13.15.2.6 Sunlight Sensor Abnormality
Abnormality detection:
When ECONAVI is ON, if the sunlight intensity value below minimum level continuously for 24 hours, the
o
sunlight sensor disconnection error counter will increase by 1 time. If the ECONAVI is OFF, the 24 hours
timer will be reset, but the sunlight sensor disconnection error counter will not be reset.
Error Code judgment
When sunlight sensor disconnection error counter reached 15 times, sunlight sensor is judged as abnormal.
o
No ECONAVI indicator blinks. Until ECO check code sent during ECONAVI operation ON, the ECONAVI
o
indicator will blinks.
When error code happened, the unit is able to operate without sunlight sensor.