IBC MVE2 Series Quick Start Manual

IBC MVE2 Series Quick Start Manual

Globe valves actuators

Advertisement

Quick Links

MVE2xx
Globe Valves Actuators
FORCE
MODEL
[N]
MVE204
400
MVE206
600
230 V AC
MVE210
1000
MVE215
1500
MVE222
2200
MVE204S
400
MVE206S
600
230 V AC
MVE210S
1000
MVE215S
1500
MVE222S
2200
APPLICATION AND USE
MVE2xx is a flexible electro-mechanical actuator for the control of two and three way globe valves in:
heating and cooling systems
Air Handling Units
district heating plants
industrial temperature control systems.
MVE2xx can be controlled either by a proportional (modulating) signal or by an increase/decrease (Floating) signal.
It is easy to mount and connect the actuator. Direct mounting is possible to any iSMA CONTROLLI flanged valve. Linkage kits are avai-
lable for iSMA CONTROLLI threaded valves as well as for valves of other manufacturers (table page 3).
The actuator has a fine resolution (500 steps on the full stroke range) for exacting fluid control and it is able to self-calibrate on a
different stroke without the need of any user action (this function is DIP switch selectable on the field).
MVE2xx has intelligent behaviour and alarm functionality in case of unexpected operation, feedback of alarms to the user is provided
by LEDs (GREEN and RED) on the control board.
N.B.: Do not use the actuator if not coupled with its relating valve.
TECHNICAL CHARACTERISTICS
DESCRIZIONE
Supply voltage F N
Power consumption (running)
Power consumption (holding)
Modulating
Running
time
Increase/decrease
Stroke
Force
Duty cycle
Analogue input Y M
Digital inputs Y1 Y2
Output V+
The performances stated in this sheet can be modifi ed without any prior notice.
DISTRIBUTION PARTNER:
POWER
DESCRIPTION
SUPPLY
Long yoke, modulating/
±10%
floating control
Short yoke, modula-
±10%
ting/floating control
MVE204
MVE204S
10 VA/4,5 W
8 VA/4 W
15 s (for valves with stroke from 5 to 15 mm)
20 s (for valves with stroke from 15 to 25 mm)
30 s (for valves with stroke from 25 to 60 mm)
400 N
Voltage 0-10 V - impedance > 100 kΩ (range: 0-10 V DC, 2-10 V DC, 0-5/2-6 V DC, 5-10/6-10 V DC)
www.ismacontrolli.com
sales@ibc.ie (ROI/INTL.)
bill@ibc.ie (NI/UK)
MVE206
MVE210
MVE206S
MVE210S
230 V AC ±10%, 50-60 Hz
13 VA/6 W
18 VA/8 W
11 VA/5 W
11 VA/5 W
60 s
5-60 mm (limited to 30 mm for MVE.S)
600 N
1000 N
max 50%/60 minutes
500 Ω (range 4-20 mA)
Connection of Y1, Y2 to M
Voltage 16 V DC ± 0,5 V, max load 25 mA,
DBL394en | 1
MVE215
MVE215S
MVE222S
21 VA/11 W
25 VA/10 W
13 VA/7 W
10 VA/4 W
(for valves with
stroke from 5 to
1500 N
Issue rev. 8 | 07/2022
st
MVE222
60 s
60 mm)
2200 N
page 1

Advertisement

Table of Contents
loading

Summary of Contents for IBC MVE2 Series

  • Page 1 MVE2xx DISTRIBUTION PARTNER: sales@ibc.ie (ROI/INTL.) bill@ibc.ie (NI/UK) Globe Valves Actuators FORCE POWER MODEL DESCRIPTION SUPPLY MVE204 MVE206 230 V AC Long yoke, modulating/ MVE210 1000 ±10% floating control MVE215 1500 MVE222 2200 MVE204S MVE206S 230 V AC Short yoke, modula-...
  • Page 2: Operation

    MVE204 MVE206 MVE210 MVE215 MVE222 DESCRIZIONE MVE204S MVE206S MVE210S MVE215S MVE222S Output U Voltage 2-10 V DC (0-100%), max load 2 mA Room temperature Operation -10°C to 55°C; storage -20°C to 55°C Room humidity Max. 90% R.H. Protection degree IP54 (with PG13,5 cable gland - not supplied) Insulation class Emission/Immunity EMC 2014/30/UE according to EN 61326-1:2013 standard Standard...
  • Page 3: Maintenance

    DMVE CLOSING RELAY OPENING RELAY K2 KC1 K3 K4 KC2 Diagnostic The actuator is provided with a self diagnostic algorithm able to detect faulty conditions: • stroke calibration out of range 5-60mm; • unexpected stall condition (e.g. valve stuck or extra stroke due to actuator link loose); •...
  • Page 4: Electrical Connections

    ACCESSORIES DMVE End point auxiliary switches GMVE Thermal insulation for MVE actuators * GMVES Thermal insulation for MVE.S actuators * KIT-P13.5 10 cable glands kit (nuts and gaskets included) KIT-T13.5 Kit 10 caps for cable glands hole (nuts and gaskets included) Stem heater 24 V, 50 W (suggested when the fluid temperature is below 0°C) * * It is not possible to install both thermal insulation (Gxxxx) and stem heaters.
  • Page 5: Terminal Block

    TERMINAL BLOCK M Y1 Y2 230~V ±10% Floting only sink (connect Y1, Y2 to M) (*) In order to use the floating control the only possible connection is * Floting only sink (connect Y1, Y2 to M) between terminal M and Y1/ Y2.
  • Page 6: Wiring Diagrams

    WIRING DIAGRAMS 3 point floating control Modulating control (0-10 V DC) Modulating Control (0-10Vcc) 3-point Floating Control 230 V AC 230V AC Controller Controller Open Y1 F Close Command + Command - Neutral Neutral DIP SWITCHES SETTINGS Set the DIP switches according to tables below. Power down and power up again the actuator or act on the manual override handle to be sure that settings will be recognized.
  • Page 7 DIAGNOSTIC - ALARM FUNCTIONS ACTUATOR BEHAVIOUR TYPICAL LEDS ACTUATOR TROUBLE RESET N° ERROR AUTOMATIC CALIBRA- BEHAVIOUR SHOOTING PROCEDURE MANUAL CALIBRATION TION (DIP N. 7 ON) CONDITION (DIP N. 7 OFF) The actuator pushes/ pulls 2 times (unexpected The actuator pushes/pulls stall) trying to remove the 2 times against endpoint possible obstacle.
  • Page 8 Manual control ON, the actuators ignores the control signal. RED GREEN ON ATTENTION! The electronic board is electrically supplied DIMENSIONS [mm] DISTRIBUTION PARTNER: sales@ibc.ie (ROI/INTL.) iSMA CONTROLLI S.p.A. - Via Carlo Levi 52, 16010 Sant’Olcese (GE) - Italy | bill@ibc.ie (NI/UK) support@ismacontrolli.com www.ismacontrolli.com DBL394en | 1 Issue rev.

This manual is also suitable for:

Mve204Mve204sMve206Mve206sMve210Mve210s ... Show all

Table of Contents