OPP-SENS® Transducer (for PT1000) M-...
Technical data
Power supply:
2-wire
15 – 35 V DC
3-wire/MOD/BAC
15 – 35 V DC or 15 – 30 V AC
Current draw:
See table on page 2
Outputs:
2-wire
4 – 20 mA, load < 500 Ω
(3.6 mA on fault)
3-wire
0 – 10 V, load > 10 kΩ or
4 – 20 mA, load < 500 Ω
(-0.3 V or 3.6 mA on fault)
MOD/BAC
digital
Adjustable sensor range: -50...200 / -20...150 / -50...50 /
-20...80 / -30...60 / 0...40 / 0...50 /
0...100* / 0...150 / 0...200 °C
*default setting
Tolerance:
± 0.5 K at 25 °C, suitable
PT1000 sensor element required
Perm.
ambient conditions:
-20 – 70 °C, 0 – 95 % RH
(non-condensing)
Sensor element:
PT1000 cable sensor
(not included in the delivered scope)
Insulation resistance:
≥ 100 MΩ, 20 °C, 500 V DC
Housing:
base: PBT, color similar to RAL 7016
display: PC, transparent
front panel: PC, color similar to
RAL 7016
ring: PBT, color similar to RAL 1003
Strain relief:
M16, PA, color similar to RAL 7001
Cable connection:
spring terminals 0.2 – 1.5 mm²
8-position captive lid
IP 65 housing, including seal ring
Fast wiring with screw-on cover and
spring terminals – no tools required
10-position offset: linear characteristic
line offset with rotating switch
10 sensor ranges selectable with
rotating switch
Optional:
Illuminated display & operator
keyboard with capacitive buttons
5P calibration: Interpolation of the output cha-
racteristic line via 5 arbitrary reference points.
BACnet / Modbus versions
with 3 cable threads
See specification sheet 20903 for suitable PT1000 cable sensors..
Function
The transducer converts the passive PT1000 sensor signal into
0 – 10 V or 4 – 20 mA analog signals, or communicates the
temperature reading via Modbus or BACnet.
Installation
All work (such as installation, electrical connection, startup,
operation, and maintenance) must only be performed by suf-
ficiently qualified tradesmen. The respectively applicable local
rules and regulations (e.g. national building codes, electrical/
VDE regulations, etc.) must be observed. Installers and opera-
ting entities are required to sufficiently familiarize themselves
before startup. Read the product description before operating
the equipment. Verify that the product can be used for the
relevant application without restrictions. We are not liable for
printing errors and changes after printing. Appropriate use
implies compliance with operating and installation instruc-
tions. We are not liable for losses due to inappropriate use.
Unauthorized or inappropriate manipulations or modifications
of the device render the operating permit, the product warranty
and warranty claims null and void.
Transducer is fastened with 2 screws (max. ø 4 mm) on the two
mounting eyelets.
Sensors PG2 | Data sheet No. 20910 | Version 02-2019 | 1 | 9

Advertisement

loading

Summary of Contents for Oppermann Regelgeräte OPP-SENS M Series

  • Page 1 OPP-SENS® Transducer (for PT1000) M-... • 8-position captive lid • IP 65 housing, including seal ring • Fast wiring with screw-on cover and spring terminals – no tools required • 10-position offset: linear characteristic line offset with rotating switch • 10 sensor ranges selectable with rotating switch Optional:...
  • Page 2 M-... Active transmitter Description Technical data Type Analog base transmitter 2-Wire / 3-Wire switchable Power supply 15 – 30 V AC/DC Current draw 25 mA (24VAC) / 10 mA (24VDC) without Display* Output 4 – 20 mA bzw. 0 – 10 V 2-Wire / 3-Wire switchable Power supply 15 –...
  • Page 3: Menu Display

    M-... Electrical connections / settings SW2: 10-position temperature offset Base temperature transmitter (2/3-wire) Position Offset M-T as 2-Wire: +0,5 +1 +1,5 +2 -2,5 -2 -1,5 -1 -0,5 [°C] SW3: Setting: 4 – 20 mA = 2-wire mode (4 – 20 mA) Setting: 0 –...
  • Page 4 M-... Electrical connections / settings Menu display 5P transmitter with 5-point calibration (2-Wire version, current transmitter only) 2-Wire-version (M-TC5P): Valid from sensor firmware 0.27 and display firmware 0.56: The device has got 3 hierarchical menu levels: – main menu – configuration menu (simple parameters) –...
  • Page 5 M-... Electrical connections / settings Menu display 5P transmitter with 5-point calibration (3-Wire version current/voltage) 3-Wire-version (M-T5P): Valid from sensor firmware 0.27 and display firmware 0.56: The device has got 3 hierarchical menu levels: – main menu – configuration menu (simple parameters) –...
  • Page 6 M-... Menu display Electrical connections / settings Valid from sensor firmware 0.28 and display firmware 0.56: Modbus transmitter with 5-point calibration The device has got 3 hierarchical menu levels: Modbus-version (M-MOD): – main menu – configuration menu (simple parameters) – password level (complex parameters, 5P-calibration) Use the buttons to move through the menu.
  • Page 7 M-... Bus settings Modbus protocol Mode: Sensor setting (default RTU) selectable RTU / ASCII Baud rate: Sensor setting (default 9.6 (= 9600)) selectable 9.6 / 19.2 / 38.4 / 56.0 Parity: Sensor setting (default Even) selectable Even / Odd / None Address: Sensor setting (default 1) selectable 1 to 127...
  • Page 8 M-... Menu display Electrical connections / settings Valid from sensor firmware 0.30 and display firmware 0.56: BACnet transmitter with 5-point calibration The device has got 3 hierarchical menu levels: BACnet-version (M-BAC): – main menu – configuration menu (simple parameters) – password level (complex parameters, 5P-calibration) Use the buttons to move through the menu.
  • Page 9 M-... 5P calibration 5-point calibration can be performed with all transmitters with Reference location 4 is ignored because the function shown in „5P“ in the article name and all Modbus and BACnet transmit- the lower left figure between reference locations 3 and 4 is not ters.