Midea CPA-09B Installation Manual page 20

Middle static pressure duct type air conditioner
Table of Contents

Advertisement

Step 3: Flare pipe ends
Proper flaring is essential to achieve an
airtight seal.
1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign
materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe.
Make sure they are facing in the right
direction, because you can't put them on
or change their direction after flaring.
See Fig. 7.6
Flare nut
Copper pipe
Fig. 7.6
4. Remove PVC tape from ends of pipe when
ready to perform flaring work.
5. Clamp flare form on the end of the pipe.
The end of the pipe must extend beyond
the flare form.
Flare form
Fig. 7.7
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool
clockwise until the pipe is fully flared.
Flare the pipe in accordance with the
dimensions shown in table 7.5.
Table 7.5: PIPING EXTENSION BEYOND FLARE FORM
Pipe
gauge
Ø 6.4
Ø 9.5
Ø 12.7
Ø 15.9
Ø 19.1
Ø 22
8. Remove the flaring tool and flare form, then
inspect the end of the pipe for cracks and
even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first,
then connect it to the outdoor unit. You should
first connect the low-pressure pipe, then the high-
pressure pipe.
1. When connecting the flare nuts, apply a thin
coat of refrigeration oil to the flared ends of
the pipes.
2. Align the center of the two pipes that you
will connect.
Pipe
Indoor unit tubing
3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque
wrench to tighten the flare nut according to
the torque values in table 7.5.
Tightening
Flare dimension (A)
torque
(Unit: mm/Inch)
Min.
Max.
18-20 N.m
8.4/0.33
8.7/0.34
(183-204 kgf.cm)
25-26 N.m
13.2/0.52
13.5/0.53
(255-265 kgf.cm)
35-36 N.m
16.2/0.64
16.5/0.65
(357-367 kgf.cm)
45-47 N.m
19.2/0.76
19.7/0.78
(459-480 kgf.cm)
65-67 N.m
23.2/0.91
23.7/0.93
(663-683 kgf.cm)
75-85N.m
26.4/1.04
26.9/1.06
(765-867 kgf.cm)
Flare nut
Fig. 7.9
Flare shape
90 ° ± 4
A
R0.4~0.8
Fig. 7.8
Pipe
Page 21