DT1102 (PS) start 1. About this document 1.1. Function This operating instructions manual has all the information you need for quick set-up and safe operation of DT1102 (PS) Please read this manual before you start setup. 1.2. Target group This operating instructions manual is directed to trained personnel. The contents of this manual should be made available to these personnel and put into practice by them.
For safety and warranty reasons, any internal work on the instruments must be carried out only by DATCON personnel. 2.2. Appropriate use The DT1102 (PS) is an instrument for industrial use. Detailed information on the application range is available in chapter 3.
DT1102 (PS) 3. Product description 3.1. Delivery configuration The scope of delivery encompasses: Delivered items • DT1102 (PS) • tool for switch setting (in case of shipping more instrument only one tool is enclosed) • documentation: this operating instructions manual certification warranty 3.2.
DT1102 (PS) 3.3. Operating principle The DT1102 (PS) Switch Configurable I/O Galvanic Isolator Area of application provide signal transmission and conversion between transmitters and signal processing units. The instruments feature complete 3-way isolation: the input, the output and the power supply are isolated from each other. The instrument has two inputs: 1.
DT1102 (PS) 3.4. Indicators, configuration switches The following figure shows the indicators and the configuration switches on the DT1102 (PS) front panel. (1) configuration switches for selection input/output ranges (2) red „error” indicator shows the error states (3) green „on” indicator shows the power on state 20220202-V0...
DT1102 (PS) 3.5. Input/output signal selection Four different input/output signal range can be selected with the front panel switches: 0-20 mA, 4-20 mA, 0-10 V, 2-10 V Default setting: 0-20 mA input, 0-20 mA output (all switches are in „off” state). The following figure shows the input/output signal range selection table: The following figure shows steps of setting:...
DT1102 (PS) 3. Set the configuration switches according to the signal range selection table 4. Close the front panel cover Do not use other tool than the enclosed one because you may cause injury either to switches or to front panel! 3.6.
DT1102 (PS) 4. Mounting 4.1. General instructions The instrument should be installed in a cabinet with sufficient IP protection, where the operating conditions are in accordance with chapter 9.1. Technical specification, as described under the title: Operating conditions. The DT1102 (PS) is built in a plastic housing, for mounting on TS-35 Mounting position rail.
DT1102 (PS) 4.3. Mounting procedure The following figure shows the mounting procedures (fixing on the rail): Mounting on the rail The mounting doesn’t need any tool. 1. Tilt the instrument according to the figure; put the instrument’s mounting hole onto the upper edge of the rail (figure step 1.). 2.
DT1102 (PS) 5. Connecting 5.1. Preparing the connection Always observe the following safety instructions: • The connection must be carried out by trained and authorized personnel only! • Connect or disconnect only in the complete absence of line voltage • You should take note the data concerning on the overcurrent protection in installation.
DT1102 (PS) 5.2. Connecting active output current source to the input The following figure shows connecting active output current source to the input: Wiring plan, connecting active output current source (see also “Application example”) Be careful the polarity of the cables 1.
DT1102 (PS) 5.3. Connecting 4-20 mA two wire (passive) transmitter to the input The following figure shows connecting 4-20 mA two wire (passive) transmitter to the input: Wiring plan, connecting 4-20 mA two wire transmitter (see also “Application example”) Be careful the polarity of the cables 1.
DT1102 (PS) 5.4. Connecting voltage source to the input The following figure shows connecting voltage source to the input: Wiring plan, connecting voltage source (see also “Application example”) Be careful the polarity of the cables 1. Loosen terminal screws. 2. Insert the wire ends into the open terminals according to the wiring plan.
DT1102 (PS) 5.5. Connecting current output to the signal processing unit The following figure shows connecting current output to the signal processing unit: Wiring plan, connecting current output (see also “Application example”) Be careful the polarity of the cables 1. Loosen terminal screws. 2.
DT1102 (PS) 5.6. Connecting voltage output to the signal processing unit The following figure shows connecting current output to the signal processing unit: Wiring plan, connecting voltage output (see also “Application example”) Be careful the polarity of the cables 1. Loosen terminal screws. 2.
DT1102 (PS) 5.7. Connecting instrument to the power supply The following figure shows connecting the instrument to the power supply: Wiring plan, connecting the power supply (see also “Application example”) The polarity of the cables is indifferent 1. Before connecting check that the supply voltage correspond with the supply voltage written on the data label.
DT1102 (PS) 6. First „power on”, front panel indicators 6.1. First „power on” After you have completed the connections, put the instrument under supply voltage. If the connection is correct green “on” indicator lights, red “error” indicator dark and you can measure the expected current or voltage on the output.
7.2. Repearing There is no user repairable part inside the instrument. In accordance with Point 2.1.: For safety and warranty reasons, any internal work on the instrument must be carried out only by DATCON personnel. 20220202-V0...
DT1102 (PS) 8. Dismounting 8.1. Dismounting procedure Before dismounting take note the warnings written in chapter 5.1. Preparing the connection. The following figure shows the dismounting procedures. Dismounting from the rail The dismounting procedure needs a screwdriver for slotted screws. Before dismounting disconnect all wires.
DT1102 (PS) 9. Appendix 9.1. Technical specification Input parameters (current) Input signal: DC current Ranges: 0-20 mA, 4-20 mA Overload: 400 mA Input resistance: 10 Ω Input parameters (voltage) Input signal: DC voltage Ranges: 0-10 V, 2-10 V Overload: 100 V Input resistance: 102 kΩ...
Page 24
DT1102 (PS) Power supply Supply voltage: DT1102 24 VDC ±10%, 1.6 W DT1102 PS 230 V AC/DC ±10%, 3.8 VA (2.4 W) Overvoltage class: CAT II. The overcurrent protection in installation: 4 A (B) Ambient conditions Operating temperature range: 0-50 °C * Storage temperature range: -20 - +70 °C Relative humidity:...