Maintenance work
6
Check that the condensate pipe is in good condition, that it is leak-tight
and that the drain is correct
7
Check whether all of the externally routed condensate pipes are dimen-
sioned correctly and have been insulated sufficiently (frost protection)
8
Check whether the gas flow rate corresponds with the specifications on
the data plate and lies within the tolerances specified in these instructions
9
If the gas flow rate lies outside of the tolerances specified in these in-
structions, eliminate the fault in accordance with the regulations and the
current technology
10
Check the general condition of the product and, if required, eliminate any
faults that are found
11
Checking the control electrode using the O
12
Carry out the combustion analysis: Measure the CO content, O₂ content
and the CO/O₂ ratio.
13
Check the product's recirculation at the supply air test point on the air/flue
pipe. If required, inspect the entire air/flue system and, if necessary, cor-
rect the fault
14
Disconnect the product from the electrical installation
15
Check and, if required, correct the electrical installation
16
Removing dirt from the product and the vacuum chamber
17
Visually checking the condition of the heat cell, checking for corrosion,
rust or damage
18
Check that the gas isolator cock and service valves function correctly
19
Check the quality of the heating water: Clarity (clouding), correct inhibitor
and pH value
20
Removing the compact thermal module
21
Check the burner for damage
22
Replacing the control electrode
23
Checking the insulating mats in the combustion area and replacing dam-
aged insulating mats
24
Cleaning the heat exchanger
25
Cleaning the condensate siphon
26
Filling the condensate siphon
27
Installing the compact thermal module
28
Checking and, if required, supplementing the pre-charge pressure for the
internal expansion vessel
29
Checking the pre-charge pressure in the shift-load cylinder expansion
vessel
30
Cleaning the strainer in the cold water inlet
31
Check the impeller sensor for dirt/damage
32
If the water volume is insufficient (domestic hot water) or the outlet tem-
perature is insufficient, check the secondary heat exchanger
33
Reassemble the product
34
Opening the service valves
35
Filling the heating installation
36
Run the test operation on the product/heating installation including hot
water generation (if available) and, if required, purge the product/heating
installation
37
Cleaning the protection kit, if available
38
Completing inspection and maintenance work
39
Re-checking the O₂ content (the air ratio)
40
Check the product for gas, flue gas, water and condensate leaks
0020308121_04 Installation and maintenance instructions
content
2
Interval
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
At regular intervals
At regular intervals
If required, at least every
5 years or 20,000 operating
hours (whichever comes first)
At regular intervals
At regular intervals
Annually
Annually
At regular intervals
At regular intervals
Annually
At regular intervals
At regular intervals
At regular intervals
After each time maintenance
work is carried out
Annually
At regular intervals
Annually
Annually
Annually
If required, at least every
2 years
Annually
46
59
48
49
37
47
49
50
36
50
63