Summary of Contents for Nidec Leroy-Somer LSA 47.3
Page 1
LSA 47.3 Low Voltage Alternator - 4 pole Installation and maintenance...
Page 2
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole This manual concerns the alternator which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES b) Do not allow children younger than 14 to go near the air outlet guards.
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 1 - RECEIPT 1.4 - Storage Prior to commissioning, machines should 1.1 - Standards and safety be stored: measures - away from humidity (< 90%); after a long alternators comply with...
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 2 - TECHNICAL 2.2 - Mechanical characteristics CHARACTERISTICS - Steel frame - Cast iron end shields 2.1 - Electrical characteristics - Protected ball bearings, greased for life This alternator is a machine without - Mounting arrangement: single bearing...
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 3 - INSTALLATION • Single-bearing coupling Before coupling, check the compatibility Personnel undertaking various between the alternator and the engine by operations indicated in this section must performing: wear personal protective equipment...
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 3.3 - Terminal connection diagrams There are 2 possible methods for restoring the above minimum values. To modify the connection, change the a) Dry out the machine for 24 hours in a position of the stator cables on the terminals.
Page 8
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole • SHUNT, AREP or PMG three-phase 12-wire Voltage / Detection Connection codes Factory connection 50 Hz 60 Hz Winding L1(U) 190 - 208 190 - 240 Parallel Star...
Page 9
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole • Option connection diagram Remote voltage potentiometer Voltage adjustment via remote potentiometer Current transformer connection Coupling A In/4 - Secondary 1 A Coupling D In/2 - Secondary 1 A - PH 1...
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole • Connection checks 3.4 - Commissioning Electrical installations must comply with the current legislation in force in the The machine can only be started up and country of use.
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 4 - SERVICING - MAINTENANCE WARNING 4.1 - Safety measures Do not use: trichlorethylene, perchlo- Servicing or troubleshooting must be rethylene, trichloroethane or any alkaline carried out strictly in accordance with products.
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 4.3 - Bearings The bearings are permanently greased Approximate life of the grease (depending on use): 20,000 hours or 3 years As an option, the bearings are regreasable Regreasing interval: 4000 hours in operation or every 6 months DE and NDE bearing: amount of grease: 45 gr...
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 4.5 - Electrical faults Fault Action Effect Check/Cause The alternator builds up and its voltage is still correct - Lack of residual magnetism when the battery is removed Connect a new battery of 4 to 12...
Page 14
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole • Checking the winding Assembly A: Connect a 12 V battery in series with a rheostat of approximately You can check the winding insulation by 50 ohms - 300 W and a diode on both exciter performing a high voltage test.
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 4.6 - Dismantling, reassembly • Access to connections and the regulation system WARNING Access is directly after removing the terminal box top panel (48).
Page 16
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole - Slide the threaded rod into the NDE bracket - Slide the threaded rod into the bracket hole hole to make it easier to assemble (see to make it easier to assemble (see basic basic diagram).
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole • Reassembling the machine • Dismantling and reassembly of the filters - Mount the rotor (4) in the stator (1) (see drawing above) taking care not to knock the - Remove the grille (51) then take out the windings.
Page 18
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole • Three-phase: 4-pole • Table of weights SHUNT/AREP excitation (values given for information only) Resistances at 20 °C (Ω) Type Total weight (kg) Rotor (kg) Exciter...
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 5 - SPARE PARTS In the event of failure to comply with this advice, the manufacturer cannot be held 5.1 - First maintenance parts responsible for any damage.
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole 5.4 - Exploded views, parts list and tightening torque • Single bearing...
Page 21
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole • Two-bearing...
Page 22
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole Screw Torque Screw Torque Ref. Qty Description Ref. Qty Description Ø Ø Non drive end (NDE) Stator assembly bearing Rotor assembly Inner bearing retainer Preloading (wavy) washer...
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole Disposal and recycling instructions All materials listed above need special treatment separate waste from committed limiting reclaimable materials and should be environmental impact of our activity.
Page 24
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole...
16015 Angoulême Boite Postale 1517 France République Tchèque 45800 St Jean de Braye France LEROY-SOMER ELECTRO- NIDEC INDUSTRIAL AUTOMATION NIDEC INDUSTRIAL AUTOMATION TECHNIQUE Co., Ltd INDIA PRIVATE Ltd - BANGALORE INDIA PRIVATE Ltd - HUBLI No1 Aimosheng Road, Galshan Town,...
Page 26
Installation and maintenance Electric Power Generation 5942 en - 2023.04 / e LSA 47.3 Low Voltage Alternator - 4 pole...
Page 27
Service & Support Our worldwide service network of over 80 facilities is at your service. This local presence is our guarantee for fast and efficient repair, support and maintenance services. Trust your alternator maintenance and support to electric power generation experts. Our field personnel are 100% qualified and fully trained to operate in all environments and on all machine types.
Page 28
www.emersonindustrial.com www.leroy-somer.com/epg Connect with us at: 5942 en - 2023.04 / e...