5. Drainage piping work

Fig. 5-2

6. Electrical work

Fig. 6-1
CN105
(RED)
Fig. 6-2
6
• For left side tubing, be sure to insert the rubber plug into the right drain port. (Fig.
• Use VP-20 (O.D. ø26 (1") PVC TUBE) for drain piping and provide 1/100 or more
• After completion of work, check that correct drain is available from the out ow
Fig. 5-1
Installing procedures (Fig. 5-2)
1. Attach the joint socket 5 supplied with the unit to the drain port on the unit with a
2. Fasten the socket cover 6 supplied with the unit to the joint socket 5.
3. Attach the eld drain tubing (VP-20) to the joint socket 5 with a vinyl chloride
4. Wrap the drain tubing cover 7 supplied with the unit. (Seam taping)
5. Check for correct drainage. (Fig. 5-3)
* Fill the drain pan with water of about 1/4 gal (1 L) from the air outlet.
Fig. 5-3
6.1. Electric wiring
Wiring procedures
1. Remove the tapping screw C then remove the beam.
2. Remove the (2) tapping screws B then remove the electric part cover A.
3. <For radio frequency interface>
4. Replace the removed parts.
5. Tie the electric wires with the local wiring clamp located in the right side of the
E
5-1)
downward slope.
port of the drain tubing.
A Drain pan
B Plug
C Insert the driver etc.in the plug deeply.
vinyl chloride adhesive.
adhesive.
A Drain pan
B Drain tubing
C Socket cover 6
D Joint socket 5
E Drain tubing cover 7
F Insertion length 1-15/32 in. (37mm)
Connect the electric cord of radio frequency interface securely to CN105 (RED)
on indoor controller board.
<For wired remote controller>
Connect the electric wires securely to the corresponding terminals (Fig. 6-1)
electrical box.
A Cover
H Grounding cable connector
B Set screws (2 pcs)
I Terminal block for wired remote controller
C Set screws (Beam)
i Secure with the wiring clamp.
D Wiring clamp
E Indoor controller board
F Wire service entrance
G Terminal block for indoor and outdoor units connection

Advertisement