INTERIOR MAKE−UP BOX
(FACTORY− INSTALLED LEFT SIDE)
Left side
FIGURE 47
EXTERIOR MAKE−UP BOX
(FIELD PROVIDED RIGHT SIDE)
FIGURE 48
Refer to figure 50 for field wiring and figure 51 for schematic
wiring diagram and troubleshooting.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE − Unit nameplate states maximum current draw.
Maximum Over−Current Protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for servic-
ing at a later date. Remove the blower access panel to
check the length of the wire.
MAKE−UP
BOX INSIDE
CABINET
MAKE−UP
BOX
OUTSIDE
CABINET
Right Side
Page 33
Complete the wiring connections to the equipment. Use the
provided unit wiring diagram and the field wiring diagram
shown in figure 50. Use 18−gauge wire or larger that is suit-
able for Class II rating for thermostat connections.
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current Na-
tional Electric Code (ANSI/NFPA No. 70) for the USA and
current Canadian Electric Code part 1 (CSA standard
C22.1) for Canada. A green ground wire is provided in the
field make−up box.
NOTE − The EL195DF furnace contains electronic compo-
nents that are polarity sensitive. Make sure that the furnace
is wired correctly and is properly grounded.
Generator Use − Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
D The furnace requires 120 volts + 10% (Range: 108
volts to 132 volts)
D The furnace operates at 60 Hz + 5% (Range: 57 Hz to
63 Hz)
D The furnace integrated control requires both polarity
and proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power
D Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion)
Accessory Terminals
One line voltage EAC" 1/4" spade terminal is provided on
the furnace integrated control. See figure 52 for integrated
control configuration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral
terminals. If an accessory rated at greater than one amp is
connected to this terminal, it is necessary to use an exter-
nal relay.
One line voltage HUM" 1/4" spade terminal is provided on
the furnace integrated control. See figure 52 for integrated
control configuration. This terminal is energized in the
heating mode when the combustion air inducer is operat-
ing. Any humidifier rated up to one amp can be connected
to this terminal with the neutral leg of the circuit being con-
nected to one of the provided neutral terminals. If a humidi-
fier rated at greater than one amp is connected to this termi-
nal, it is necessary to use an external relay.
One 24V "H" 1/4" spade terminal is provided on the furnace
integrated control. See figure 52 for integrated control con-
figuration. The terminal is energized in the heating mode
when the combustion air inducer is operating and the pres-
sure switch is closed. Any humidifier rated up to 0.5 amp
can be connected to this terminal with the ground leg of the
circuit connected to ground or the "C" terminal.