Download Print this page
Berker 75010015 Technical Documentation Manual
Berker 75010015 Technical Documentation Manual

Berker 75010015 Technical Documentation Manual

Power supply 640ma rmd uninterruptible

Advertisement

Quick Links

Power supply 640mA RMD
uninterruptible
75010015
Product name: Power supply 640mA uninterruptible
Design:
REG (rail-mounted device)
Article no.:
7501 00 15
ETS search
System Components/Power supply/Power supply unit 640mA RMD uninterruptible
path:
Functional description:
The uninterruptible KNX/EIB power supply 640 mA (USV) generates and monitors the KNX/EIB system
voltage. The power supply is designed to ensure the interruption-free supply of max. 64 bus devices (1
line) directly via the integrated choke and is therefore suitable for use especially in KNX/EIB security
systems. The device is connected to the system by means of the bus connecting terminal at the front of
the device (no data rail required). The bus output is overload- and short-circuit-protected in acc. with the
KONNEX specification and offers protection against overvoltage.
The KNX/EIB voltage can be buffered with a 12 V DC gelled lead-acid storage battery which is connected
to the device by means of a pre-assembled 4-wire connecting cable. When the mains voltage is on, the
storage battery is recharged via the uninterruptible power supply in a temperature-controlled mode. In
case of mains voltage failure, the KNX/EIB power supply and with it all connected bus devices are
supplied with power from the storage battery. To increase the buffering time during a mains failure, a
second storage battery can be connected to the system with a pre-assembled 2-wire connecting cable.
Storage batteries and cable sets must be ordered separately as accessories.
A potential-free change-over contact can be employed for fault signalling puposes in the event of mains
failures, battery trouble, overvoltage / overloading and short-circuits. Up to 5 different LEDs on the front of
the device inform the user about the different states of operation of the power supply.
Layout:
A
1
2
3
L1
N
E
F
230V OK
OK
12 V
Code /
150 mA
650 mA
ϑ
10
7
8
9
D
Dimensions:
Width:
144 mm (8 modules)
Height:
90 mm
Depth:
66 mm
© Gebr.Berker 2007
(Subject to prior change)
B
4
5
6
µ
µ
G
H
Betrieb
Überlast
I
Reset
30V DC
C
Technical
Documentation
Controls and indicators:
A: mains connection (L, N, PE)
B: connection for potential-free change-over
contact (fault signalling contact)
C: bus connection
D: connecting terminals for storage battery
and external temperature sensor (cf. wiring
diagrams)
E: LED "230 V OK" (green):
lit up when mains voltage is OK.
F: LED "
OK" (green):
lit up when storage battery is connected
and OK.
G: LED "Operation" (green):
lit up when bus voltage is on and OK.
Switches off in the event of bus voltage
failure.
H: LED "Overload" (red):
Lights up in the event of overload (e.g. too
many devices on the bus line) and of
short-circuit.
Eliminate short-circuit / reduce load.
Flashes when overvoltage at bus
connection.
Device switches off automatically
(reset), Locate cause and rectify
I: Reset button and LED (red):
LED lit up during reset state.
Version: 06.07.2007
75010015.doc
Page: 1 / 9
Part 8

Advertisement

loading
Need help?

Need help?

Do you have a question about the 75010015 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Berker 75010015

  • Page 1 Flashes when overvoltage at bus connection. Device switches off automatically (reset), Locate cause and rectify I: Reset button and LED (red): LED lit up during reset state. Page: 1 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change) 75010015.doc...
  • Page 2 < 5 Ah ϑ") (terminals "Code / 650 mA -" und " Terminals: screw terminals: 0.2 … 2.5 mm² stranded wire 0.2 … 4.0 mm² single-wire Page: 2 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change) 75010015.doc...
  • Page 3 User replaceable fuse in in-line fuse holder with bayonnet lock. Type: 5 x 20 mm, time-delay type "T 6,3 H 250 V" Interrupting capacity 1.500 A Page: 3 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change) 75010015.doc...
  • Page 4 ϑ 30V DC wh ye bk rd KNX / EIB basic cable set extension cable set (required) (optional) ϑ storage battery additional storage battery Page: 4 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change) 75010015.doc...
  • Page 5 230V OK 12 V Code / 150 mA 650 mA Reset ϑ 30V DC KNX / EIB basic cable set (required) ϑ storage battery Page: 5 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change) 75010015.doc...
  • Page 6 - The uninterruptible power supply has no facility at the rear for making contact with a data rail. If data rails are to be supplied with power, additional data rail connectors must be used. Page: 6 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change) 75010015.doc...
  • Page 7 LED "Overload" flashes and the bus is automatically reset. The fault message is stored in the relay contact (cf. "Fault message" overleaf). Page: 7 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change)
  • Page 8 A message can also be transmitted automatically to a service technician, if a suitable phone dialler is connected to the fault signalling contact. Page: 8 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change)
  • Page 9 ETS symbol: System Components / Power supply / Power supply 640mA RMD uninterruptible PEI type Applications: No. Summarized description: Name: Version: No application ! Page: 9 / 9 © Gebr.Berker 2007 Version: 06.07.2007 Part 8 (Subject to prior change) 75010015.doc...

This manual is also suitable for: