UNITI POWER SYMPHONY
SPY1500RMi2U &
SPY3000RMi2U
USER MANUAL
A RACKMOUNTABLE UNINTERRUPTIBLE POWER
SUPPLY PROVIDING UNITY POWER AND TRUE
ONLINE DOUBLE CONVERSION
Please visit
www.unitipower.com
for assistance
Download the app

Advertisement

Table of Contents
loading

Summary of Contents for UNITI SPY1500RMi2U

  • Page 1 Download the app UNITI POWER SYMPHONY SPY1500RMi2U & SPY3000RMi2U USER MANUAL A RACKMOUNTABLE UNINTERRUPTIBLE POWER SUPPLY PROVIDING UNITY POWER AND TRUE ONLINE DOUBLE CONVERSION Please visit www.unitipower.com for assistance...
  • Page 2: Safety Instructions

    SAFETY INSTRUCTIONS KEEP THESE INSTRUCTIONS IN A SAFE PLACE This manual contains important instructions that should be followed during the installation and maintenance of the UPS and batteries. UPS models operate at an optimal temperature of 20-25C CERTIFICATION STANDARDS • Safety: IEC/EN 62040-1 •...
  • Page 3: Safety Of Persons

    SAFETY OF PERSONS • Dangerous voltage levels are present within the system. It should only be opened by qualified service personnel. • The system must be properly grounded • The battery supplied with the system contains small amounts of toxic materials. To avoid accidents, the instructions listed below must be observed: Servicing of batteries should be performed by personnel knowledgeable about batteries and the required precautions...
  • Page 4: Product Safety

    PRODUCT SAFETY • The UPS connection instructions and operation described in the manual must be followed in the indicated order • UPS enclosure IP rating IP20 • CAUTION: To reduce the risk of fire, the unit connects only to a circuit provided with a branch circuit overcurrent protection of 20A rating, The upstream circuit breaker must be easily accessible •...
  • Page 5: Table Of Contents

    Contents SAFETY INSTRUCTIONS ..........................2 CERTIFICATION STANDARDS ..........................2 SPECIAL SYMBOLS ............................... 2 SAFETY OF PERSONS ............................3 PRODUCT SAFETY ..............................4 SPECIAL PRECAUTIONS ............................4 INTRODUCTION ........................... 7 ELECTRONIC EQUIPMENT PROTECTION ....................7 ENVIRONMENTAL PROTECTION ....................... 7 PRODUCT OVERVIEW .......................... 8 WEIGHT AND DIMENSIONS ........................
  • Page 6 UPS BLOCK DIAGRAM ..........................26 UPS SPECIFICATION ..........................27...
  • Page 7: Introduction

    1. INTRODUCTION Thank you for selecting UNITI to protect your electrical equipment. We recommend that you take the time to read this manual and take full advantage of the many features of the UPS (uninterruptible power supply). Before installing the UPS, please read the safety instructions. Then follow the indications in this manual.
  • Page 8: Product Overview

    2.1 WEIGHT AND DIMENSIONS The weights in this table is for reference only, please see the labels on the carton for details Description Net Weights (KG) Dimensions: D x W x H (mm) SPY1500RMi2U 15.8 445 x 438 x 85.5 SPY3000RMi2U 26.2 600 x 438 x 85.5...
  • Page 9: Rear Panels

    2.2 REAR PANELS SPY1500RMi2U SPY3000RMi2U EBM3618RT2U EBM7718RT2U Legend WLAN (HDMI) Ethernet RPO / Dry in / Dry out EBM auto detection RS232 Slot card box EBM connector Input breaker (optional) Input socket / Input Output socket / output Output fuse (optional)
  • Page 10: Installation

    3. INSTALLATION 3.1 INSPECTING THE EQUIPMENT If any equipment has been damaged during shipment, keep the shipping cartons and packaging materials for the carrier or place of purchase. Returns policy subject to supplier and not specific to the manufacturer 3.2 CHECKING THE ACCESSORY KIT Input cable Output cables USB cable...
  • Page 11: Installation (Ups)

    3.3 INSTALLATION (UPS) Always keep 200mm of space behind the UPS rear panel for ventilation. Check that the indications on the name plate located on the top cover of the UPS meets the AC-power source and the electrical consumption of the total load. Connect the UPS input socket to the AC-power source using the cable from the protected equipment Connect the loads to the UPS using the output cables...
  • Page 12: Rt Models

    3.3.1 RT MODELS Rack installation Follow steps 1 to 4 for module mounting on the rails.
  • Page 13: Connecting The Ebm(S)

    Tower Installation Follow steps 1 to 5 for module mounting on the feet provided. 3.4 CONNECTING THE EBM(S) A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm the user.
  • Page 14: Operation

    4. OPERATION 4.1 LCD PANEL The UPS provides useful information about the UPS itself, load status, events, measurements and settings. Indicator Status Description The UPS is operating normally in Online or High Green Efficiency Mode The UPS is in Battery Mode Yellow The UPS is in Bypass Mode Yellow...
  • Page 15: Lcd Description

