Hohner IT 210 Operating Manual page 10

Level converter, direction signal decoder and programmable pulse divider
Table of Contents

Advertisement

The green LED signals operational readiness (power switched on).
The yellow LED signals an input error. (RS-422 or HTL Differential only)
An HTL Error Signal (input error, only for RS-422 or HTL differential) is available on
the X3 screw terminal 1. (Error = low)
Basic settings:
At the front DIL switches DIL1 and DIL2, some basic presets have to be made when
commissioning. These determine the input/output mode, the input and output
format, as well as settings of the Z Pulse.
Changes in the settings on the DIL switches will only be taken over
by the device after the supply voltage has been switched on again!
DIL1 (Front 8-pole)
1
2
3
4
ON
OFF
ON ON
ON OFF
OFF ON
OFF OFF
ON ON
OFF ON
ON OFF
OFF OFF
DIL2 (Front 3-pole)
It210_01a_oi_e.docx / Jan-20
www.hohner-elektrotechnik.de
Configuration
5
6
7
8
Level for HTL Single Ended: U
> 14V
Level for HTL Single Ended: U < 5V / U >
9V
Input format: TTL
Input format: HTL Single Ended
Input format: RS-422
Input format: HTL Differential
Z-pulse length: 1 Z-Puls, independent of A
/ B
Z-pulse length: ynchronized with AOUT /
BOUT
Z-pulse length: synchronized with AIN /
BIN
Z-pulse length: 1 Z-Puls, a depending on
A/B
ON
Input Mode : A/B Dir (Pulse / Direction)
OFF
Input Mode : A/B 90°
ON
Output Mode : A/B Dir (Pulse / Direction)
OFF
Output Mode : A/B 90°
ON ZERO_A : Zero setting delayed, no errors
ZERO_A : Zero setting immediately, error
OFF
possible
Configuration
Function
< 10V / U
L
Page 9 / 21
H
10

Advertisement

Table of Contents
loading

Table of Contents