Page 1
Service Manual K DCI Inverter series Indoor Units Outdoor Units K 9 DCI INV GC9 DCI INV K 12 DCI INV GC12 DCI INV K 18 DCI INV GC18 DCI INV REFRIGERANT R410A HEAT PUMP TM KDCI-A-1-GB DECEMBER 2004...
Page 2
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
INTRODUCTION INTRODUCTION General The new K DCI INVERTERS split Cassette range comprise the following RC (heat pump) models: K 9 DCI INV • K 12 DCI INV • K 18 DCI INV • The New DCI K units can be easily fitted to residential and commercial applications featuring esthetic design, compact dimensions, and low noise operation.
Page 5
INTRODUCTION Filtration The K DCI INV series presents several types of air filters: Easily accessible, and re-usable pre-filters (mesh) • Pre-charged electrostatic filter (disposable) • Active carbon filter (disposable) • Control The microprocessor indoor and outdoor controllers, and an infrared remote control, supplied as standard, provide complete operating function and programming.
Page 6
INTRODUCTION Matching Table 1.9.1 R410A INDOOR UNITS OUTDOOR UNITS FLO9DCI FLO12 DCI K9 DCI K12 DCI K18 DC MODEL REF. GC 9 DCI R410A √ √ GC 12 DCI R410A √ √ GC 18 DCI R410A √ The above table lists outdoor units and K indoor units which can be matched together. In addition the listed outdoor units can be matched with other types of indoor units such as wall mounted, Service Manual - K DCI...
RATING CONDITIONS RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: C DB 19 C WB Outdoor: 35 C DB Heating: Indoor: C DB Outdoor: 7 C DB 6 C WB Operating Limits Indoor Outdoor...
PERFORMANCE DATA PERFORMANCE DATA K9 DCI 5.1.1 Cooling Capacity (kW) - Run Mode ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB DATA 22/15 24/17 27/19 29/21 32/23 TEMPERATURE [C 80 - 110 % of nominal -10 - 20 80 - 105 % of nominal (protection range) 25 - 50 % of nominal...
Page 13
PERFORMANCE DATA 5.1.3 Heating Capacity (kW) - Run Mode ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/ DATA WB TEMPERATURE [ºC] 2.16 2.01 1.86 -15/-16 0.55 0.60 0.66 2.41 2.26 2.11 -10/-12 0.66 0.72 0.77 2.59 2.44 2.29 -7/-8...
Page 15
PERFORMANCE DATA K12 DCI 5.3.1 Cooling Capacity (kW) - Run Mode ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB DATA 22/15 24/17 27/19 29/21 32/23 TEMPERATURE [ºC] 80 - 110 % of nominal -10 - 20 80 - 105 % of nominal (protection range) 25 - 50 % of nominal...
Page 16
PERFORMANCE DATA 5.3.3 Heating Capacity (kW) - Run Mode ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/ DATA WB TEMPERATURE [ºC] 2.74 2.55 2.35 -15/-16 0.80 0.88 0.96 3.05 2.86 2.66 -10/-12 0.96 1.04 1.12 3.28 3.09 2.90 -7/-8...
Page 18
PERFORMANCE DATA K18 DCI 5.7.1 Cooling Capacity (kW) - Run Mode ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL 22/15 24/17 27/19 29/21 32/23 ENTERING AIR DB DATA TEMPERATURE [ºC] 80 - 110 % of nominal -10 - 20 80 - 105 % of nominal (protection range) 25 - 50 % of nominal...
Page 19
PERFORMANCE DATA 5.7.3 Heating Capacity (kW) - Run Mode ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB DATA TEMPERATURE [ºC] 2.66 2.28 1.90 -15/-16 1.15 1.23 1.31 3.52 3.13 2.75 -10/-12 1.30 1.38 1.46 4.16 3.77 3.39 -7/-8 1.41...
Page 20
PERFORMANCE DATA Capacity Correction Factor Due to Tubing Length 5.8.1 Cooling 1.001 1.000 0.999 0.998 0.997 0.996 0.995 0.994 0.993 Tubing Length[m] 5.8.2 Heating 1.02 1.00 0.98 0.96 0.94 0.92 0.90 0.88 0.86 Tubing Length[m] 5-12 Service Manual - K DCI...
ELECTRICAL DATA ELECTRICAL DATA Single Phase Units K 9 DCI K 12 DCI K 18 DCI Model Power Supply 1 PH, 220-240 VAC, 50Hz Connected to Indoor Maximum Current 10 A 12 A 35 A Inrush Current 10 A 10.5 A Starting Current Circuit breaker 16 A...
CONTROL SYSTEM CONTROL SYSTEM 11.1 General Functions and Operating Rules The DCI software is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual.
Page 32
CONTROL SYSTEM Target frequency limits as a function of outdoor air temperature )OAT(: OAT Range Cool mode limits Heat mode limits < 6 MaxFreqAsOATC No limit 6 ≤ OAT < 15 MaxFreqAsOAT1H 15 ≤ OAT < 24 MaxFreqAsOAT2H 24 ≤ OAT No limit 11.1.4 Frequency Changes Control...
Page 33
CONTROL SYSTEM 11.1.8 Heating Element Control Heating element can be started if LOAD > * Maxi mumNLOAD AND Indoor Coil temperature <45. The heating element will be stopped when LOAD < MaximumNLOAD OR if Indoor Coil Temperature > 11.1.9 Outdoor Fan Control 7 outdoor fan speeds are determined for each model.
