Information: Tools Required; Step 1 - Mount Shelf; Step 2 - Connect Chassis Ground; Step 3 - Connect Ac Input - ABB J2007003L051C-52C Quick Start Manual

Sps -48v slimline power shelf
Table of Contents

Advertisement

Information: Tools Required

Wire cutters and strippers
Cable crimpers
Step 1 – Mount Shelf
1.
Reposition mounting ears as required - 4 screws each.
Torque to 25 in-lb (2.8Nm) - Phillips screwdriver.
2.
Install Inter-Shelf brackets between adjacent shelves (optional).
Torque to 25 in-lb (2.8Nm) - Phillips screwdriver.
3.
Attach shelf to the frame using a minimum of four screws
(two on each side) - 12-24 (provided).
Torque to 35 in-lb (4Nm) - 5/16" socket.
Step 2 – Connect Chassis Ground
Lug Landings: #10 double-hole on 5/8-inch center
(lugs not provided)
Some applications may rely on frame mounting screws for
shelf ground omitting the chassis ground cable.
Minimum 10 AWG wire is recommended.
Torque 10-32 screws to 30 in-lb (3.4Nm) - 5/16" socket.
Step 3 – Connect AC Input
Connect AC to the detachable input terminal block in wiring
box. Knockout for 3/4" conduit or cord grip.
Cords available - See Slimline Power System Brochure.
External Feed Protector - See Information: Rectifier Options.
V
− 120V~ / 200-240V~, 50-60Hz
AC
Wire size: 10 – 12AWG Recommended (12-24AWG range)
Strip − 0.3" (7mm)
Torque − 4.4 in-lb. (0.5Nm)
Pull on wires to verify connection.
Danger:
Turn OFF and lock-out tag-out the AC source before making AC connections.
Follow all local and national wiring rules.
Caution:
Route AC cables to avoid contact with sharp or rough surfaces that may damage insulation and cause a
short circuit.
Page 7
2023 ABB. All rights reserved.
Torque wrench - 0-65 in-lb (0-10Nm)
Sockets - 5/16", 7/16, etc.
SPS Shelf L051C_L052C_QSG
Screwdrivers - Philips #1 and #2, Flat small
2 Adjacent
Shelves
Inter-Shelf Bracket
Chassis Ground
Mounting Ears
AC Wiring Box
Knockout
Rev 5.0