Page 1
Shiel A-XT Releasing Fire Control Panel ® Installation and Operation Manual Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 Issue Date: 5/2/2012...
Page 2
Underwriters Laboratories (UL) File number (S 8485) Fire Alarm Equipment Shield Fire, Safety and Security Ltd. The model series of the Shield A-XT Releasing Fire Control Panel is suitable as follows: • Local Signaling Unit, Cross Zone and Releasing •...
Page 3
This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Field Terminals ............. 16 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM...
Page 6
Reset ..............47 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM...
Page 7
Mode Select Key Switch ........... . 59 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM...
Page 8
Physical Specifications ............77 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM...
Page 9
Emergency Contact............112 Appendix E UL Compliance Label Appendix F UL 864 Permitted Configurations Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Page 10
Introduction Section 1 Introduction Shield Figure 1-1 Shield A-XT Releasing Fire Control Panel Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 1 of 127...
Introduction Using This Manual The following sections provide instructions for installing, testing and troubleshooting the Shield A-XT Releasing Fire Control Panel: Section 1 Introduction provides document conventions, the technical help-line, repair and return information. Section 2 Overview provides a summary features of the Shield A-XT Releasing Fire Control Panel.
Damaged Goods In the event of damage to equipment during transit or any defect in the quality of goods, the Buyer shall Notify Shield within seven days of delivery.The goods may then be returned to the Customer Service Department of Shield for repair, or replacement parts may be supplied (by arrangement).
Returned equipment will be held awaiting authorisation for a period not exceeding 60 days from the date of quotation. After this period, Shield reserves the right to dispose of these items or return them.
Shield are under no liability if the repaired or replaced components are found to have failed due to fair wear and tear, willful damage, negligence, abnormal working conditions, misuse or alteration or repair without approval or failure to follow the sellers instructions.
Section 2 Overview The Shield A-XT Releasing Fire Control Panel is a co nventional re control panel and releasing system. The re control panel provides connections for Detection Zones, Noti cation Appliance Circuits (NACs), Releasing Circuits, Relay Outputs, Status Units and AUX 24 V power.
Page 16
TROUBLE RELAY. Interconnected status units Interconnected status units are provided with a limited set of indicators and functions compared with those provided on the Shield A-XT Releasing Fire Control Panel. Status unit functions are non-configurable on the fire control panel.
Overview Hardware Features The figure below illustrates hardware features of the Shield A-XT Releasing Fire Control Panel: Figure 2-2 Hardware Features FUSE AL FLT REMOTE DATA POWER NAC1 NAC2 ZONE 1 ZONE 2 ZONE 3 NAC3 1ST STAGE 2ND STAGE MODE MAN.
Overview Internal Power Supply The internal power supply of the Shield A-XT Releasing Fire Control Panel meets UL 864, 9th edition and provides a 2 Amp, linear power-source for operating FACP functions as well as charging the standby batteries. The 2 Amp power supply operates 115 VAC and 230 VAC models of the Shield A-XT Releasing Fire Control Panel.
Overview Panel Controls and Indicators The fascia of the Shield A-XT Releasing Fire Control Panel is divided into sections for controls and indicators. The figure below illustrates controls and indicators of the Shield A-XT Releasing Fire Control Panel: Figure 2-3...
Page 20
Overview The table below describes upper controls of the Shield A-XT Releasing Fire Control Panel: Controls Modes Releasing Key-Switch Provides key-switch modes for automatic & manual or manual-only release Manual Extinguishant Provides manual release as a push button Release Central Controls...
Access Level 3. Indicators The front-panel of the Shield A-XT Releasing Fire Control Panel provides upper, central and lower indicators. Upper Indicators The figure below illustrates upper indicators of the Shield A-XT Releasing Fire Control Panel:...
Page 22
Overview The table below describes upper LED indicators of the Shield A-XT Releasing Fire Control Panel: General System Status LED Color Fire, NAC Output State Flashing = NACs Activated ON Continuous = NACs silenced OFF = Panel and NACs Reset...
Page 23
(+10) (+1) The central indicator is the System Mode display of the Shield A-XT Releasing Fire Control Panel. The System Mode display contains three seven segment LEDs. Use this indicator to identify status conditions and to program configurations on the fire control panel.
