Installing Wireless Devices

Careful planning is needed when locating the receivers and transmitters based
on the construction materials in the space and possibility of tenant's furniture
disrupting the transmissions.
The temperature sensor should be installed in the space where the receiver is
mounted and connected to the temperature control equipment however the
signal will travel through material barriers.
Refer to the tables below for range considerations with building materials that
reduce the radio signal power.
Wireless System Layout Hints
• Avoid locating transmitters and receivers on the same wall.
• Avoid locating transmitters and receivers where the telegrams must
penetrate walls at acute angles. This increases the material the telegram
must pass through reducing the signal power.
• Avoid large metal obstructions as they create radio shadows. Place
receivers in alternate locations to avoid the shadow or use repeaters to go
around the obstacle.
• Do not locate receivers close to other high frequency transmitters. Leave
at least 3' (1 m) between the receiver and any other source of interference
including, ballasts, LED drivers, computers, video equipment, Wi-Fi/LAN
routers, GSM modems and monitors. Transmitters are not affected by
these sources of interference.
Material
Wood
Plaster
Glass
Brick
MDF
Ferro concrete
Metal
Aluminum
Material
Line of sight:
Line of sight:
Plasterboard:
Brick
Ferro concrete
Ceiling:
Attenuation
0 - 10%
0 - 10%
0 - 10%
5 - 35%
5 - 35%
10 - 90%
90 - 100%
90 - 100%
Radio Range-typical
80' (24m) corridors
150' (46m)open halls
80' (24m) through 3 walls
33' (10m) through 1 wall
33' (10m) through 1 wall
Not Recommended