    The following table shows the indicator status and description: The button Function Illustration Press the button for >100ms & <1s to perform a Power on cold start function (without mains) When mains power is present, press the button for Turn on >1s to turn on the UPS Turn off Press the button >3s to turn off the UPS...
  • Page 16 Operation Cause Description status Standby mode The UPS is off without an output The UPS is operating normally and protecting the Online mode critical load An input failure has occurred, and the UPS is Battery mode powering the equipment for shutdown, if possible 1 beep every 4 seconds Battery mode with battery...
  • Page 17: Display Functions

    4.3 DISPLAY FUNCTIONS When starting the UPS, the display is in the default UPS status summary screen. Main menu Submenu Display information or menu function UPS mode, IoT status, date/time, battery UPS status status and current alarms (if any) Event log Display the events and faults stored [Load] W VA P%, [Input/Output] V, Measurements...
  • Page 18: Starting The Ups With Utility Power

    Start / Auto restart / Cold start / auto restart: enabled start [disabled], [enabled] Start from bypass from bypass: disabled Site wiring fault [enabled], [disabled] disabled Overload pre-alarm [50% - 105%] 105% [Auto detection]. External battery [manual EBM: 0-4], Auto detection 0 EBM [Manual Ah: 7-144Ah] [2A], [4A], [6A], [8A] for Charger current...
  • Page 19: Starting The Ups On Battery

    4.6 STARTING THE UPS ON BATTERY Before using this feature, the UPS must have been powered by utility power with output enabled at least once. Battery start can be disabled. Refer to the Chapter 4.4 User setting 4.7 UPS SHUTDOWN...
  • Page 20: Communication

    5. Communication 5.1 RS232 AND USB Connect a communication cable to the serial or USB port on a computer Connect the other end of the communication cable to the RS232 o USB communication port on the UPS 5.2 UPS REMOTE CONTROL FUNCTIONS Remote power off (RPO) When the RPO is activated, the UPS will cut off the output immediately, and continue to alarm.
  • Page 21: Iot

    5.3 IOT The built-in ethernet port and WLAN (optional accessory) ports enable market leading and easy to use IoT solutions for: • A mobile application which allows users to remotely monitor UPS(s) and keep appraised about critical UPS events • Remote report UPS faults and status (contact with your service provider for more details) from APP or registered APP account (email address) •...
  • Page 22: Modbus Tcp

    The wireless module is optional, please contact your local distributor for details. 5.4 MODBUS TCP Built-in ethernet port offers Modbus TCP feature to facilitate remote monitoring of the UPS into your own software. Contact your service provider for protocol details. 5.5 INTELLIGENT CARDS (OPTIONAL) Intelligent cards allow the UPS to communicate with different types of devices in variety of networking environments.
  • Page 23: Winpower View App

    Installation procedure: 1. Go to the website: http://www.ups-software-download.com/content/ups-download-software/download.html 2. Choose the operating system relevant to your needs and follow the instructions described on the website to download the software. 3. When downloading all required files from the internet, enter the serial No: 511C1-01220-0100-478DF2A to install the software.
  • Page 24: Ups Maintenance

    6. UPS MAINTENANCE 6.1 EQUIPMENT CARE For the best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the equipment at an ambient temperature of 20°C (68°F). The batteries are rated for a 3-5-year service life.
  • Page 25: Troubleshooting

    By separating waste electrical and electronic equipment, you will help reduce the volume of waste sent for incineration or land-fills and minimize any potential negative impact on human health and environment. 7. TROUBLESHOOTING Typical alarms and faults: To check the UPS status and event log: Press any button on the front panel display to activate the menu options Press the button to select event log Scroll through the listed events and faults.
  • Page 26: Specifications

    LED is on. Beep every second Over temperature warning The UPS internal temperature is Clear vents and remove any heat sources. too high. At the warning level, the UPS generates the alarm Ensure the airflow around the UPS is not but remains in the current restricted.
  • Page 27 8.2 UPS SPECIFICATION Model name SPY1500RMi2U SPY3000RMi2U Power rating VA/Watt 1500VA / 1500W 3000VA / 3000W Line mode Efficiency ECO mode 160-300V 100% load, 110-160V derating to 50% load Voltage range linearly Rated frequency 50Hz/60Hz Frequency Input performance 40Hz-70Hz (45Hz-55Hz, 54Hz-66Hz @ load>60%) range >0.99...
  • Page 28 Charging Optimize Battery Management (OBM) method Charger Charging current Other mode CVCF Yes (derating to 60% load) Display Dot matrix LCD (optional segment LCD) Language Multi-Language USB 2.0 with HID power device RS232 Yes (DB9) Dry in / out 1 programmable dry in; 1 programmable dry out Intelligent slot Yes (for card) Network card...
  • Page 29 Surge IEC/EN 61000-4-5 Input power cable Output power Yes (For IEC models) cable EBM cable Yes (in EBM) USB cable Accessory RS232 cable Optional Rail kit Optional Tower feet Rack ear Manual (English)