Page 24
Overview Lower Indicators The figure below illustrates the lower indicators of the Shield A-XT Releasing Fire Control Panel: Figure 2-9 Lower Indicators Mains Aux.24V Batt. Comms Earth Sys.Fuse NAC1 NAC2 NAC3 Exting. Abort Man.Rel. Mode Release Tell Trbl. Trbl. Fail Trbl.
Overview Field Terminals The figure below illustrates field terminals of the Shield A-XT Releasing Fire Control Panel: Figure 2-10 Field Terminals AL FLT REMOTE DATA POWER NAC1 NAC2 ZONE 1 ZONE 2 ZONE 3 NAC3 1ST STAGE 2ND STAGE MODE MAN.
Page 26
Relay contact is 1 Amp maximum with voltage free change-over FIRE RELAY Relay contact is 1 Amp maximum with voltage free change-over Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 17 of 127...
Installation Section 3 Installation This section provides instructions for connecting cables, mounting and testing the Shield A-XT Releasing Fire Control Panel for installation. Install this product in accordance with NFPA 72, the National Electrical Code and all local codes. General Installation Checklist To complete the installation: Create a plan for the fire alarm system and provide a checklist for installing the fire control panel.
Ground straps must be worn by installers before handling electronic components to prevent this damage. Acquire the following items that are not included with the Shield A-XT Releasing Fire Control Panel, but may be required for the installation:...
Open the cabinet-door of the fire control panel using the door-lock-key. Disconnect the green ground cable from the cabinet-door. Remove the cabinet-door from the cabinet-box of the Shield A-XT Releasing Fire Control Panel. Remove the fascia from the cabinet-box. Remove the standby-batteries from the base of the cabinet-box.
Installation Removing the Fascia Remove the fascia of the Shield A-XT Releasing Fire Control Panel prior to the mounting process to prevent damage to circuit board components. To remove the fascia from the cabinet-box of the Shield A-XT Releasing Fire Control Panel: Remove the two mounting-screws on the fascia that secure it to the cabinet-box.
Installation Mounting Drill holes in the premises-wall to mount the cabinet-box of the Shield A-XT Releasing Fire Control Panel using mounting-hardware to secure it. Screws or bolts providing a minimum diameter of 0.2” (5 mm) must be used to mount the cabinet-box in three mounting positions.
Mon. AC Cabling Power cabling from the mains to the Shield A-XT Releasing Fire Control Panel must provide connections to branch circuits containing a 15 Amp fuse. Specify 14 AWG wiring for this connection. Power cabling must enter the at the back, top or left-side of the fire control panel cabinet through the cabinet-knockouts.
Battery standby-hours are dependant on battery capacity and loading of the FACP system. To install the replacement standby-batteries: Place standby-batteries at the bottom of the Shield A-XT Releasing Fire Control Panel cabinet. Connect the black battery-lead to the negative terminal of Battery 2.
Page 34
( Black Cable ) 7 AH Battery 7 AH Battery The illustrated series connection above provides a standby voltage of 24 VDC required by the Shield A-XT Releasing Fire Control Panel. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Zones of the Shield A-XT Releasing Fire Control Panel operate NFPA 72 Class B, Style C or NFPA 72, Class B, Style B. Style C devices provide trouble conditions for direct shorts and opens on zone loops. Style B devices provide alarm conditions for direct shorts and trouble conditions for opens on zone loops.
Page 36
( - ) Supervised Inputs Supervised inputs of the Shield A-XT Releasing Fire Control Panel are Class B, Style C Initiating Device Cir- cuits (IDC). Supervised inputs include the field terminals of MAN RELEASE, ABORT, REL. PRES. SWITCH and LOW P.
NAC devices are connected to these NAC outputs. NAC 1 and 2 NAC 1 and 2 of the Shield A-XT Releasing Fire Control Panel provide single and dual circuit synchronization for Zones 1 and 2 when operating with authorized synchronization modules. Single circuit synchronization provides synchronized NAC outputs on one channel of the Shield A-XT Releasing Fire Control Panel.
