Interrupting
Permissible
time
tripping
7
delay (y)
ms / cycles
Sec
83 / 5
2
83 / 5
2
83 / 5
2
83 / 5
2
83 / 5
2
83 / 5
2
83 / 5
2
83 / 5
2
Type GMSG 63 kA circuit breaker
front view
Max. sym.
% dc
interrupting
component
(I)
kA rms sym
%
40
47
50
47
63
47
40
47
25
47
40
47
50
47
63
47
Type GMSG 63 kA circuit breaker
rear view
Short-time
Closing and latching
current (I)
(momentary)
(three
seconds)
kA rms
Asymmetrical
(1.55 x I)
kA rms
40
62
50
78
63
98
40
62
25
39
40
62
50
78
63
98
Appendix
Circuit
breaker
type
1
Peak
(2.6 x I)
kA peak
5-GMSG-
104
40-xxxx-104
5-GMSG-
130
50-xxxx-130
5-GMSG-
164
63-xxxx-164
7-GMSG-
104
40-xxxx-104
15-GMSG-
65
25-xxxx-65
15-GMSG-
104
40-xxxx-104
15-GMSG-
130
50-xxxx-130
15-GMSG-
164
63-xxxx-164