Download Print this page

ETC Echoflex RTS Series Installation Manual page 6

Resonate wireless temperature sensor

Advertisement

released the test mode button, place the sensor under a lamp with at least 100 foot-
candles (1000 lux) for 1 hour before retrying.
LIGHT LEVEL TEST TABLE
The green LED will blink according to the energy produced by the solar cell
Blinks
Lux
0,1
< 15
2
15-50
3
50-100
4
100-200
5
200-400
The time to fully charge is based on the storage capacitor charging from a
non-operational condition. Discharge time indicates how long a fully charged
sensor will operate in the dark. The test will repeat every 2 seconds and run for
a duration of 100 seconds. You may quit the test at any time by pressing the test
button for 6 seconds.
Range Confirmation Test: provides visual feedback of the sensors signal
strength by a linked receiver with range confirmation capability (only "F series"
controllers have range confirmation ability). One and only one receiver can be
linked to the sensor for proper operation of the test. (disable repeaters in range
for proper test operation).
1. To enter Range Confirmation Test mode, press and hold the occupancy/
test button for 6 seconds. The green led will begin to blink.
2. A quick press and release of the button at this point will allow you to select
between light level test (green LED) and range confirmation test (amber).
When the amber LED is blinking, go to step 3. (If the 3 LEDs fail to blink
during this test, place under a lamp with at least 100 fc (1000 lux) for 1
hour before retrying.)
3. Press and hold the test button again for 6 seconds to select Range
Confirmation Test.
All three LED's can blink in this test mode when the sensor transmits or receives
a Range Confirmation Telegram. The sensor will display the signal strength
status for 5 seconds, see table below.
The test will repeat every 10 seconds and run for a duration of 3 minutes.
You may quit the test at any time by pressing the occupancy/test button for 6
seconds.
6
Foot Candles Time to Fully Charge
< 1.4
below operating level
1.4 - 4.6
min operating level
4.6 - 9.3
24 hours to full charge
9.3 - 18.6
12 hours to full charge
18.6 - 37.2
6 hours to full charge
RANGE CONFIRMATION TEST TABLE
LED
Signal Strength
Green
Amber
Red
> -70 dbm
> -80 dbm
< -80 dbm
Discharge time
n/a
n/a
100 hours
150 hours
200 hours

Advertisement

loading

This manual is also suitable for:

Echoflex rts-1t-nwEchoflex rts-1h-nwEchoflex rts-1ts-nwEchoflex rts-2hs-nw