FEATURE MODELS ARA45LCTU / AOA45LBTL, AOA45LCTL AO A45LBTL AO A45LCTL FEATURES Energy saving High energy saving was realized by making the indoor unit and outdoor unit fan motor and compressor all DC and optimal design of the refrigerant cycle. Class A was achieved in European energy classifications.
Page 5
Easy maintenance It can easily access the fan and the motor by the divided panel structure. Structural improvement is attained by making the 1. Control box bottom panel two pieces, front and rear. 2. Fan casing The internal fan casing is also manufactured 3.
WIRED REMOTE CONTROLLER FEATURES Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.(2 times Start / Stop per day for a week) When setting up a timer, operation mode and a temperature setup ...
Page 7
FUNCTIONS START/STOP button Pressed to start and stop operation. SET TEMP. button Selects the setting temperature. MODE button Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). FAN button Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH). ECONOMY (THERMO SENSOR) button Turns the economy efficient mode on and off.
SPECIFICATIONS DUCTED MODEL Type INVERTER HEATPUMP Indoor unit ARA45LCTU Model name Outdoor unit AOA45LBTL Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Cooling European energy label Heating 12.5 Rated BTU/h 42700 Cooling 4.0-14.0 Min-Max BTU/h 13700-47800 Capacity 14.0 Rated BTU/h...
Page 9
DUCTED MODEL Type INVERTER HEATPUMP Indoor unit ARA45LCTU Model name Outdoor unit AOA45LCTL Power source 230V~ 50Hz Available voltage range 198-264V ~ 50Hz Cooling European energy label Heating 12.0 Rated BTU/h 41000 Cooling 4.0 - 13.3 Min.-Max. BTU/h 13700 - 45400 Capacity 13.3 Rated...
DIMENSIONS MODEL : ARA45LC (Unit : mm) Front view Side view (L) Side view (R) Top view Rear view Refrigerant piping flare connection (Gas) Refrigerant piping flare connection (Liquid) Drain piping connection Drain piping connection with cap. ...
Page 11
INSTALLATION PLACE (Unit : mm) 300 or more 150 or more MAINTENANCE HOLE It shall be possible to install and remove the It shall be possible to install and remove the control box. control box, fan units and filter. Maintenance hole Maintenance hole Intake panel...
ELECTRIC CHARACTERISTICS Model name AR A45LC Voltage 230 ~ Power supply Frequency Max. operating current (Indoor unit) Connection cable 1.5-2.5 Wiring spec. (Indoor unit to outdoor unit) Limited wiring length - (01 - 22) -...
SAFETY DEVICES Model Protection form AR A45LC Circuit protection Current fuse (PCB) 3.15A 250V Over current protection 1.90±0.24A Fan motor protection 115±15°C OFF Thermal protection program 70°C ON - (01 - 23) -...
Page 27
EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS Control input CN102 — (Operation/Stop) CN103 — Operation status output See external input/output settings for details. — Fresh air control output CN10 — Auxiliary heater output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop) ...
Page 28
11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor Connected unit control PC board Connector Ex.)Relay unit Ex.)Display 24V DC Relay power supply *10 m Signal Field supply * Make the distance from the PC board to the connected unit within 10m.
Page 29
FRESH AIR CONTROL OUTPUT A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example Indoor Connected unit control PC board Ex.) Fan Ex.) Relay unit 12 V Connector...
Page 30
AUXILIARY HEATER OUTPUT A signal is outputed from Connector when indoor fan and compressor turn on under heating operation. Tr-Ts * Signal output performance specifications are as Tr-Ts = -1°C shown on the right Tr-Ts = -3°C Ex. When Set Temperature(Ts) is 22°C ▪ a nd Room Temperature(Tr) increase above 12°C, signal output is on.
FUNCTION SETTING 12-1. INDOOR UNIT INDOOR UNIT DIP SW Indoor unit address setting Remote controller signal code Jumper Wire Fan delay setting SWITCH POSITION MAIN PCB Indoor unit Printed circuit board DIP-SW SETTING Indoor unit address setting ...
Page 32
JUMPER WIRE SETTING Remote control unit signal cod e (JM1, JM2) Indoor unit setting Factory setting) Jumper wire Remote control unit signal code JM 1 JM 2 Connect Connect Disconnect Connect Connect Disconnect Disconnect Disconnect Fan delay setting (JM3) ...
12-2. INDOOR UNIT (Setting by remote controller) ● The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. ● After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote controller.
Page 34
(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops flashing. If the setting value display changes or if “- -” is displayed when the flashing stops, the setting value has not been set correctly. (An invalid setting value may have been selected for the indoor unit.) SU MO TU WE TH FR SA Setting value...
12-3. WIRED REMOTE CONTROLLER Can not be used. (Do not change) Dual remote controller setting Can not be used. (Do not change) DIP SW Can not be used. (Do not change) Can not be used. (Do not change) Memory backup setting SWITCH POSITION ...
OPTIONAL PARTS Exterior Parts name Model No. Summary Square flange UTD-SF045T Both the Square flange and the Round flange can be selected. Round flange is also used when the fresh air duct is installed Round flange UTD-RF204 Long-life filter can be Long-life filter UTD-LF25NA mounted to the indoor unit.
Page 37
2. OUTDOOR UNIT SINGLE TYPE : AO A45LBTL D2D_AO052E/01 2009.04.30...
2-1. SPECIFICATIONS Type INVERTER HEATPUMP Model name AO A45LBTL Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current 15.0 Cooling 6600 Airflow rate Heating 6600 Type × Q'ty Propeller × 2 Motor output 103 × 2 Cooling Sound pressure level dB(A)
2-2. DIMENSIONS MODEL : AOA45L (Unit : mm) Top view Front view Side view Air flow Drain cap 4-Ø12mm hole mounting places Bottom view MOUNTING POSITION When there are obstacles When there are obstacles When there are obstacles When there are obstacles at the at the back or front side.
2-5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE This table is created using the maximum capacity. MODEL : AOA45L Pipe length (m) COOLING – – – – 0.893 0.890 0.870 – – – 0.919 0.908 0.905 0.885 ...
2-7. AIR FLOW MODEL : AOA45L Cooling Number of rotations Air flow (r.p.m) 6600 Upper fan 1833 Lower fan 3884 Heating Number of rotations Air flow (r.p.m) 6600 Upper fan 1833 Lower fan 3884 - (02 - 07) -...
2-9. ELECTRIC CHARACTERISTICS Model Name AO A45L Voltage 230 ~ Power Supply Frequency Max. Operating Current 20.0 Starting Current 15.0 Main Fuse (Circuit breaker) Current *1) Wiring Spec. Power Cable 5.3 - 6.0 *2)Limited wiring length *1) Wiring Spec. : Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) *2) Limited Wiring length :...
2-10. SAFETY DEVICES Model Protection form AO A45L Current fuse (NEAR THE TERMINAL) 25A 250V Current fuse (NEAR THE TERMINAL) 10A 250V Circuit protection Current fuse (MAIN PRINTED CIRCUIT BOARD) 5A 250V Current fuse (MAIN PRINTED CIRCUIT BOARD) 3.15A 250V OFF : 130±20°C Fan motor protection Thermal protection program...
Page 50
2. OUTDOOR UNIT SINGLE TYPE : AOA45LCTL AOA54LCTL DTR_AO081E_01 2011.03.01...
Page 51
CONTENTS 2. OUTDOOR UNIT SPECIFICATIONS ······························································································ 02 - 01 2. DIMENSIONS ········································································································ 02 - 02 INSTALLATION PLACE ················································································ 02 - 03 3-1. SINGLE OUTDOOR UNIT INSTALLATION ················································· 02 - 03 3-2. MULTIPLE OUTDOOR UNIT INSTALLATION ············································ 02 - 04 3-3. OUTDOOR UNIT INSTALLATION IN MULTI ROW ···································...
