURES INDEX OF TABLES WSS6 SERIES – IOM (REV. A 4/21)
CAUTION The CAUTION symbol indicates a potentially hazardous situation that may result in minor or moderate injury. NOTE Used to highlight suggestions, which may result in enhanced installation, reliability or operation. WSS6 SERIES – IOM (REV. A 4/21)
Installation of this equipment, wiring, ducts, and any property damage. related components must conform to current agency codes, state laws, and local codes. Such regulations take precedence over general instructions contained in this manual. WSS6 SERIES – IOM (REV. A 4/21)
WSS6 Series UNIT DIMENSIONAL DATA FIGURE 3 - Right Top View FIGURE 2 - Dimensional Drawing FIGURE 4 - Left Top View FIGURE 6 - Return View FIGURE 5 - Front View WSS6 SERIES – IOM (REV. A 4/21)
8) Ensure that evaporator distributor tubes are not touching one in another and that they are over the drain pan. 9) Check the condensate sensor on the drain pan to make sure that it is rigid and attached. WSS6 SERIES – IOM (REV. A 4/21)
When soldering and brazing, it is recommended to have a fire extinguisher readily available. When soldering and brazing close to valves or sensitive components, heat shields or wet rags are required to prevent damage to the valves or components. WSS6 SERIES – IOM (REV. A 4/21)
. 3/8”-1/2” vibration isolation FIGURE 8 - Mounting Illustration pads must be used to minimize vibration transmission. FIGURE 8 - Mounting Illustration WSS6 SERIES – IOM (REV. A 4/21)
Page 12
FIGURE 9 - Mount on High Platform Units should be mounted level on a solid platform no less than ¾” plywood or other related material with a proper drain pan pitch toward the condensate drain. WSS6 SERIES – IOM (REV. A 4/21)
Refer to the project drawings and specifications for sizing. On units with plastic drain pans the drain connection must be made hand tight only. WSS6 SERIES – IOM (REV. A 4/21)
All 208-240 Volt units are factory wired for 240 Volt operation. For 208 Volt operation, moving/changing/rewiring the line voltage tap on the 24 Volt control transformer is required. See note 3 on the wiring diagram for instruction. WSS6 SERIES – IOM (REV. A 4/21)
Valves should be adjusted to supply proper water flow material can cause damage or failure to the water or to rated for the unit. refrigerant heat exchanger. Failure to do so will VOID ALL FACTORY WARRANTY. WSS6 SERIES – IOM (REV. A 4/21)
Page 17
The discharge water from the heat pump is not specialized training. contaminated in any manner and can be disposed of in various way depending upon local codes. WSS6 SERIES – IOM (REV. A 4/21)
WSS6 Series - IOM CONTROLS SEQUENCE OF OPERATIONS FIGURE 14 - Sequence of Operations WSS6 SERIES – IOM (REV. A 4/21)
Page 19
If the LED display is flashing “Ay” the thermostat is not Test mode can be exited by shorting the test pins for set in cooling mode. approximately 3 seconds. NOTE Test mode will be automatically exited after a 10 minute period. WSS6 SERIES – IOM (REV. A 4/21)
Page 20
RANDOM START HIGH PRESSURE The WSCM module features a 5-80s random start upon If the high-pressure switch opens at any time, the receiving a call to operate. compressor relay is de-energized immediately. WSS6 SERIES – IOM (REV. A 4/21)
Page 21
Revering valve output terminals – direct connect from “O” COND_SW Condensate overflow input terminal Output terminal for electric heat FIGURE 15 - Control Board Layout Grounded common Table 7 - Control Board Layout Legend WSS6 SERIES – IOM (REV. A 4/21)
