Download Print this page

Oppermann Regelgeräte CO2TRH Manual

Co2-, temperature and humidity transducer for indoor installation

Advertisement

Quick Links

CO2-, temperature and humidity transducer CO2TRH
for indoor installation
Technical Data
Valid from firmware V 1.11
CO
-Sensor:
Non-dispersive infrared technology
2
(NDIR) with automated baseline
correction (vers. K 70)
Sensor ranges:
CO
2
Temperature
Relative humidity 0 – 100 %
Fault thresholds:
– Temperature:
± 1,0 °C
– CO
:
± 30 ppm ± 3% of the sensor reading
2
– RH:
±5 % RH (at 20 – 80 % RH)
Sampling cycle:
every 15 seconds
CO
pressure sensitivity: +1.6% of the sensor reading per kPa
2
deviation from standard pressure
(100 kPa)
Service interval:
5 years (recommended
for the first inspection)
Service life:
> 15 years
Rated ambient
conditions:
Humidity: 0 – 95% RH
(non-condensing)
Storage temperature: -30 – 70 °C
Operating temperature: 0 – 50 °C
Protection type:
IP 20
Dimensions (L x W x D): approx. 83 x 123 x 23 mm
Weight:
approx. 130 g
3-way sensor. Multi-functional detection
and control of CO
humidity.
Analog outputs 0 – 10 V for all 3 variables.
With additional relay output for CO
2.4" TFT LCD color touch display with
alarm function
Standard Modbus and BACnet interface.
For demand-based ventilation as a
function of CO
(recommended threshold value < 1,000 ppm).
Automated on-board self-calibration and
on-board diagnostics with service intervals of
longer than 5 years.
Latest generation infrared technology
(NDIR) for measuring carbon dioxide gas.
Power supply:
Power consumption:
Heat-up time:
0 – 2.000 ppm
0 – 50 °C
Response time T 1/e:
Run-in period:
Screw terminals:
Outputs
RS485 Bus:
Relay output:
Analog outputs:
Sensors PG1 | Data sheet No. 14110 | Version 04-2017 | 1 | 14
, temperature, and
2
.
2
concentration
2
24 V DC or 24 V AC
(50 – 60 Hz) ±20 %
< 0.6 W with display. max. 2 W peak
1 Min
(full specification after 15 minutes)
< 3 minutes
> 3 weeks after startup
max. 1,5 mm²
Modbus or BACnet, selectable
closer (rated load 1 mA/5 V up to
1A/50 V AC / 24 V DC). Closes at
1,000 ppm CO
, hysteresis 100 ppm
2
(adjustable). Menu-controlled
switching between temperature or
humidity.
3 linear analog outputs
0 – 10 V DC
(R
< 100 Ω, R
> 5 k Ω).
out
Load
OUT1: 0 – 10 V DC
scaled to 0 – 2,000 ppm CO
OUT2: 0 – 10 V DC
scaled to 0 – 50 °C
OUT3: 0 – 10 V DC
scaled to 0 – 100 % RH
2

Advertisement

loading

Summary of Contents for Oppermann Regelgeräte CO2TRH

  • Page 1 CO2-, temperature and humidity transducer CO2TRH for indoor installation • 3-way sensor. Multi-functional detection and control of CO , temperature, and humidity. • Analog outputs 0 – 10 V for all 3 variables. With additional relay output for CO •...
  • Page 2: Electrical Connection

    Studies show that CO -based ventilation management cuts heating costs. The CO2TRH is designed to measure temperature, relative humidity and carbon dioxide concentration of indoor air (e.g. conference rooms, hotels, hospitals, schools), and to control the ventilation system based on demand.
  • Page 3: Installation

    -, temperature and humidity transducer CO2TRH Installation Attention: the correct positioning and proper technical connec- tion of cables is a basic condition for proper technical function. Please observe these instructions. The airflow requires particular attention. All work (such as installation, electrical connection, startup, Note the following instructions: •...
  • Page 4: Opening The Housing

    -, temperature and humidity transducer CO2TRH Opening the housing Figure 1 Plint Outputs (factory settings) Terminal Default Default Output Range Output OUT (1) 0 - 10 VDC 0 - 2000 ppm CO OUT (2) 0 - 10 VDC 0 – 50...
  • Page 5: Display Menu - Operation

    -, temperature and humidity transducer CO2TRH Display menu – operation The following instructions only address the most important functions for illustration purposes. Modifications may be made without notice, in particular in connection with software updates. This documentation refers to software V 1.06.
  • Page 6 -, temperature and humidity transducer CO2TRH Adjusting the threshold values of alarm display (yellow and red) CO2 for yellow limit, for illustration . The procedure is the same for temperature and relative humidity and RED limit. +/-100 ppm red limit 1000ppm...
  • Page 7 -, temperature and humidity transducer CO2TRH Expanded screen setting (Screen) Attention optional** ** only when PIN1 is active; one pin is queried in this case. Factory setting = no PIN Brightness To save energy and to extend the service life of the display, we recommend not adjusting the brightness higher than 90%.
  • Page 8 -, temperature and humidity transducer CO2TRH Blink/alternating mode Temperature UoM °C or °F 8 | 14 | Sensors PG1 | Data sheet No. 14110 | Version 04-2017...
  • Page 9 Changes in this area must be made with full knowledge of the resulting responses from the CO2TRH transmitter and connected peripherals and the resulting functionality of any other connected systems, specifically such as ventilation, heating, DDC, central building control systems, etc.
  • Page 10 -, temperature and humidity transducer CO2TRH Adjusting BUS parameters (comply with the supplemental documentation for Modbus and BACnet) Note: changes only become active after these are acknowledged with "RESET". Setting the bus protocol (automatic detection, Modbus or BACnet) RS-485 RS-485...
  • Page 11 -, temperature and humidity transducer CO2TRH Offset / wall calibration for temperature and humidity An offset can be applied to the sensor value if the sensor location is not ideal and deviations from the target/reference value are identified. 0.0..-0.1…-0.2°C Parameter programming/scaling of outputs...
  • Page 12 -, temperature and humidity transducer CO2TRH Parameter programming/scaling of outputs Determining the lower / upper sensor range for the voltage output Example for the lower threshold value "LOW". Upper threshold value "High" is adjusted accordingly. Low 600ppm 600, 550…400ppm Low 400ppm...
  • Page 13 -, temperature and humidity transducer CO2TRH Inverting outputs Analogue Analogue invert Inverting outputs Temperature UoM °C or °F Analogue Analogue invert CO2 calibration This is intentionally not described even if the menu provides the option. We ask that you not make changes / take actions in this area.
  • Page 14 -, temperature and humidity transducer CO2TRH Error codes and trouble-shooting (in English – only for trained technicians) Error codes are displayed as a hexadecimal value in the parameter programming area under "Meter"  "Meter Info"  Meter status and output via the bus.