810SA/811SA: Installation, Start–Up, Operating and Service and Maintenance Instructions
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used
(see
Fig.
12). Install field-supplied, 5/16 x 1-1/2 in. (8 x 38 mm) (max)
corrosion-resistant machine bolts, washers and nuts.
5/ 16
(8mm)
3
1
/
4
(44mm)
(8mm)
5
/
16
(44mm)
3/ 4
1
(44mm)
Fig. 12 – Leveling Legs
NOTE: Bottom closure must be used when leveling legs are used. It
may be necessary to remove and reinstall bottom closure panel to install
leveling legs. To remove bottom closure panel, see Item 1. in Bottom
Return Air Inlet section.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom
corner of furnace (see
Fig.
2. For each leg, install nut on bolt and then install bolt and nut in hole.
(Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer
if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut
to secure arrangement.
5. Reinstall bottom closure panel if removed.

LOCATION RELATIVE TO COOLING EQUIPMENT

The cooling coil must be installed parallel with, or on the downstream
side of the unit to avoid condensation in the heat exchangers. When
installed parallel with the furnace, dampers or other flow control must
prevent chilled air from entering the furnace. If the dampers are
manually operated, they must be equipped with means to prevent
operation of either unit unless the damper is in the full-heat or full-cool
position.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle
iron or metal plumber's strap as shown (see
angle iron to bottom of furnace as shown. Heavy-gauge sheet metal
straps (plumber's straps) may be used to suspend the furnace from each
bottom corner. To prevent screws from pulling out, use 2 #8 x 3/4-in. (19
mm) screws into the side and 2 #8 x 3/4-in. (19 mm) screws in the
bottom of the furnace casing for each strap (see
the screws are attached to ONLY the furnace sides and not the bottom,
the straps must be vertical against the furnace sides and not pull away
from the furnace sides, so that the strap attachment screws are not in
tension (are loaded in shear) for reliable support.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
(8mm)
5/ 16
3
1
/
4
(44mm)
(8mm)
5/ 16
3/ 4
1
12).
Fig. 14
and
Fig.
15). Secure
Fig. 14
and
Fig.
Platform Furnace Support
Construct working platform at location where all required furnace
clearances are met (see
mm) clearance requirement on side, set furnace on noncombustible
blocks, bricks or angle iron. For crawl space installations, if the furnace
is not suspended from the floor joists, the ground underneath furnace
must be level and the furnace set on blocks or bricks.
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
SEDIMENT
TRAP
Fig. 13 – Typical Attic Installation
A89014
OUTER DOOR
ASSEMBLY
8" (203mm) MIN
FOR DOOR REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
Fig. 14 – Horizontal Unit Suspension
15). If
Fig. 15 – Horizontal Suspension with Straps
10
Fig. 1
and
Fig.
13). For furnaces with 1-in. (25
GAS
TYPE-B
ENTRY
VENT
m m )
( 1 5 2
I N *
6 " M
30-IN. (762mm)
MIN WORK AREA
"
3
(451mm)
17
/
4
SHEET
METAL
22"
UNION
1
" (6mm) THREADED ROD
/
4
4 REQ.
1" (25mm) SQUARE, 1-1/4"x1-1/4"x1/8" (32x32x3mm)
ANGLE IRON OR UNI-STRUT MAY BE USED
METHOD 1
FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH
(4) #8 x 3/4 (19 mm) SHEET METAL SCREWS
(2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
" (451mm)OVERALL
3
17
/
4
" (121mm) UNDER DOOR
4
3
/
4
1" (25mm) UNDER FURNACE
EXTEND OUT 12" (305mm)
FROM FACE OF DOOR
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
A10164
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3
3 #8 x
/
" (19mm) SCREWS
4
TYPICAL FOR 2 SUPPORTS
A10130
METHOD 2
USE (4) #8 x 3/4 (19 mm) SHEET
METAL SCREWS FOR EACH
STRAP. THE STRAPS
SHOULD BE VERTICAL
AGAINST THE FURNACE
SIDES AND NOT PULL AWAY
FROM THE FURNACE
SIDES.
A10131