Compressor Startup Error, Compressor Lock Error, Compressor Rotation Error - Samsung AJ009JNNDCH/AA Service Manual

Multi air conditioner
Table of Contents

Advertisement

4-5-4 Compressor startup error, Compressor Lock error, Compressor rotation error.

1. Check items
1) Are the power supply and compressor connecting wires connected correctly?
2) Is the inter-phase resistance of the compressor normal?
2. Check procedure
4-30
Checking Comp Resistance ( Normal value )
U-V
AJ020JCJ2CH
0.5~1.1Ω
AJ024JCJ3CH
0.2~0.6Ω
AJ036JCJ5CH
0.1~0.5Ω
V-W
W-U
0.5~1.1Ω
0.5~1.1Ω
0.2~0.6Ω
0.2~0.6Ω
0.1~0.5Ω
0.1~0.5Ω