2. INSTALLATION AND MAINTENANCE INSTRUCTION MANUAL

ROOF FANS HIGH TEMPERATURE 'HTC'
DO NOT INSTALL THE FAN BEFORE READING THESE INSTRUCTIONS. KEEP THEM FOR FUTURE APPARATUS
MAINTENANCE OR HANDLING.

2.1 IMPORTANT F400

All F400 fans (400°C/2h) manufactured by Woods Air Movement and described in this manual are approved
according to the UNE EN 12101-3/2002 standard in order to comply with the CTE 2006.D.C.B97106CEE directive
(FORMERCPI196),andarethereforespecificallyrecommendedforemergencysmokeextractionincaseoffire.
The selected model can be installed either inside the risk zone (IMMERSED DUTY MODELS with F400 motors), or
used to carry high temperature gases (EXTERIOR DUTY MODELS); in this case, they must be installed outside the
risk zone. The exterior models are equipped with normal-serial motors and other elements which are not suitable
foruseinthefirezone.
F400 FAN SERVICE MUST ALWAYS BE VERIFIED IN THE FAN LABEL F400- IMMERSED // F400 EXTERIOR DUTY.
ALL F400 WOODS AIR MOVEMENT FANS ARE SUITABLE FOR EXTERIOR DUTY ONLY.
3. EC APPROVAL AND CORRECT USE OF THE FAN
All fans manufactured and supplied by Woods Air Movement have been manufactured in accordance with the
98/37/CE (MAQUINAS-MACHINES) safety standard and according to the safety standard for low voltage materials
73/23/CE.isalsoextendedtoeachparticularrangeincompliancewiththerequiredspecificstandards.
UNE 100250 (ISO 12499)
UNE-EN ISO 12100-1
UNE-EN ISO 12100-2
UNE-EN 294:1993
UNE-EN1050
UNE-EN ISO 3744
ISO 1940-1
ISO 10816-1
In general, all the fan applications where an electronic velocity regulation system is needed require consultation
and authorisation by Woods Air Movement and should comply with the electromagnetic compatibility 89/336/CEE
standard.
The unauthorised use of any type of electronic controller with the fan can be very dangerous and render all
security devices useless, and does not comply with F400 requirements.
For maximum safety in fan maintenance, Woods Air Movement recommends the installation of a SAFETY STOP/
START SWITCH, with manual disconnection. These devices must also be accredited to F400.
IMPORTANT: THIS PARTICULAR FAN MAY NOT BE SUITABLE FOR THE SAFETY REQUIREMENTS OF YOUR
INSTALLATION. PLEASE VERIFY THAT THE CHARACTERISTICS SPECIFIED IN THE APPARATUS COMPLY WITH THE
APPLICATION REQUIREMENTS BEFORE ITS INSTALLATION. VERIFY THAT THE GROUP, CATEGORY, AND CLASS
TEMPERATURE SPECIFIED IN THE CHARACTERISTICS PLATE ARE COMPATIBLE WITH THOSE REQUIRED BY THE
INSTALLATION.
4
Industrial fans. Fan mechanical safety.
Machinery safety- Basic concepts, general principles for design-Part 1:Basic terminology, methodology.
Machine safety- Basic concepts, general principles for design-Part 2: Technical principles.
Machine safety. Safety distances to impede reach of dangerous zones with upper limbs.
Machine safety. Risk evaluation principles.
Acoustics. Risk assessment principles
Mechanical vibrations. Balancing quality.
Mechanical vibrations. Machine vibration evaluation.