Mitsubishi Electric MUZ-JP09WA-U1 Service Manual page 35

Table of Contents

Advertisement

M How to check miswiring and serial signal error
MUZ-JP09/12WA
Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND
VOLTAGE" in the outdoor service manual.)
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-sec-
ond-ON quick blinking"? 3
Turn OFF the power supply.
Remove the bridge between the outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there rated voltage between the indoor terminal block S1 and S2?
<Confi rmation of power voltage>
Is there amplitude of 10 to 20 V DC between the indoor terminal block
S2 and S3? <Confi rmation of serial signal>
A
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
• Reinstall
either the unit
or the light
away from
Is serial signal
each other.
• Attach a fi lter
error indicated 6
No
on remote
minutes later?
control receiv-
Yes
ing section
of the indoor
unit.
B
OBH821A
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Yes
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the OPERATION INDICATOR lamp light
up? <Confi rmation of the power to the indoor
unit>
Yes
Is serial signal error indicated 6 minutes later?
Yes
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and
S3. 1
Turn ON the power supply.
Yes
Yes
Yes
Yes
Is there 2 V DC or less between CN10A (+)
and JPG (GND)(-) on the indoor electronic
control P.C. board?
Yes
Is there 2 V DC or less between
CN10A (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
Replace the indoor power
P.C. board and the indoor
terminal P.C. board
35
Check the power supply.
No
No
Is there any miswiring, poor
contact, or wire disconnec-
tion of the indoor/outdoor
No
connecting wire?
1. Miswiring may damage indoor electronic control P.C.
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board is normal, LED blinks 6 times after 3
minutes.
Replace the inverter P.C. board. 2
No
(Lighted
2. Be careful of the residual voltage of smoothing
or not
lighted)
Check the wiring
If there is any error of the indoor/outdoor connecting wire:
such as the damage of the wire, intermediate connection,
No
and/or poor contact to the terminal block, replace the indoor/
outdoor connecting wire.
No
No
Is there 2 V DC or less between
CN10A (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
No
Yes
Replace the indoor elec-
tronic control P.C. board.
No
Check the wiring.
Correct them.
Yes
No
Check of power supply.
(Refer to 10-5. .)
No
capacitor.
Yes
No