Page 38
Provide a connection from the NAC output to the NAC Extender PS-8 of Cooper Industries. During a trouble condition inputs open on the 1N1 terminals of the NAC Extender PS-8 providing a trouble condition on the Shield A-XT Releasing Fire Control Panel.
Page 39
ZONE 3 TATUS UNITS iances of the Shield A-XT Releasing Fire Control Panel only. NAC 3 provides a special application output that is pulsed and continuous. The pulsed output of NAC 3 prevents it from operating strobe devices or s ynchronizing with devices on NAC 1 and NAC 2.
Maintain maximum current limits and loading. Releasing Circuit This section describes how to install releasing devices on the EXTING terminals of the Shield A-XT Releasing Fire Control Panel. The Shield A-XT Releasing Fire Control Panel operates releasing devices in compliance with Fire Protection Service Valves under UL 260, UL 429 and UL 429A.
Page 41
Installation The Shield A-XT Releasing Fire Control Panel operates only Shield authorized solenoid releasing valves. Reference Appendix B, Equipment List for a list of Authorized Releasing Valves. The figure below illustrates an example of the wiring for the releasing solenoid:...
Fire Control Panel - Status Unit Terminals This section describes the Status Unit terminals of the Shield A-XT Releasing Fire Control Panel. Status Unit ter- minals of the Shield A-XT Releasing Fire Control Panel contain connections for Data and Power. The Data termi- nals provide RS485 communication.
To test the installation of the Shield A-XT Releasing Fire Control Panel: Disconnect wiring from the EXTING. terminals to the releasing solenoid before applying power from the source.
Troubleshoot the Shield A-XT Releasing Fire Control Panel when conflicts exist after installing or configuring. Monitor the lower fascia indicators of the fire control panel to determine the cause of the trouble condition. The lower indicators of the fascia are visible after opening the cabinet-door of the Shield A-XT Releasing Fire Control Panel.
Page 45
Can only be reset by pressing processor reset and W/DOG reset or powering down the fire control panel. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 36 of 127...
Page 46
Installation This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 37 of 127...
The Shield A-XT Releasing Fire Control Panel can be configured for almost any installation requirement. Navi- gate the menu on the System Mode LED display using the Select and Enter buttons of the Shield A-XT Releasing Fire Control Panel. The System Mode LED, Select and Enter buttons are located in the center of the front-panel fascia.
Page 48
Missing flashing dot that the configuration indicates that the code is set. configuration code is not set. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 39 of 127...
Programming and Operating Configuration Codes Not all configuration codes of the Shield A-XT Releasing Fire Control Panel are authorized for operation under UL 864. Reference Appendix G, UL 864 Permitted Configurations for the list of authorized configuration codes of the Shield A-XT Releasing Fire Control Panel.
Page 50
Allows extinguishant output to be reset before countdown timer has reset during imminent phase. expired for installing and testing Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 41 of 127...
Page 51
Any combination can be selected. Zone 2 operates through I.S. Barrier Zone 3 operates through I.S. Barrier Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 42 of 127...
Page 52
29 minutes after discharge output has operated Panel can be reset 30 minutes after discharge output has operated Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 43 of 127...
300 seconds Operating the Fire Control Panel Access levels are provided for controls and programming on the Shield A-XT Releasing Fire Control Panel. Access Level 1 provides restricted controls, Access level 2 provides less restricted controls with limited programming and Access Level 3 provides unrestricted controls and programming.
Page 54
Programming and Operating Functions and Codes Functions and codes for operating the Shield A-XT Releasing Fire Control Panel in Access Level 2 are described below: Function Terminal Codes Description Test Zones ZONE 1 Select codes t1, t2 or t3 to place Zones 1, 2 or 3 in Test Mode.
Programming and Operating Control Operation The table below describes control operation of the Shield A-XT Releasing Fire Control Panel: Controls Operation Terminate Release Press the Terminate Release button while in Access Level 3 to terminate the flow of extinguishant caused by a releasing event and reset the fire control panel. The flow of extinguishant can not be stopped using the reset button until after the extinguishant duration timer has elapsed.
