14.7 Parameter data

The parameter data of the temperature sensor complies with the smart sensor profile (V1.0).
Index hex
Subindex
hex
0x02
0x00
System Com-
mands
0x03
0x00
Data Storage In-
dex
0x0C
0x00
Device Access
Lock
0x24
0x00
Device Status
0x3D
0x01
SetPoint Logic 1
0x3D
0x02
SetPoint Mode 1
0x3D
0x03
SetPoint Hyster-
esis 1
0x3F
0x01
SetPoint Logic 2
0x3F
0x02
SetPoint Mode 2
0x3F
0x03
SetPoint Hyster-
esis 2
0x93
0x00
SetPoint type 1
0x97
0x00
SetPoint type 2
0xD4
0x00
Unit
www.gemu-group.com
Object name
0x81 = Delete min./max. value
0x82 = res
0xA0 = Set0
0x01: Upload Start
0x02: Upload End
0x03: Download Start
0x04: Download End
0x05: Datastorage Break
0x00: Unlocked
0x01: Parameter access - Lock
0x02: Data storage - Lock
0x04: Local parameterization - Lock
0x08: Local user interface - Lock
0x03: Parameter access & Data Storage - Lock
0x05: Parameter access & Local parameterization -
Lock
0x09: Parameter access & Local user interface - Lock
0x06: Data Storage & Local parameterization - Lock
0x0A: Data Storage & Local user interface - Lock
0x07: Data Storage & Parameter access & Local
parameterization - Lock
0x0B: Data Storage & Parameter access & Local user
interface - Lock
0x00 Device is operating properly
0x02 Out-of-Specification
0x04 Failure
0x00: Value as specified
0x80: Hysteresis NO
0x81: Hysteresis NC
0x0000: No Hysteresis
0x00: Value as specified
0x80: Hysteresis NO
0x81: Hysteresis NC
0x0000: No Hysteresis
0x01 – NPN Output
0x00 – PNP Output
0x01 – NPN Output
0x00 – PNP Output
0x00 °C
0x01 °F
0x02 K
Single Value
0x82: Window NO
0x83: Window NC
0x82: Window NO
0x83: Window NC
0x02 – 0 to 10 V
Output
0x03 – 4 to 20 mA
21 / 28
14 IO-Link Interface
Default
Comment
The action is
performed by
writing to the
subindex
0x00:
Unlocked
0x80: HNo
0x80: HNo
0x00: °C
Temperature
temperat-
unit for the dis-
ure unit
play is changed,
the IO-Link pro-
cess data is not
changed
GEMÜ 3240