Page 22
Vacated Premises DIP SWITCH 2 With Fan With Comp Accessory Relay Control None Compressor Delay With Fan With Comp Accessory Relay 2 Control None Fan Delay Table 9 - WSCM DIP Switch Functions WSS6 SERIES – IOM (REV. A 4/21)
G1, G2, and G3, or by directly changing the speed tap at the motor terminal. NOTE High efficiency brushless DC motors are wired with power applied at all times, see illustration above. Low voltage thermostat demand and board algorithms will control its use. WSS6 SERIES – IOM (REV. A 4/21)
NOTE: There may be multiple power sources supplying the unit. Condensing Section Weights Unit Weight (lbs) WSS6006 WSS6009 WSS6012 WSS6015 WSS6018 WSS6024 WSS6030 FIGURE 19 - Ebox Removal Table 10 – Condensing Section Weights WSS6 SERIES – IOM (REV. A 4/21)
Page 25
FIGURE 22 - Mechanical Fittings WARNING Do not pick up condensing section from unit piping or water-coil. Use the integrated handles on the condensing section base pan in order to lift the condensing unit. WSS6 SERIES – IOM (REV. A 4/21)
14. Verify that the water piping is complete and installation. correct. 15. Check condensate overflow sensor for proper operation and adjust position if required. WSS6 SERIES – IOM (REV. A 4/21)
1150 1120 1090 1060 1030 MEDIUM-HIGH 1040 1010 WSS6030 MEDIUM Airflow data shown is with a dry coil at 70°F DB EAT and with standard 1” filter. Table 11 - WSS6 Blower Data WSS6 SERIES – IOM (REV. A 4/21)
WSS6 Series - IOM CIRCUIT SCHEMATIC AP – ACCESS PORT HP – HIGH PRESSURE SWITCH LP – LOW PRESSURE SWITCH FIGURE 27 - Circuit Schematic WSS6 SERIES – IOM (REV. A 4/21)
The unit is low on refrigerant. Check for refrigerant leak, repair, Refrigerant charge evacuate and recharge with factor recommended charge. Low pressure switch Check for defective or improperly calibrated low pressure switch. Table 12 - Troubleshooting Table WSS6 SERIES – IOM (REV. A 4/21)
Page 34
The refrigerant system may be contaminated with moisture or non- Moisture, non- condensables. Reclaim refrigerant, evacuate and recharge with condensables factory recommended charge. Replace filter dryer. Table 13 - Troubleshooting Table Continued WSS6 SERIES – IOM (REV. A 4/21)
19-25 17-21 178-188 346-366 34-40 16-20 134-144 331-351 19-25 8-12 203-213 370-390 38-44 8-12 140-150 459-479 18-24 15-19 Operation Not Recommended 140-150 426-446 18-24 7-11 Table 16 - WSS6012 Pressure & Temperature Data WSS6 SERIES – IOM (REV. A 4/21)
Page 36
21-27 18-22 181-191 384-404 36-42 15-19 126-136 337-357 21-27 8-12 203-213 405-425 40-46 7-11 134-144 515-535 19-25 18-22 Operation Not Recommended 132-142 448-468 20-26 7-11 Table 19 - WSS6024 Pressure & Temperature Data WSS6 SERIES – IOM (REV. A 4/21)
Page 37
Table 20 - WSS6030 Pressure & Temperature Data WATER PRESSURE DROP WATER PRESSURE DROP (psi) DATA Entering Water Temperature °F MODEL WSS6006 WSS6009 WSS6012 WSS6015 WSS6018 WSS6024 WSS6030 Table 21 - Water Pressure Drop (psi) Data WSS6 SERIES – IOM (REV. A 4/21)
FOH = PSI x 2.3 Temperature °C = (°F – 32) x 5/9 Power kW = Btuh / 3412 Weight oz = lb x 16 Weight kg = lb / 2.2 COP x 3.413 EER / 3.413 WSS6 SERIES – IOM (REV. A 4/21)
MAINTENANCE UPDATES Check regularly for a current copy of the maintenance program log which can be found at under “product information”. WSS6 SERIES – IOM (REV. A 4/21)
Need help?
Do you have a question about the WSS6 Series and is the answer not in the manual?
Questions and answers