Westlake GVS-65 Installation Manual

Side wall vent termination kit for type bh, class iia (65c) gas venting systems

Advertisement

Quick Links

Plumbing
INSTALLATION GUIDE
GVS-65 SIDE WALL VENT TERMINATION KIT
For Type BH, Class IIA (65°C) Gas Venting Systems
This vent kit is designed and certified as a vent termination
for gas appliances with flue gas temperatures of up to 65°C.
The use of this termination kit must be approved by the appliance
manufacturer. Termination must be made outside the structure.
The vent kit is made for mounting on vertical walls only. The
vent kit is supplied in 2" and 3" versions; it is the responsibility of
the installer to ensure the correct version is used based on the
appliance being vented.
This vent kit is to be installed by a qualified service technician.
Codes and local utility requirements governing the installation of
gas fired equipment, wiring, plumbing, and flue connections must
be adhered to. In the absence of local codes, the installation must
conform to the Natural Gas and Propane Installation Code CAN/
CSA B149.1. Failure to follow these instructions and proper codes
may result in: improper installation, faulty appliance operation,
fire, carbon monoxide poisoning, explosion, property damage,
personal injury or death.
Westlake Pipe & Fittings GVS-65 Side Wall Vent Termination
Kits are certified to ULC S636, for use with the our GVS-65 Gas
Venting System. The Westlake Pipe & Fittings GVS-65 Side Wall
Vent Termination Kit must be installed according to the appliance
manufacturers installation instructions, this installation guide and
the GVS-65 Installation Guide.
Side Wall Vent Termination Kit consists of the following
components:
1 - Vent Terminal Base
4 - #8 x 1" SS Screws
4 - Plastic Screw Anchors 1 - Installation Guide
IMPORTANT:
Seal all holes through wall with sealant
Field-Supplied
Reducing Couplings, if required
2" or 3"
Pipe
4 Plugs
1" x 4 Screws
2" x 4 Screws
www.westlakepipe.com
©2023 Westlake Pipe & Fittings All rights reserved PL-IG-021-CA-EN-0523.1
1 - Vent Terminal Cap
4 - #8 x 2" SS Screws
Vent
Terminal
Base
Vent
3" Pipe
Terminal
Cap
Vent Pipe Material
Installer supplied vent pipe, fittings, primer and solvent cement
must be part of the Westlake Pipe & Fittings GVS-65 Gas Venting
System. Vent pipe and fittings must be sized according to appliance
manufacturer recommendations.
Installation:
1. Determine the best location for the vent termination. In addition
to all applicable codes, consider the following:
a. Minimize the length of pipe and fittings in the piping. Consult
the appliance installation manual to determine maximum
length of pipe and fittings allowed.
b. Termination kit should be positioned where vent vapors will not
damage plants, shrubs, building materials, or air-conditioning
equipment, or where the vapors might be objectionable.
c. Termination kit should be located where it will not be affected
by wind gusts, snow build up, leaves or other debris that will
inhibit the function of the vent exhaust or intake.
2. Vent may be oriented as shown below as long as it is mounted
on a vertical wall.
3. If multiple vent kits are being installed, there must be at least 16"
horizontal space between the vent caps. To prevent possibility
of condensate freeze up, do not locate the vent kits above one
another.
Vertical Installation
Horizontal Installation