Gas Connection - A.O. Smith BFM - 100 Installation & Service Manual

A.o. smith gas water heater installation user and service manual
Table of Contents

Advertisement

3
3.7.5
3.8

Gas connection

26
Installation
C
IMD-0122 R1
Circulation pipe
See (C) in the installation diagram
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance
of the circulation system.
2. Fit a non-return valve (5) behind the circulation pump to guarantee the
direction of circulation.
3. Fit two stop valves for service purposes (4).
4. Connect the circulation pipe to the T-piece at the drain valve (9) as shown in
the drain valve figure
(3.6.4 "Drain
Warning
The installation should be carried out by an authorised installation engineer,
in compliance with general and local regulations
Caution
Make sure that the diameter and length of the gas supply pipe are large
enough to supply sufficient capacity to the appliance.
See (D) in the installation diagram
1. Fit a manual gas valve (10) in the gas supply pipe.
2. Blow the gas pipe clean before use.
3. Close the manual gas valve.
4. Fit the gas supply pipe to the gas control.
Warning
After fitting, check for leaks.
(3.5 "Installation
diagram").
valve").
(1.3
"Regulations").
(3.5 "Installation
diagram").
Instruction manual BFM
is

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bfm 120Bfm 30Bfm 50Bfm 80

Table of Contents