Removal of a detector from it’s base or a trouble on any of the zone wiring will cause the Trouble LED and Zone Trouble LEDs to flash, indicating the zone in which the trouble has occurred. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
C2C (software version 1.2 and above only). Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
To disable NAC outputs, press the mode button to select “db” on the seven segment display. Pressing enter will disable all NAC outputs and cause the General Disablement and NAC Trouble/ Disabled LEDs to light. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Reference additional disablement options in Functions and Codes of this section. Relay Operation The Shield A-XT Releasing Fire Control Panel provides volt free changeover relay contacts for local control and signalling. The relay contacts are rated for switching signalling circuits only and the maximum ratings should not be exceeded under any circumstances.
Calibrating the Releasing Circuit Calibrate the releasing circuit by adjusting the EXTING. MON. potentiometer on the front-panel of the of the Shield A-XT Releasing Fire Control Panel. Adjust the EXTING MON setting to provide supervision of the “EXTING.”...
Cleaning the External Cabinet and Door Clean the external cabinet and door of the Shield A-XT Releasing Fire Control Panel with a damp cloth. Do not clean these surfaces with detergents or solvents. Do not permit water to enter the cabinet during the cleaning process.
Replacing Fuses The Shield A-XT Releasing Fire Control Panel contains a battery fuse and an AC input fuse to protect it against circuit overloads. The battery fuse is a 3.0 Amp slow blow and the AC input fuse is a 1.6 Amp slow blow.
Install the replacement fuse in the upper-half of the fuse-housing. Connect the upper-half to the lower-half of the fuse-housing. Secure the fascia to the cabinet of the Shield A-XT Releasing Fire Control Panel using the two retaining-screws. Re-connect the red-lead of the recharging circuit to the positive terminal of the standby-batteries.
Confirm that 115 VAC or 230 VAC is turned-off at the power source. Install the replacement fuse in the terminal block housing. Re-connect cabling to the EXTING. terminals of the Shield A-XT Releasing Fire Control Panel. Close and lock the door of the Shield A-XT Releasing Fire Control Panel.
Status Units are supervised for open-circuit, short-circuit and ground-fault conditions. Status Units are compatible with all models of the Shield A-XT Releasing Fire Control Panel. The Status Unit requires a data connection and 24 VDC to operate. Status Units can also be powered by the AUX 24V output or an auxiliary 24 VDC source that is listed for Fire Applications with Regulated and Power Limited Outputs.
Page 66
J2 Jumper removed from removed from this connected on this Status Unit Ancillary Board last Status Unit Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 57 of 127...
Supplementary Devices Abort Connections Abort connections of the Shield Status Unit are supervised for open-circuit, short-circuit and ground-fault conditions. Abort connections on the circuit board of the Status Unit are labeled Hold. Hold and Abort functions are identical. To provide supervised connections on the Abort terminals: Connect a 470 Ohm trigger-resistor, SEOLR-470 in series with one-leg of the normally open switch.
Therefore, all mode inputs must be inactive for the system to be in Automatic or Manual Mode. The system can include the Shield A-XT Releasing Fire Control Panel, IDCs, Status Units and Ancillary Boards. LED indicators on the front-panel of the Status Unit illuminate when the key-switch is in the “Automatic and Manual Only”...
MAN REL Relay The MAN REL relay operates when a manual release input occurs on the fire control panel. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 60 of 127...
UNIT, POWER terminals of the Shield A-XT Releasing Fire Control Panel. The total current obtained from connecting multiple Ancillary Boards and Status Units to the Shield A-XT Releasing Fire fire control panel must be below the maximum ratings of the AUX 24V or STATUS UNIT, POWER outputs.
Abort indicators and the buzzer will sound. The panel display will show the status unit or ancillary boards that have the same address. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Disable the Write enable switch (push to the left). Disable the Enable controls key-switch. The panel should return to the normal, quiescent condition. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 63 of 127...
The seven segment display on the panel will show the number of the unit that is disconnected and all LEDs on the status unit that is disconnected will flash. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Page 74
Supplementary Devices This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 65 of 127...
