Slant/Fin SENTINEL SE-42 Installation And Operating Instructions Manual page 14

Table of Contents

Advertisement

14
OPTIONAL FEATURES Continued
RESTORE FACTORY DEFAULT SETTINGS
To restore all features to the factory default settings (see following chart for default settings)
1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as Pro
2. Turn the HI TEMP dial to select feature dEF
3. Push the Test/Settings Button to
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 11)
Dial
Feature
Setting
1
Thermal Pre-Purge
2
Fahrenheit or Celsius
3
LWCO Manual or
Automatic Reset
4
Circulator Options
Circulator Hold Off
Not available
on this control
Not available
on this control
Low Water Cut-Off
Function
High Limit
Differential
dEF
Restore Factory
Defaults
*: "Circulator Hold Off" feature would be "Active" if defaults are restored. Turn it OFF (Inactive) if required.
to reset all features to the default settings.
Y
Options
OFF
Purge Inactive
On
Purge Active
F
Degrees Fahrenheit
c
Degrees Celsius
A
Automatic Reset
b
Manual Reset
A
Circulator operation on T/TV call only
b
Circulator operation on I1/I2 call only
C
Circulator operation on call from either
Circulator Hold Off – Active
Circulator Hold Off – Inactive
Low Water Cut-Off ON
Low Water Cut-Off OFF
10˚ Differential
20˚ Differential
30˚ Differential
Y
Restore Defaults
n
Do Not Restore Defaults
SEE PAGE 11 FOR ADDITIONAL SETTINGS
Description
*
Sentinel
Record
Default
Your
Setting
Settings
OFF
F
A
A
n

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents