Miles Valor H5 Series Installation Manual

Gas conversion kits for 1100 & 1150 only

Advertisement

Available languages

Available languages

Quick Links

INSTALLATION MANUAL
1100NGK / PGK & 1150NGK / PGK
Gas Conversion Kits
for 1100 & 1150 ONLY
This appliance is certifi ed for use from 0–4500 feet. For
altitudes above 4500 feet, see local codes.
Kit Contents
1 Pilot injector
1 Main burner elbow injector
1 Set of conversion labels
1 Minimum rate by-pass screw
Tools Required
• Wrenches, to disconnect gas line
• Phillips (+) screwdriver, to remove burner module
• Small (jewelers size) fl at blade screwdriver, to set
pressure
• Small fl at blade screwdriver, to release pressure tap
on valve
• Needle nose pliers, to remove by-pass screw
• Hex (Allen) wrench, 4 mm or 5/32", to remove pilot
injector
• Manometer, to set pressure when regulator is integral
with valve
Specifi cations
Model
Gas
Altitude (Ft.)*
Input Maximum (Btu/h)
Input Minimum (Btu/h)
Manifold Pressure (in w.c.)
Minimum Supply Pressure (in w.c.)
Maximum Supply Pressure (in w.c.)
Main Burner Injector Marking
Pilot Injector Marking
Min. Rate By-Pass Screw
4004585-05
©2020, Miles Industries Ltd.
H5 Series
1100NG 1100LPG
Natural
Propane
0-4,500 feet*
28,000
13,000
3.5"
5.0
10.0
850
51
185
This conversion kit shall be installed by
a qualifi ed service agency in accordance
with the manufacturer's instructions and
all applicable codes and requirements of
the authority having jurisdiction. If the
information in these instructions is not
followed exactly, a fi re, explosion or pro-
duction of carbon monoxide may result
causing property damage, personal injury
or loss of life. The qualifi ed service agency
is responsible for the proper installation of
this kit. The installation is not proper and
complete until the operation of the con-
verted appliance is checked as specifi ed in
the manufacturer's instructions supplied
with the kit.
Use this manual in conjunction with the
installation manual supplied with the
appliance.
1150NG
1150LPG
Natural
0-4,500 feet*
28,000
30,000
13,000
16,000
9.0"
4.0"
11.0
5.0
14.0
10.0
300
850
30
51
125
195
WARNING
Propane
30,000
16,000
9.0"
11.0
14.0
360
30
135

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Valor H5 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Miles Valor H5 Series

  • Page 1 Manifold Pressure (in w.c.) 3.5” 9.0” 4.0” 9.0” Minimum Supply Pressure (in w.c.) 11.0 11.0 Maximum Supply Pressure (in w.c.) 10.0 14.0 10.0 14.0 Main Burner Injector Marking Pilot Injector Marking Min. Rate By-Pass Screw 4004585-05 ©2020, Miles Industries Ltd.
  • Page 2 General Notes Regarding Conversion 4. Supporting injector elbow, unlock and remove pipe assembly, remove injector locknut from inside The conversion may be done before or after the manifold housing. appliance is installed into the cavity. However, the gas must be connected to set the manifold pressure. Prepare the appliance 1.
  • Page 3 Replace the minimum rate by-pass screw Adjust the air shutter 1. Turn module assembly upside down, unlock and The air shutter is located under the ceramic fuel bed at remove pipe assembly. the back. 1. Carefully turn the fuel bed upside down and locate 2.
  • Page 4 Because our policy is one of constant development and improvement, details may vary slightly from those given in this publication. Designed and Manufactured by / for Miles Industries Ltd. 190–2255 Dollarton Highway, North Vancouver, BC, CANADA V7H 3B1 Tel. 604-984-3496 Fax 604-984-0246 www.valorfi replaces.com © Copyright Miles Industries Ltd., 2020...
  • Page 5 GUIDE D’INSTALLATION Série H5 Trousses de conversion de gaz 1100NGK / PGK & 1150NGK / PGK pour 1100 & 1150 SEULEMENT Cet appareil est homologué pour utilisation de 0 à 4 AVERTISSEMENT 500 pieds. Pour altitudes au-dessus de 4 500 pieds, consultez la règlementation locale.
  • Page 6 À propos de la conversion 4. En supportant l’injecteur coude, débranchez la conduite et enlevez l’écrou de verrouillage de La conversion d’un gaz à l’autre peut être faite avant l’injecteur de l’intérieur du manifold. ou après l’installation de l’appareil dans la cavité. Cependant, le gaz doit être branché...
  • Page 7 Remplacez la vis d’indice minimum Réglez l’obturateur d’air 1. Tournez la plaque du brûleur à l’envers; enlevez L’obturateur d’air est situé sous le brûleur de céramique l’écrou de verrouillage et débranchez de la conduite. vers l’arrière. 2. Enlevez les deux vis 1.
  • Page 8 Parce que nous favorisons une politique de développement continu, certains détails de la présente publication peuvent varier. Conçue et fabriquée par / pour Miles Industries Ltd. 190 – 2255 Dollarton Highway, North Vancouver, BC, CANADA V7H 3B1 Tél. 604-984-3496 Téléc. 604-984-0246 www.foyervalor.com © Copyright Miles Industries Ltd., 2020...

This manual is also suitable for:

Valor 1100ngkValor 1100pgkValor 1150ngkValor 1150pgk

Table of Contents