AIR-TRANSFER ATVUT 180 P5 User Manual

Air handling unit

Advertisement

Quick Links

USER'S MANUAL
ATVUT 180 P5
ATVUE 180 P5
ATVUT 180 P5 EC
ATVUE 180 P5 EC
ATVUT 180 P5 B EC
ATVUE 180 P5 B EC
Air handling unit

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ATVUT 180 P5 and is the answer not in the manual?

Questions and answers

Summary of Contents for AIR-TRANSFER ATVUT 180 P5

  • Page 1 USER’S MANUAL ATVUT 180 P5 ATVUE 180 P5 ATVUT 180 P5 EC ATVUE 180 P5 EC ATVUT 180 P5 B EC ATVUE 180 P5 B EC Air handling unit...
  • Page 2: Table Of Contents

    Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country. www.air-transfer.nl...
  • Page 3: Safety Requirements

    The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. Never touch the unit with wet or damp hands. Never touch the unit when barefoot. www.air-transfer.nl...
  • Page 4 Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances. THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE. www.air-transfer.nl...
  • Page 5: Delivery Set

    – asynchronous EC - electronically commutated Additional components without a bypass B - bypass Casing design Spigot orientation P - suspended mounting, horizontal spigot orientation Rated air ow [m Series of units ATVUT - heat recovery ATVUE - energy recovery www.air-transfer.nl...
  • Page 6: Technical Data

    The unit design is constantly being improved, thus some models may be slightly different from those described in this manual. TECHNICAL DATA MODEL ATVUT 180 P5 B ATVUE 180 P5 B ATVUT 180 P5 ATVUE 180 P5* Voltage [V/50 (60) Hz]...
  • Page 7: Design And Operating Logic

    The heater maintains air temperature in the supply duct at level that prevents the heat exchanger from freezing. Heater installation and connection to the unit are described in the heater user’s manual. Duct reheater. • The heater maintains the user-defined room air temperature. Heater installation and connection to the unit are described in the heater user’s manual. www.air-transfer.nl...
  • Page 8 - periodically the supply fan is turned off - with the bypass - with the electric preheater (if the unit is equipped with a duct preheater). Mode selection and settings are described in the control system user’s manual. www.air-transfer.nl...
  • Page 9: Mounting And Set-Up

    The HV2 humidity sensor is not included in the delivery set and can be ordered separately. Install the humidity sensor into the mount on the inner side of the unit and connect the humidity sensor to the appropriate connector. www.air-transfer.nl...
  • Page 10 Mounting of the unit to an uneven surface can lead to the unit casing distortion and operation disturbance. Fix the mounting brackets on the wall or the ceiling depending on the type of installation. Expansion Fastener anchor Mounting bracket www.air-transfer.nl...
  • Page 11 Unscrew the thumbscrews on the unit before attaching it to the mounting brackets. Set the unit thumbscrews into the mating cutouts in the mounting brackets and tighten the thumbscrews. Unit mounting example Extract Supply Intake Exhaust drain pipes Diagram 1. Wall vertical installation Ø19 34÷38 drain pipes Diagram 2. Suspended mounting www.air-transfer.nl...
  • Page 12 ATVUT/AT ATVUE 180 P5(B) (EC) Installation options according to diagrams 3-4 are possible for the ATVUE 180 P5B modification. Intake Exhaust Supply Extract drain pipe Diagram 3. Wall vertical installation Extract Intake Exhaust Supply Ø19 Diagram 4. Wall horizontal installation www.air-transfer.nl...
  • Page 13 CONDENSATE DRAINAGE The ATVUT 180 P5(B) (EC) heat recovery units require condensate drainage. The hole for the drain pipes is in the cover of the unit. CAUTION! The drain pipe on the side of the intake air from the street is designed to drain condensate, which forms when the intake air is cooled in the heat exchanger if the unit is operating in a warm, humid climate.
  • Page 14 0 °C, the condensate drainage system must be equipped with heat insulation and preheating facilities. Condensate drainage is not required for the ATVUE 180 P5(B) (EC) units as they are equipped with an enthalpy heat exchanger. www.air-transfer.nl...
  • Page 15: Connection To Power Mains

    Make the electric connections through the terminal block, located in the control unit, in compliance with the External wiring diagram. Access to the control unit DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE PROXIMITY AND PARALLEL TO THE CONTROL PANEL CABLE! DO NOT COIL THE CONTROL PANEL CABLE WHILE LAYING ITS OUT. www.air-transfer.nl...
  • Page 16 * Not included in the delivery set. Available upon a separate order. **Wire cross-section with a cable length of no more than 100 m. Maximum cable length from the controller to the control panel Cable type Distance to power source Shielded cable AWG24 up to 20 m www.air-transfer.nl...
  • Page 17 1 2 3 4 5 6 7 8 9 10 11 12 10 11 12 13 N L3 L4 L1 L L1 L2 L3 Designation Name Wire Designation Name Wire Control panel 4 x 0.75 mm Control panel 6 x 0.75 mm www.air-transfer.nl...
  • Page 18 ** The U supply voltage of the SM1, SM2 external dampers is selected depending on the type of dampers. *** Maximum connecting cable length is 20 m! Output parameters: terminals 17-22 — 3 A, 30 V DC / ~ 250 VAC («dry contact»). — ELECTRIC SHOCK HAZARD! www.air-transfer.nl...
  • Page 19: Technical Maintenance

    After cleaning, re-install the heat exchanger into the unit. Before removing the heat exchanger, unscrew the 7 screws and remove the cover. Remove it from the unit and clean the heat exchanger by using compressed air or a vacuum cleaner. After cleaning, re-install the heat exchanger into the unit. www.air-transfer.nl...
  • Page 20 The drainage system is soiled, damaged, or installed Clean the drain line if necessary. Check the drain line Water leakage (only in incorrectly. slope angle. Make sure that the U-trap is filled with ATVUT units). water and the drain pipes are frost protected. www.air-transfer.nl...
  • Page 21: Storage And Transportation Regulations

    The unit must be transported only in the working position. • Avoid sharp blows, scratches, or rough handling during loading and unloading. • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours. www.air-transfer.nl...
  • Page 22: Manufacturer's Warranty

    FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE FREE OPERATION OF THE UNIT. USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP. www.air-transfer.nl...
  • Page 23: Certificate Of Acceptance

    The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer. Signature: WARRANTY CARD Unit Type Air handling unit Model Serial Number Manufacture Date Purchase Date Warranty Period Seller Seller’s Stamp www.air-transfer.nl...

This manual is also suitable for:

Atvue 180 p5Atvut 180 p5 ecAtvue 180 p5 ecAtvut 180p5 becAtvue 180 p5 b ec