General Data - LG ARND DCR4 Series Installation Manual

Split compact dedicated outdoor air system (doas)
Hide thumbs Also See for ARND DCR4 Series:
Table of Contents

Advertisement

Table 2: Split Compact DOAS General Data.
Unit Model No.
Cooling Mode Performance
Total Cooling Capacity (Btu/h)
Hot Gas Reheat Capacity (Btu/h)
Moisture Removal Capacity (lb. / h)
Heating Mode Performance
Capacity (Btu/h) (Main Coil)
Entering Air
Cooling Maximum (°F, D.B. / W.B.)
Heating Minimum (°F, D.B.)
Unit Data
Refrigerant Type
1
Refrigerant Control
Sound Power dB(A)
2
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cable
(No. x AWG)
3
Fan
Type
Motor (HP / W)
Motor / Drive
Airflow Rate (CFM)
External Static Pressure (in. w.g.)
Airflow Range (CFM)
Piping
Liquid Connection Size (in., O.D.)
High Pressure Vapor Connection Size (in., O.D.)
Low Pressure Vapor Connection Size (in., O.D.)
Drain Pump (in., I.D.)
Condensate Drain (in.)
Gravity (in.,O.D.)
Filter
Outdoor
EEV - Electronic Expansion Valve
ECM - Electronically Commutated Motor
Power Supply (V/Hz/Ø): 208-230/60/1
codes.
This data is rated 0 ft. above sea level, with 25 ft. of refrigerant piping per coil.
Main Coil Cooling Capacity Rating obtained with entering air of 95°F D.B. / 75°F W.B. and
leaving air of 52.9°F D.B. / 52.5°F W.B.
Main Coil Heating Capacity Rating obtained with entering air of 44°F D.B. and leaving air
of 70°F D.B.
Reheat Coil Heating Capacity Rating obtained with entering air of 54°F D.B. and leaving
air of 75°F D.B.
Actual discharge air temperatures may vary from discharge air temperature set-point due to changes in outdoor air processing loads.
ARND093DCR4
70,000
13,000
33.0
40,000
122 / 80
14
R410A
EEV
60
342
381
2 (2 conductor) x 18
Sirocco
0.33 / 250
ECM / Direct
900
1.0
500-900
3/8 Brazed
5/8 Brazed
3/4 Brazed
1
1
2" Merv 8 (25" x 20")
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

GENERAL DATA

ARND153DCR4
120,000
24,000
55.0
51,000
122 / 80
(10
) 14
4
R410A
EEV
74
390
430
2 (2 conductor) x 18
3D Plug
1 / 750
ECM / Direct
1,500
2.0
1,000
– 1,500
5
1/2 Brazed
3/4 Brazed
1-1/8 Brazed
1
1
2" Merv 8 (25" x 20")
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
1
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
Sound power levels are tested under AHRI 260 Standard.
2
All communication cable from the outdoor unit to the DOAS unit is to be minimum 18 AWG,
3
2 (2 conductor), twisted, stranded, shielded and must comply with applicable local and na-
tional codes. Ensure the communication cable is properly grounded at the outdoor unit only.
Do not ground the outdoor unit -DOAS unit communication cable at any other point.
4
10°F entering air temperature is allowed for 1,500 CFM or less with minimum 12-ton out-
door unit for one (1) DOAS connected to one (1) outdoor unit, and minimum 30-ton outdoor
unit for two (2) DOAS units connected to (1) outdoor unit. Maximum number of two (2)
DOAS units may be connected to one (1) outdoor unit with 10°F entering air temperature.
Both the ARND153DCR4 and the ARND203DCR4 can provide CFM as low as 900 CFM.
5
For a 900 CFM application, the unit requires a 1-to-1 combination with an LG MV 5 Heat
Recovery 6-ton or 8-ton outdoor unit.
ARND203DCR4
143,100
30,000
67
59,900
122 / 80
14
R410A
EEV
72
390
430
2 (2 conductor) x 18
3D Plug
1 / 750
ECM / Direct
2,000
1.5
1,000
– 2,000
5
1/2 Brazed
7/8 Brazed
1-1/8 Brazed
1
1
2" Merv 8 (25" x 20")
11

Advertisement

Table of Contents