Section 2 - General Operation - Velocity VDOT-H2 Instruction Manual

Analog heat detector
Table of Contents

Advertisement

1.3
VDOT-H2 and VDOT-H2-H common features
* Low profile, stylish appearance
* Soft addressing
* Low monitoring current
* Supplied with protective dust cover
TM
* OMNIVIEW
360 ° LED Indicator for polling and fire alarm indication
Section 2 – GENERAL OPERATION
The VDOT-H2 heat detector initiates an alarm in response to both 8.3 °C (15 °F) rate-of-rise temperature or a 57 °C
(135 °F) fixed temperature alarm point.
The VDOT-H2-H initiates an alarm in response to 83 °C (181 °F). Heat detector incorporates a highly linear
thermistor circuit, with the thermistor mounted externally. The specially designed cover protects the thermistor while
allowing maximum air flow. The thermistor circuit produces a voltage proportional to temperature which is scaled, and
transmitted as a digitally encoded value to the control panel.
GLT-299-7-2(3) Rev.0