This Quick Start Guide provides a general overview for basic installation. For more in-depth information and troubleshooting steps, please refer to the full Operator's Guide for your meter.
INSTALLATION OVERVIEW
1
1.
Remove covers
Loosen top cover screws (x4) [Note: Screws are captured
in the case.] Remove the High Voltage Cover Screws (x2).
[Note: These screws are NOT captured; do not lose.]
x2
x4
4
4.
Connect AC voltage wires
WARNING: RISK OF ELECTRIC SHOCK. DO NOT
ENERGIZE METER WITH VOLTAGE COVER REMOVED.
FOLLOW ALL STATE AND FEDERAL ELECTRICAL
CODES.
▪ Using 14 AWG THHN, 600VAC rated wire, connect the
voltage leads (L1, L2, L3, and N) as necessary to the
meter through a dedicated disconnect or circuit breaker.
DO NOT EXCEED 346V L-N or 600V L-L.
▪ Mark the circuit breaker as "PowerScout Meter"
VIN1
WIRING
HIGH VOLTAGE MAY BE PRESENT. RISK OF ELECTRIC SHOCK. LIFE THREATENING
VOLTAGE MAY BE PRESENT. QUALIFIED PERSONNEL ONLY.
i
These diagrams show the wiring configuration for the Service Types available in the
Service drop-down list under "Meter Setup; Service " in ViewPoint HD Software.
The PowerScout HD Meter is internally powered through
i
the voltage between L1 and L2. For Single Phase
installations, where no L2 exists, connect a jumper from N
to L2. This connection provides power to the meter while
maintaining Neutral as the metering voltage reference.
i
The PowerScout HD Meter uses the Neutral terminal as a voltage reference. For
systems without a neutral conductor, connect a wire from the N terminal to ground.
CONNECTING VOLTAGE WIRING AND CTs TO THE METER
This image shows how to connect CTs to the PowerScout HD Meter for Three Phase services. For
other service types (Single Phase and Split Phase), see the Operator's Guide. Three Phase loads are
shown on the left only for illustration and may be used on the right as well. All meter elements are fully
configurable and interchangeable.
© DENT Instruments, Inc.
PowerScout™ 12/24/48 HD
Multi-Circuit Power Meter
Quick Start Guide
FOR QUALIFIED PERSONNEL ONLY
2
2.
Mount
Use the enclosure as a template to mark mounting
holes
Note: Mechanical specifications and drawings are
found in the Operator's Guide.
5
5.
Re-attach high voltage cover
Meter is IP30 (TouchSāf™) with internal cover installed.
VIN2
N
N
L1
L2
www.DENTinstruments.com
#8 Fastener
x4
Not Provided
EXAMPLE 1
Wiring the PowerScout in a 3-Wire, Split Phase Service Panel
TYPICAL LOADS:
Single Phase L1-N or L2-N 110 VAC: Lighting, Appliance, or Living Zone
Single Phase L1-L2 220 VAC: Water Heater or Equipment with no Neutral wire.
Split Phase L1-L2 220 VAC: Service Entrance, Dryers, or Equipment with Neutral wire.
3-Wire, 1-Phase
used on MAINS
L1-N, L2-N
RōCoil CTs Shown
L3
Single Phase
110 VAC Plug Loads
L1-N or L2-N
Split Core CTs Shown
EXAMPLE 2
Wiring the PowerScout in a 4-Wire, 3-Phase Service Panel
4-Wire, 3-Phase
Mains Monitoring
L1-N, L2-N, L3-N
RōCoil CTs Shown
Single Phase
Branch Load
L1-N
4-Wire, 3-Phase
WYE Load with
Neutral Current
L1-N, L2-N, L3-N
1.800.388.0770 ■
3
3.
Connect
▪ Attach 1" EMT Conduit fittings (or reducer bushing)
▪ Attach flexible Conduit
▪ Plug unused holes with blanking plugs (provided)
Communication Wiring
Current
Transformers
Power Wiring
6
6.
Connect CT & communications wiring
Use only 333.3mV (1/3 V) output CTs or DENT RōCoils.
Ethernet
White (+)
Black or Brown (-)
Bare (RŌCoil) (S)
METER DISCONNECT
METER DISCONNECT
support@DENTinstruments.com
Rev060120
USB
RS-485
Connect the Neutral
wire to VIN 1, N
terminal on the
PSHD Meter
Meter is powered
from L1 to L2 on the
VIN 1 connector
Label as Meter
Disconnect
Single Phase
220 VAC Load
L1-L2
3-Wire, 1-Phase
Split Load
L1-N, L2-N
Connect the Neutral
Wire to the VIN 1
Neutral Terminal on
the PSHD Meter
Meter Power
Connect All Phases to
the VIN 1 Terminals
Label as Meter
Disconnect
3-Wire, 3-Phase
DELTA Load
No Possibility of
Neutral Current
Two CTs on L1 and L3