SPECIFICATIONS Model name AOA45LCTL AOA54LCTL Power source 1Ø 230V~ 50Hz Available voltage range 198-264V~ 50Hz Starting current 18.9 20.9 Cooling 6,750 6,750 Airflow rate Heating 6,200 6,850 Type × Q'ty Propeller × 2 Motor output Cooling Sound pressure level dB(A) Heating Dimensions (H ×...
INSTALLATION PLACE 3-1. SINGLE OUTDOOR UNIT INSTALLATION WHEN THE UPWARD AREA IS OPEN (Unit : mm) Obstacles at front and Obstacles at rear Obstacles at rear and Obstacles at front only sides only only rear only 1000 or more 1000 or more WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA ...
3-2. MULTIPLE OUTDOOR UNIT INSTALLATION WHEN THE UPWARD AREA IS OPEN (Unit : mm) Obstacles at rear only Obstacles at front only Obstacles at front and rear only 1500 or more 1500 or more WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA ...
AIR FLOW MODEL : AOA45LC, AOA54LC Cooling Number of MODEL rotations Air flow (r.p.m.) 6750 Upper fan AO A45LC 1875 Lower fan 3974 6750 Upper fan AO A54LC 1875 Lower fan 3974 Heating Number of MODEL rotations Air flow...
ELECTRIC CHARACTERISTICS Model name AO A45LC AO A54LC Voltage 230 ~ Power supply Frequency *1) Max. operating current 22.5 23.5 Main fuse (Circuit breaker) *2) Wiring spec. Current Power cable *1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring spec.
SAFETY DEVICES Model Protection form AO A45LC AO A54LC Current fuse 10A 250V, 3.15A 250V (Filter printed circuit board) Circuit protection Current fuse 3.15A 250V (Main printed circuit board) OFF : 150±15°C Fan motor protector Thermal protector ON : 120±15°C Thermal protection program OFF : 108°C (Compressor temp.)
EXTERNAL INPUT & OUTPUT Input Output Connector Remarks Low noise mode ― CN10 Peak cut mode ― CN11 See external input/output settings ― Error status CN12 for details. ― Compressor status CN13 12-1. EXTERNAL INPUT ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specified by external signal.
Page 67
PEAK CUT MODE • Operation that suppressed the current value can be performed by means of the following on- site work. The air conditioner is set to the Peak cut mode when closing the contact input of a commercial ON/OFF switch to a connector on the outdoor control PC board.
12-2. EXTERNAL OUTPUT ERROR STATUS OUTPUT • An air conditioner error status signal is produced when a malfunction occurs. Circuit diagram example Outdoor unit Connected unit control PC board Connector Power supply 1) Power supply ●Voltage (Chart sign=Vcc) : DC 24V or less 2) Load Load ●...
Page 69
COMPRESSOR STATUS OUTPUT • Compressor operation status signal is produced when the compressor is running. Circuit diagram example Outdoor unit Connected unit control PC board Connector Power supply 1) Power supply ●Voltage (Chart sign=Vcc) : DC 24V or less 2) Load Load ●...
FUNCTION SETTING Caution Discharge the static electricity from your body before setting up the push buttons. Never touch the terminals or the patterns on the parts that are mounted on the board. 13-1. FIELD SETTING SWITCHES The positions of the switches on the outdoor unit control board are shown in the figure below. LED lamps Push buttons...
13-2. SETTING METHOD Stop the operation of air conditioner before this setting. 13-2-1. LOW NOISE MODE LED lamp part (1) Switch to “Local setting mode” by pressing [MODE] button (SW1) for 3 seconds or more. (2) Confirm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW3). PUMP POWER LOW NOISE...
13-2-2. PEAK CUT MODE LED lamp part (1) Switch to “Local setting mode” by pressing [MODE] button (SW1) for 3 seconds or more. (2) Confirm (POWER / MODE) blinks 9 times, and press [ENTER] button (SW3). PUMP POWER LOW NOISE PEAK CUT DOWN ERROR...
OPTIONAL PARTS Exterior Parts name Model No. Summary Use to operate the External input External connect UTY-XWZXZ3 and output function of Outdoor unit. - (02 - 22) -...