Specifications Appendix A Specifications This appendix provides electrical and environmental specifications for the Shield A-XT Releasing Fire Control Panel with Releasing. Electrical AC Line Connection Terminals Description Voltage AC Line 115 VAC @ 50 / 60Hz (Supervised) 230 VAC @ 50 / 60Hz (Supervised)
Page 76
Maximum Current Draw The maximum current draw of the Shield A-XT Releasing Fire Control Panel cannot exceed 2.0 A. Outputs of the fire control panel can be loaded with any combination of currents as long as the total current does not exceed 2.0 A.
Specifications NAC outputs on the Shield A-XT Releasing Fire Control Panel are load dependant and are limited to a maximum current load of 500 mA. The releasing output on the Shield A-XT Releasing Fire Control Panel is load dependant and is limited to a maximum current load of 1000 mA.
Page 79
Battery leads are provided in the cabinet for recharging the standby-batteries. One end of the battery leads are permanently connected to the power supply of the Shield A-XT Releasing Fire Control Panel. The opposite end of the battery leads connect to terminals of the standby-batteries.
Fused: Electronic 1.1 A Supervision: Voltage reversing DC Short Circuit Threshold: 130 Ohms +/- 20% Maximum line-voltage-drop: 2 VDC Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 71 of 127...
Low Press. Switch Monitored Input EOL: 6.8K Ohm, SEOLR-6.8 +/- 5% resistor supplied in terminals, activation impedance: 470 Ohms Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 72 of 127...
Page 82
(NC), (C) and (NO) Relay Function: Common 30 VDC @ 1A maximum, volt free change over contact Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 73 of 127...
18 - 28 VDC Special Application Output, 500 mA maximum Power Output Circuits The Shield A-XT Releasing Fire Control Panel provides power output circuits on NAC 1, NAC 2, NAC 3, AUX 24V, STATUS UNITS, POWER and the EXTING terminals.
Connect Zone cabling using a minimum of 1 mm cross sectional area. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
30 VDC @ 1A maximum, volt free change over contact Power Fault (PF) No Connect (NC) terminal Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 76 of 127...
Maximum Screw Diameter: 0.2" (5 mm) screws This fire control panel is designed for indoor use only. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 77 of 127...
Current loading calculations do not include the combined IDC currents of the Shield A-XT Releasing Fire Control Panel. These combined IDC currents are negligible in comparison to fire control panel, ancillary device and NAC currents of the Shield A-XT Releasing Fire Control Panel and are therefore excluded from the current loading calculation.
Current-Loading Current-loading of the Shield A-XT Releasing Fire Control Panel is limited to the 2.0 Amp capacity of the power supply and the 7 AH capacity of the standby-batteries. The standby-batteries can provide an operating duration of twenty-four hours followed by five minutes of alarm when the standby current does not exceed 236 mA.
= [ ( 0.209 + 0.209 + 0.209 + 16 / 10K ) ] A = ( 0.627 + 0.0016 ) A = 0.6286 A total Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 80 of 127...
Page 90
= 1/2 [ ( 4.4 / 0.6286 ) / ( 0.006385 Ohms / FT ) ] = 548 FT Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 81 of 127...
Page 91
Example circuit identifies wire measured across outmin length for two conductor cable NAC1 terminals NAC1 NAC2 Fire In Zon Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 82 of 127...
65% nominal UL 429 specifies that the SRV operate a minimum voltage 65% below the nominal rating. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 83 of 127...
Page 93
The circuit connection is provided with 18 AWG solid copper wire. • The maximum power rating for the SRV (WSRV ) is 9.11 Watts. • The nominal output-voltage for the Shield A-XT Releasing Fire Control Panel (Vout ) is 24 VDC. nominal • The nominal operating-voltage for the SRV (VSRV ) is 24 VDC.
Page 94
Refer to the manufacturer specifications of the SRV for the maximum power rating (WSRV = 9.11 W / 15.6 VDC Imax = 584 mA Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 85 of 127...
Page 95
SRV terminals. opmin EOL Diode 1N504-G, SEOLD-504 band end to ( + ) Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 86 of 127...
Page 96
Calculations This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 87 of 127...
This wiring diagram describes circuit connections for all models of the shield A-XT Releasing Fire Control Panel. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 88 of 127...
