TS-RMP Sensor Series
Stainless Steel Wall Plate Temperature Sensors
Figure 1: TS-RMP Series Stainless Steel Wall Plate Temperature Sensors
Product Description
This document describes the hardware installation procedures for the
TS-RMP Series Stainless Steel Wall Plate Temperature Sensors,
including one model with tamper proof screws.
The TS-RMP Series is a single gang, blank stainless steel wall plate
that incorporates a precision temperature sensor used to monitor room
temperatures where additional security is required. Additional options
are available that include manual override.
The TS-RMP Series can be flush mounted directly to a single gang
electrical box or directly to a wall. Insulating foam is adhered to the
back of the wall plate to provide a thermal barrier from internal wall
temperatures.
A pigtail is used for connection to the Building Automation System.
The TS-RMP Series can accommodate a wide variety of sensing
elements such as NTC thermistors, RTD elements, Nickel RTD
elements and IC sensors. A 10 kΩ, type 2, NTC thermistor is standard.
General Installation Requirements
For proper installation and subsequent operation of each device, pay
special attention to the following recommendations:
-
Upon unpacking the product, inspect the contents of the carton for
shipping damages. Do not install damaged device.
-
Avoid areas where corroding, deteriorating or explosive vapors,
fumes or gases may be present.
-
Ensure that all equipment is installed according to local, regional,
and national regulations.
H a r d w a r e I n s t a l l a t i o n G u i d e
Personal injury or loss of life may occur if you do not follow a
procedure as specified.
Equipment damage or loss of data may occur if you do not
follow a procedure as specified.
Take reasonable precautions to prevent electrostatic
discharges to the controller when installing, servicing or
operating the controller. Discharge accumulated static
electricity by touching one's hand to a well-grounded object
before working with the controller.
Wiring
All two-wire sensors are polarity insensitive.
Installation
Surface sensors can be mounted directly on a wall or to a wall box. For
the most accurate results, units should be mounted on an inside wall to
a wall box, away from any supply air exhausts and other sources of
heat or cold.