Advertisement

Quick Links

Download the app
UNITI POWER SYMPHONY
SPY6KiRM & SPY10KiRM
USER MANUAL
A RACKMOUNTABLE UNINTERRUPTIBLE POWER
SUPPLY PROVIDING UNITY POWER AND TRUE ONLINE
DOUBLE CONVERSION
Please visit
www.unitipower.com
for assistance

Advertisement

Table of Contents
loading

Summary of Contents for UNITI POWER SYMPHONY SPY6KiRM

  • Page 1 Download the app UNITI POWER SYMPHONY SPY6KiRM & SPY10KiRM USER MANUAL A RACKMOUNTABLE UNINTERRUPTIBLE POWER SUPPLY PROVIDING UNITY POWER AND TRUE ONLINE DOUBLE CONVERSION Please visit www.unitipower.com for assistance...
  • Page 2: Safety Instructions

    SAFETY INSTRUCTIONS KEEP THESE INSTRUCTIONS IN A SAFE PLACE This manual contains important instructions that should be followed during the installation and maintenance of the UPS and batteries. UPS models operate at an optimal temperature of 20-25C SPECIAL SYMBOLS RISK OF ELECTRIC SHOCK – observe the warning associated with the risk of electric shock symbol Important instructions that must always be followed EU separate collection and lead content mark for lead-acid batteries.
  • Page 3: Safety Of Persons

    SAFETY OF PERSONS • RISK OF VOLTAGE BACKFEED. The system has its own power source (the battery). Isolate the UPS and check for hazardous voltage upstream and downstream during lockout-tagout operation. Terminal blocks may be energized even if the system is disconnected from the AC power source. •...
  • Page 4: Product Safety

    PRODUCT SAFETY • The UPS connection instructions and operation described in the manual must be followed in the indicated order • UPS enclosure IP rating IP20 • CAUTION: To reduce the risk of fire, the unit connects only to a circuit provided with a branch circuit overcurrent protection of 20A rating, The upstream circuit breaker must be easily accessible •...
  • Page 5: Table Of Contents

    Contents SAFETY INSTRUCTIONS ..........................2 SPECIAL SYMBOLS ............................... 2 SAFETY OF PERSONS ............................3 PRODUCT SAFETY ..............................4 SPECIAL PRECAUTIONS ............................4 INTRODUCTION..........................7 PRODUCT FEATURES ..........................7 ENVIRONMENTAL PROTECTION ....................... 7 PRODUCT OVERVIEW ......................... 8 WEIGHT AND DIMENSIONS ........................8 PRESENTATION ............................
  • Page 6 TRANSPORTING THE UPS ........................31 STORING THE EQUIPMENT ........................31 REPLACING BATTERIES ........................... 31 RECYCLE ..............................31 TROUBLESHOOTING ......................... 32 TYPICAL ALARMS AND FAULTS: ......................32 SILENCING THE ALARM ........................... 34 SPECIFICATIONS ..........................35 UPS BLOCK DIAGRAM ..........................35 UPS SPECIFICATION ..........................36...
  • Page 7: Introduction

    1. INTRODUCTION Thank you for selecting UNITI to protect your electrical equipment. We recommend that you take the time to read this manual and take full advantage of the many features of the UPS (uninterruptible power supply). Before installing the UPS, please read the safety instructions. Then follow the indications in this manual.
  • Page 8: Product Overview

    2. PRODUCT OVERVIEW 2.1 WEIGHT AND DIMENSIONS The weight in this table is for reference only, please see the labels on the carton for details Dimension ‘D’ is chassis only, not including panel. Description Net Weights (KG) Dimensions: D x W x H (mm) SPY6KiRM 15.8 540 x 438 x 86.3(2U)
  • Page 9: Presentation

    2.2 PRESENTATION SPY6KiRM & SPY10KiRM Front view Ventilation area LCD module, including 2(1)---button, 2(2)---LCD screen, 2(3)---LED indicator Rear view Intelligent slot 7. Parallel slot RS232 8. RJ45 (for EBM detection / rack MBP detection) Ethernet port (RJ45, for IoT function) 9.
  • Page 10 Rear view Fuse board cover (replace EBM fuse) EBM port 1 EBM port 2 EBM detection Box (RJ45 port)
  • Page 11: Installation

    3. INSTALLATION It is recommended to move the equipment to the installation site by using a pallet jack or truck before unpacking. The system may be installed only by a qualified electrician in accordance with applicable safet regulations. Boxes may be heavy, please install with at least two people. 3.1 UNPACKING &...
  • Page 12: Checking The Accessory Kit

    3.2 CHECKING THE ACCESSORY KIT Description Battery Cable √ EBM detection √ cable USB cable √ RS232 cable Parallel cable Tower foot √ Extension plate of √ tower foot Rack ear √ √ Rack rail kit Quick start (EBM) √ User manual (UPS) √...
  • Page 13: Installation (Ups)

    3.3 INSTALLATION (UPS) These UPS support 2 installation modes: rack installation and tower installation Always keep 500mm of space behind the UPS rear panel for ventilation. Do not carry the front / rear panel of the module during installation Rack installation The procedure is suitable for 19 inch rack cabinet installation, it is recommended that the depth of the cabinet be no less than 800mm.
  • Page 14 Slide the unit into the ‘rail kit’ and ensure the rack mounting screws are tightened EBM model Identify the final position and keep 3U space for installation. It is recommended to install below the UPS Install the rail kit (if configured): same as UPS as above Install ‘rack ear’...
  • Page 15: Power Cables Connection

    Tower Installation Rotate the LCD screen to the tower position Set up the tower foot, then place the unit on to the tower foot. Set up the ‘extension plate as below and install the tower foot from UPS. place the UPS & EBM into the tower foot individually: place EBM module to the right of the UPS and align with the front panel 3.4 POWER CABLES CONNECTION This chapter introduces how to wire AC IN/OUT cable to UPS in different modes, and connect UPS to EBM...
  • Page 16: Wiring For Ac Cable (Ac Source To Ups)

    Danger! The rated current of the utility power switch must be greater than the UPS input current, otherwise the utility power switch may be burnt! Recommended upstream protection and downstream switch: Downstream switch UPS power rating Upstream circuit breaker Backfeed contactor 6kVA D curve –...
  • Page 17: Wiring With External Battery Module (Ebm) (Dc Source To Ups)

    3.4.3 WIRING WITH EXTERNAL BATTERY MODULE (EBM) (DC SOURCE TO UPS) Be sure to disconnect the battery cable from the EBM before connecting the battery terminals of the UPS Make sure the UPS is completely off before connecting or disconnecting the EBM Before connecting the EBM, make sure that the EBM specification is compatible with UPS configuration.
  • Page 18: Parallel System Installation And Operation (Optional)

    4. PARALLEL SYSTEM INSTALLATION AND OPERATION (OPTIONAL) If your UPS is configured with a parallel function, up to 3 UPS can be connected in parallel to configure a sharing and redundant output power. In parallel, the mechanical installation for each module is the same as the single system. For details, please refer to chapter 3.3.
  • Page 19: Wiring For Parallel Signal Cable

    Parallel system: 4.2 WIRING FOR PARALLEL SIGNAL CABLE Parallel signal cable connection diagram: Remove the cover of the parallel box, then connect each UPS one by one with the parallel cable, make sure the cable is screwed to parallel port tightly. It is recommended to lock the parallel cable as above for preventing the parallel ports suffering an unexpected pulling force and causing the parallel system fault.
  • Page 20: Parallel System Operation

    4.3 PARALLEL SYSTEM OPERATION Turn on the input breakers for the parallel UPS Pressing the button continuously of one UPS in the system, then the system will start to turn on and enter line mode. Regulate the output voltage of each UPS separately, and check if the output voltage difference is less than 0.5V among the parallel system.
  • Page 21 The following table shows the indicator status and description: The button Function Illustration Press the button for >100ms & <1s to perform a Power on cold start function (without mains) When mains power is present, press the button Turn on for >1s to turn on the UPS Turn off Press the button >3s to turn off the UPS...
  • Page 22: Lcd Description

    5.2 LCD DESCRIPTION Operation Cause Description status Standby mode The UPS is off without an output The UPS is operating normally and protecting the Online mode critical load An input failure has occurred, and the UPS is Battery mode powering the equipment for shutdown, if possible 1 beep every 4 seconds...
  • Page 23 Battery test UPS is undertaking a battery test The UPS detects low battery voltage, or the Battery fail battery has been disconnected Too much load attached to UPS output. Remove Overload any unnecessary items to reduce the total load on the UPS A serious fault has occurred which requires Fault mode urgent attention...
  • Page 24: Display Functions