Page 98
AC input. Related Documentation The following documents shall be used to provide additional information for installing and operating the Shield A-XT Releasing Fire Control Panel: ■ Installation and Operations Manual, SEXTCP-OM, Rev. E01.XX ■ Operating Instructions, SEXTCP-OI, Rev. P01.XX ■...
Page 100
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 91 of 127...
Page 101
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 92 of 127...
Page 102
■ MAN RELEASE ■ ABORT ■ REL. PRES. SWITCH ■ EXTING ■ LOWP. SWITCH ■ DATA, STATUS UNITS Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 93 of 127...
Page 103
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 94 of 127...
Page 104
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 95 of 127...
Page 105
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 96 of 127...
Page 106
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 97 of 127...
Page 107
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 98 of 127...
Page 108
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 99 of 127...
Page 109
500 mA threshold of each NAC output. Security Ltd. Security Ltd. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 100 of 127...
Page 110
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 101 of 127...
Page 111
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 102 of 127...
Page 112
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 103 of 127...
Page 113
Wiring Diagram Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 104 of 127...
Page 114
Wiring Diagram This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 105 of 127...
Appendix D Operating Instructions This section provides operating instructions, SECTCP-OI for the Shield A-XT Releasing Fire Control Panel. These operating instructions shall be placed on the cabinet-front or on a separate sheet that can be framed and located adjacent to the control unit: Shield Fire, Safety and Security Ltd.
Page 116
Operating Instructions Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 107 of 127...
Page 117
Operating Instructions Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 108 of 127...
Page 118
Operating Instructions Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 109 of 127...
Page 119
Operating Instructions Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 110 of 127...
Operating Instructions Inspecting Batteries Inspect the standby-batteries annually to determine the connection integrity to the Shield A-XT Releasing Fire Control Panel. The fire control panel contains sealed lead acid batteries to provide standby power in the event of mains failure. The standby-batteries have a life expectancy of 3 to 5 years. Test the standby-batteries annually in accordance with the battery manufacturer’s recommendations to determine their suitability for continued standby...
UL Compliance Label, SEXTCP-UL, Revision E01.XX Emergency Contact IN THE EVENT OF TROUBLE CONTACT NAME ADDRESS CITY STATE TELEPHONE Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 112 of 127...
Page 122
Operating Instructions This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 113 of 127...
Software XTUS_ Release Installation For dry indoor use only Environment Label SEXTCP-UL, E01.00, Date: 05/01/2012 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 114 of 127...
Page 124
UL Compliance Label This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 115 of 127...
Page 125
Zone 1 or Zone 2 or Zone 3 Enable / Disable Enable / Disable Detectors Trigger Automatic Release Code: C16 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 116 of 127...
Page 126
Active Code: C27 No Activation Delay Upon Enable / Disable Enable / Disable Manual Release Code: C28 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 117 of 127...
Page 127
Zone 3 Alarm From Delay Options 0 To 9 Option 0 to disable Pull Station Delayed Code: C43 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 118 of 127...
Page 128
Zone 2 Non-Latching Enable / Disable Disable Code: C82 Zone 3 Non-Latching Enable / Disable Disable Code: C83 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 119 of 127...
Page 129
Panel Can Be Reset Enable / Disable Enable / Disable 30 Minutes After Discharge Output Has Operated Code: E30 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 120 of 127...
Page 130
Code: 60 to 295 Extinguishant Duration 60 To 300 Seconds 60 To 300 Seconds In 5 Second Steps Code: 300 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 121 of 127...
Page 131
Contacting VES For Repair ..... 1 Shield ........78 Control Operation .
Page 132
....94 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Page 133
Manual Release ......32 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Page 134
Silence/Sound Alarms ......47 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Page 135
Troubleshooting ......35 Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Page 136
Index This page intentionally left blank. Shield Fire, Safety and Security Ltd. Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00 127 of 127...
Page 137
Shield A-XT Releasing Fire Control Panel - Installation and Operation Manual SEXTCP-OM Revision E01.00...
Need help?
Do you have a question about the Shiel A-XT and is the answer not in the manual?
Questions and answers