Bryant 821T Installation, Start-Up, Operating And Service And Maintenance Instructions page 30

Variable--speed, ecm induced--combustion, 2--stage 4-way multipoise, non-condensing gas furnace
Table of Contents

Advertisement

Table 8 – Minimum Allowable Input Rating of
Space- -Heating Appliance in Thousands of Btuh per Hour
INTERNAL AREA OF CHIMNEY
VENT HEIGHT
FT. (M)
12
(7741)
Local 99% Winter Design Temperature: 17 to 26 degrees F
6
0
8
52
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design Temperature: 5 to 16 degrees F*
6
NR
8
NR
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design Temperature: --- 10 to 4 degrees F*
6
NR
8
NR
10
NR
15
NR
20
NR
30
NR
Local 99% Winter Design Temperature: --- 11 degrees F or
Not recommended for any vent configuration.
*The 99.6% heating (db) temperatures found in the 1997 or 2001
ASHRAE Fundamentals Handbook, Climatic Design Information chapter,
Table 1A (United States) and 2A (Canada) or the 2005 ASHRAE Funda-
mentals handbook, Climatic Design Information chapter, and the CD ---
ROM included with the 2005 ASHRAE Fundamentals Handbook.
Air for combustion must not be contaminated by halogen
compounds which include chlorides, fluorides, bromides, and
iodides. These compounds are found in many common home
products such as detergent, paint, glue, aerosol spray, bleach,
cleaning solvent, salt, and air freshener, and can cause corrosion
of furnaces and vents. Avoid using such products in the
combustion- -air supply. Furnace use during construction of the
building could cause the furnace to be exposed to halogen
compounds, causing premature failure of the furnace or venting
system due to corrosion.
Vent dampers on any appliance connected to the common vent
can cause condensation and corrosion in the venting system. Do
not use vent dampers on appliances common vented with this
furnace.
SQ. IN. (SQ. MM)
19
28
38
(12258)
18064)
(24516)
55
99
141
74
111
154
90
125
169
NR
167
212
NR
212
258
NR
NR
362
78
121
166
94
135
182
111
149
198
NR
193
247
NR
NR
293
NR
NR
377
NR
145
196
NR
159
213
NR
175
231
NR
NR
283
NR
NR
333
NR
NR
NR
lower
Additional Venting Requirements
A 4- -in. (102 mm) round vent elbow is supplied with the furnace.
A 5- -in. (127 mm) or 6- - in. (152 mm) vent connector may be
required for some model furnaces. A field- -supplied 4- -in. (102
mm) to 5- -in. (127 mm) or 4- -in. (102 mm) to 6- -in. (152 mm)
sheet metal increaser fitting is required when 5- -in. (127 mm) or
6- -in. (152 mm) vent connector is used. See Fig. 36 - - 48, Venting
Orientation for approved vent configurations.
NOTE: Vent connector length for connector sizing starts at
furnace vent elbow. The 4- -in. (102 mm) vent elbow is shipped
for upflow configuration and may be rotated for other positions.
Remove the three screws that secure vent elbow to furnace, rotate
furnace vent elbow to position desired, reinstall screws. The
factory- -supplied vent elbow does NOT count as part of the
number of vent connector elbows.
The vent connector can exit the furnace through one of five
locations on the casing.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses and
gloves when handling parts, and servicing furnaces.
1. Attach the single wall vent connector to the furnace vent
elbow, and fasten the vent connector to the vent elbow
with at least two field- -supplied, corrosion- -resistant, sheet
metal screws located 180_ apart.
NOTE: An accessory flue extension is available to extend from
the furnace elbow to outside the furnace casing. See Product Data
Sheet for accessory listing. If flue extension is used, fasten the
flue extension to the vent elbow with at least two field- -supplied,
corrosion- -resistant, sheet metal screws located 180_ apart. Fasten
the vent connector to the flue extension with at least two
field- -supplied, corrosion resistant sheet metal screws located
180_ apart.
2. Vent the furnace with the appropriate connector as shown
in Fig. 36 - - 48.
3. Determine the correct location of the knockout to be re-
moved.
4. Use a hammer and screwdriver to strike a sharp blow
between the tie points and work the slug back and forth
until the slug breaks free.
An accessory Vent Guard Kit is REQUIRED for downflow
applications for use where the vent exits through the lower
portion of the furnace casing. Refer to the Vent Guard Kit
Instructions for complete details. See Product Data Sheet for
accessory listing.
30

Advertisement

Table of Contents
loading

This manual is also suitable for:

820taA series

Table of Contents