Heating Operation - Fujitsu RCG24KVLA Service Instruction

Split type room air conditioner cassette
Hide thumbs Also See for RCG24KVLA:
Table of Contents

Advertisement

1-2. Heating operation

A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
• If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
• If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
• Compressor frequency range
Model name
AUXG24KVLA
• Limit of maximum speed based on outdoor temperature
In heating operation, maximum frequency is defined by outdoor temperature and fan mode.
Model name
AUXG24KVLA
1-2. Heating operation
Minimum frequency
Outdoor
temperature rises
14°C
-10°C
Outdoor
temperature
HIGH
zone
A zone
130
B zone
130
C zone
130
14
Outdoor
temperature drops
C zone
12°C
B zone
-12°C
A zone
Indoor unit fan mode
MED
93
93
93
- (04-2) -
Unit: rps
Maximum frequency
130
Unit: rps
LOW
QUIET
83
77
83
77
83
77
1. Compressor frequency control

Advertisement

Table of Contents
loading

This manual is also suitable for:

Auxg24kvlaAo g24kata seriesRog24kata

Table of Contents