To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat against terminals and fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard electrical junction boxes.
Set the desired address via D.I.L. switch on the back of the detector. Please refer to D.I.L. Switch Configuration and Address Settings sections. Allign detector components using provided allignment marks on both the head and base. Allign detector mark and short allignment mark on base. Fit the detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit and activate the detection loop. Test the detectors as described below.
All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at the conclusion of testing.
SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector's smoke chamber for at least 10 seconds. When sufficient smoke has entered, the detector will signal an alarm. This will be indicated by the illumination of the 2 RED LEDs provided. Make sure to clear smoke out of the chamber before resetting in order to keep the detector at its current sensitivity setting.
HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65ºC and 80ºC. This requirement can be met by some domestic hair dryers. Switch on the warm airflow and check that the temperature is correct and stable. From a distance of several cms, direct the airflow at the guard protecting the thermistor. The detector should alarm within 60 seconds. Upon alarm immediately remove the heat source and check that the RED LEDs of the detector are illuminated. If a detector fails to activate within 60 seconds, confirm connections and programming. If necessary replace unit.
Note: After testing, check that the system is returned to normal operation. Notify the appropriate authorities that the testing procedure has been completed and the system is active again.
The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low power vacuum cleaner. >> DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR
Note: Positive terminal of remote indicator should be connected to terminal 4 (+ Loop IN/ OUT)
Switches 1-7 used to configure the module's address
Switch 8 Not used
Address Switches binary weights
1 on =1
2 on =2
3 on =4
4 on =8
5 on =16
6 on =32
7 on = 64
To lock detector remove pin available at terminal 4 on the underside of the sounder using a small screwdriver.
To unlock detector from its base push unlock key provided through hole available on the base side wall as shown.
SUPPLY VOLTAGE | Loop Powered - 17V to 30V DC |
CURRENT - QUIESCENT / SURGE | 450 uA max. |
CURRENT - DEVICE IN ALARM | 4 mA - Alarm LED Iluminated |
SENSITIVITY | According to EN54-5 and EN54-7 |
CABLE SIZE | 0.5-2.5 mm² |
RESET/STAR-UP TIMES | 20 seconds max. |
COLOUR / CASE MATERIAL | White / ABS |
OPER. TEMPERATURE / MAX. HUMIDITY | -10ºC to 50ºC / 95% RH Non-Condensing |
DIMENSIONS / WEIGHT | 100 mm (D) x 50 mm (H) inc. base / 144 g inc. base |
ORDER CODE | DESCRIPTION |
ZEOS-AD-S | Analogue Addressable Photoelectric Smoke Detector |
ZEOS-AD-H | Analogue Addressable Temperature/Heat Detector |
ZEOS-AD-SH | Analogue Addressable Combined Smoke & Heat Detector |
ZEOS-AD-SI | Analogue Addressable Photo. Smoke Detector inc. Isolator |
ZEOS-AD-HI | Analogue Addressable Heat Detector inc. Isolator |
ZEOS-AD-SHI | Analogue Addr. Combined Smoke & Heat Detector w/ Isolator |
Global Fire Equipment S.A. declares that this product is free from defects in materials and workmanship and it will repair or replace any product or part thereof which proves to be defective in workmanship or materials during the life expectancy of the product. This period is determined to be no longer than 10 years starting from the date of manufacture. Please visit Global Fire Equipment's web site (www.globalfire.pt) for a full description of Global Fire Equipment's LIMITED WARRANTY, which, among other things, limits the duration of warranties of merchantability and fitness for a particular purpose and excludes liability for consequential damages. Acceptance of order and/ or original invoice which will become part of your sales agreement. Please contact Global Fire Equipment's web site for details on how to obtain a return Merchandise Authorization Number (RMA) before returning goods to the factory. Shipment must be prepaid and Global Fire Equipment will repair or replace your returned detector.
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL
Tel: +351 289 896 560 • Sales: sales@globalfire.pt • Technical Support: techs@globalfire.pt • www.globalfire.pt
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Global Fire ZEOS-AD Series - Analogue Addressable Fire Detector Manual