Instruction Manual
VDOT-S6 Base
Sounder Base
Before Installation
Please read these instructions carefully and keep for future reference.
The information in this document is subject to change without notice. For updates please refer to our website.
Do not use the products outside the rated power supply voltage range specified in
the Specifications. It may cause a fire or damage to equipment.
Note: Follow the requirements for the installation of the products in accordance with the Specifications. Otherwise
it may cause malfunction.
Note: Do not install the product in any location where oil, dust, iron powder, chemicals, or hydrogen sulphide may
occur or affect the product. It may cause damage to equipment.
Section 1 – INTRODUCTION
VDOT-S6 Base is a detector base with sounder which is individually or collectively controlled by Velocity MMP
Control Panel series using addressable system and designed to be used with the model VDOT-PY, VDOT-PYH,
VDOT-DPH, and VDOT-H2 detector head.
The detector base has 4 sound patterns which are continuous, march, ANSI 3 temporal and 4 temporal patterns.
These patterns which are used in and around buildings can be selected by the control panel. Only ANSI 3
temporal pattern shall be used for UL Listed applications.
The sounder pressure level at 3 m (10 ft.) from the base is over 85 dB.
127 bases can be connected to a loop of the control panel.
The base is designed to be mounted to 3-1/2" octagonal, 4" octagonal or 4" square electrical box.