    5.3 DISPLAY FUNCTIONS When starting the UPS, the display is in the default UPS status summary screen. Main menu Submenu Display information or menu function UPS mode, IoT status, date/time, UPS status battery status and current alarms (if any) Event log Display the events and faults stored [Load] W VA P%, [Input/Output] V, [Temperature] ℃...
  • Page 25 Output voltage [230V] [220V], [230V], [240V] [autosensing], [converter Output frequency Autosensing 50Hz, 60Hz] High efficiency Disabled [disabled], [enabled] mode Auto bypass Disabled [disabled], [enabled] Cold start: [disabled], Enabled [enabled] Start / restart Auto restart: Enabled [disabled], [enabled] Site wiring fault [enabled], [disabled] disabled Overload pre-alarm...
  • Page 26: Starting The Ups With Utility Power

    5.5 STARTING THE UPS WITH UTILITY POWER 5.6 STARTING THE UPS ON BATTERY Before using this feature, the UPS must have been powered by utility power with output enabled at least once. 4.4 User setting Battery start can be disabled. Refer to the Chapter 5.7 UPS SHUTDOWN...
  • Page 27: Communication

    6. Communication 6.1 RS232 AND USB Connect a communication cable to the serial or USB port on a computer Connect the other end of the communication cable to the RS232 o USB communication port on the 6.2 UPS REMOTE CONTROL FUNCTIONS Remote power off (RPO) When the RPO is activated, the UPS will cut off the output immediately, and continue to alarm.
  • Page 28: Iot

    6.3 IOT The built-in ethernet port and WLAN (optional accessory) ports enable market leading and easy to use IoT solutions for: • A mobile application which allows users to remotely monitor UPS(s) and keep appraised about critical UPS events • Remote report UPS faults and status (contact with your service provider for more details) from APP or registered APP account (email address) •...
  • Page 29: Ups Management Software

    • SPYNMC – Ideal monitoring solution enables user to monitor and control the status of a UPS on a web browser via the internet • SPYRC – Provides voltage-free dry contact signals for programmable controller and management systems • SPYEMP – Supports temperature and humidity sensors for remote environment monitoring. SPYNMC Card is required.
  • Page 30: Winpower View App

    Installation procedure: 1. Go to the website: http://www.ups-software-download.com/content/ups-download-software/download.html 2. Choose the operating system relevant to your needs and follow the instructions described on the website to download the software. 3. When downloading all required files from the internet, enter the serial No: 511C1-01220-0100-478DF2A to install the software.
  • Page 31: Ups Maintenance

    7. UPS MAINTENANCE 7.1 EQUIPMENT CARE For the best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the equipment at an ambient temperature of 20°C (68°F). The batteries are rated for a 3-5-year service life.
  • Page 32: Troubleshooting

    should be handed in for recycling in accordance with the local environmental regulations for waste disposal. By separating waste electrical and electronic equipment, you will help reduce the volume of waste sent for incineration or land-fills and minimize any potential negative impact on human health and environment. 8.
  • Page 33 Inside temperature of the UPS Check the ventilation of the UPS and UPS temp. alarm is too high check the ambient temperature FAULT Problem displayed Possible cause Remedy Check the loads and remove some non - Inverter overload Overload critical loads. Check if some leads have failed.
  • Page 34: Silencing The Alarm

    8.2 SILENCING THE ALARM Press the ESC (Escape) button 3s on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes or press the ESC button 3s on the front panel display, the alarm beeps again, overriding the previous alarm silencing.
  • Page 35: Specifications

    9. SPECIFICATIONS 9.1 UPS BLOCK DIAGRAM...
  • Page 36: Ups Specification

    9.2 UPS SPECIFICATION Model name SPY6RMi2U SPY10RMi2U Power rating VA/Watt 6KVA / 6KW 10KVA / 10KW Rated frequency 50/60Hz Voltage range 110Vac – 276Vac Input Rated voltage 220 / 230 / 240Vac Frequency 40Hz-70Hz (45Hz-55Hz, 54Hz-66Hz @ load>60%) range Rated current ≤60% rated load: 40-70Hz Frequency >60% rated load: 45-55Hz (50Hz system)/54-66Hz (60Hz system)
  • Page 37 IEC/EN 62040-2 Performance IEC/EN 62040-3 (1) In CVCF mode, UPS needs to be de-rated to 60% capacity (rated output power and maximum charging current). (2) @220VAC input phase voltage, rated output power and maximum charging.

This manual is also suitable for:

Power symphony spy10kirmPower symphony spy6kirtb

Table of Contents