Page 34
CONTROL SYSTEM 11.1.13 Electro Static Filter )ESF( Control ESF is on when ESF switch is on, Safety switch is pressed, unit is on, AND indoor fan is on. 11.1.14 Base Heater Control When OAT is connected, Base Heater will be on when unit is in heating and OAT<2 When OAT is disconnected, Base Heater will be on when unit is in heating.
Page 35
CONTROL SYSTEM 11.4.2 Indoor Fan Control in Heat Mode Indoor fan speed depends on the indoor coil temperature: ICTST ICTVL ICTL ICTH ICTT 11.5 Auto Cool/Heat Mode When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature )∆T(.
Page 36
CONTROL SYSTEM 11.7.2 Indoor Coil over Heating Protection ICT Trend Fast Decreasing No Change Increasing Fast Decreasing Increasing > 53 <ICT ≤ 55 49 < ICT ≤ 53 47 < ICT ≤ 49 45 < ICT ≤ 47 Norm Norm 43 <...
Page 37
CONTROL SYSTEM 11.7.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35) HST Trend Decreasing No Change Increasing > 90 85 < HST ≤ 90 82 < HST ≤ 85 80 < HST ≤ 82 78 < HST ≤ 80 Norm Norm HST ≤...
Page 38
CONTROL SYSTEM 11.7.6.2 Deicing Protection Procedure Threshold COMP max. 12 minutes HEAT COOL OFAN EEVDeicerOpen T1 = T2 = 36 seconds, T3 = 6 seco 11.8 Condensate Water Over Flow Protection Each of the pins P1, P2, P3 can have two options: 1 –...
Page 39
CONTROL SYSTEM Water Level LEVEL4 LEVEL 3 LEVEL1 Pump NLOAD BLINK OPER LED NORMAL 11.8.2 1 Level Logic (used in all models except for floor/ceiling models) Level Don`t Normal care Don`t Overflow care Overflow when Overflow when unit is ON unit is OFF Overflow Water Level...
Page 40
CONTROL SYSTEM 11.10 Operating the Unit from the Mode Button Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature according to the following table: Forced operation Mode Pre-set Temperature Cooling Heating 11.11 On Unit Controls and Indicators 11.11.1 Indoor Unit Controller Controls and Indicators For All Models Except for Floor/Ceiling model...
Page 41
CONTROL SYSTEM 11.11.2 Indoor Unit Controls and Indicators for LCD Display STBY Cool Heat Auto SPT(1*) SPT(1*) SPT(1*) SPT(1*) SPT(1*) SPT(1*) OFF(2*) ON(2*) ON(2*) ON(2*) ON(2*) ON(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) (Low) User User User User User (Med) setting setting setting...
Page 42
CONTROL SYSTEM 11.11.3 Indoor Unit Controller Controls and Indicators for Floor/Ceiling Model STANDBY Lights up when the Air Conditioner is connected to power and is ready INDICATOR for operation OPERATE 1. Lights up during operation. INDICATOR 2. Blinks for 300 msec., to announce that a R/C infrared signal has been received and stored.
Page 43
CONTROL SYSTEM 11.12 Jumper Setting 11.1 . Indoor Unit Controller 0 = Open Jumper (disconnect jumper). 1 = Close Jumper (connect jumper). Self test Jumper – J1 OPERATION SELF-TEST NORMAL Compensation Jumper – J2 Model J2 (Default) Compensation Wall Mounted Activated Floor/Ceiling Deactivated...
Page 44
CONTROL SYSTEM Model selection Jumper – J7, J8 Model J9- Presence Detector/Power Shedding OPERATION Presence Detector Power Shedding Jumper – J10 OPERATION WNG DCI LCD 11.12.2 Outdoor Unit Controller JP9 JUMPER LAYOUT Reserved (PIN ODU3 (PIN 7) ODU2 (PIN 5) ODU1 (PIN 3) ODU0 (PIN 1) GND (PIN 10)
Page 45
CONTROL SYSTEM 11.13.2 Unit Operation in Test Mode In test mode, the unit will operate in fixed settings according to the indoor fan speed setting: Indoor Fan Speed Setting Unit Setting Minimum Capacity Setting High Nominal Capacity Setting Auto Maximum Capacity Setting During test mode, protections are disabled, except for stop compressor status.
Page 46
CONTROL SYSTEM 11.14.2 Outdoor Units SW Parameters Parameter Name DCI9 DCI12 DCI18 DCI50 DUO Compressor Parameters MinFreqC MaxFreqC MinFreqH MaxFreqH Step1Freq Step2Freq Step3Freq Frequency limits as a function of outdoor air temperature MaxFreqAsOATC MaxFreqAsOAT1H MaxFreqAsOAT2H Compressor Over Heating Protection CTTOH1 CTTOH2 CTTOH3 CTTOH4...
TROUBLESHOOTING TROUBLESHOOTING Warning When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE Never open the Outdoor unit before turning off the PowerHIG When turned off, the system is still charged (400V)yle It takes about 4 Min. to discharge the system. Touching the controller before discharging may cause an electrical shock For safe handling of the controller please refer to section 12.6 below.
Page 48
TROUBLESHOOTING SYMPTOM PROBABLE CORRECTIVE ACTION CAUSE Compressor is on but Problem with Check outdoor fan motor according outdoor fan does not outdoor electronics to the procedure in section 12.5.3 work or outdoor fan below, if not OK replace controller Unit works in wrong Electronics or Check RV power connections, if OK, mode )cool instead of...
Page 49
TROUBLESHOOTING 12.3 Judgment by Indoor/Outdoor Unit Diagnostics Enter diagnostics mode - press for five seconds Mode button in any operation mode. Acknowledgment is by 3 short beeps and lights of COOL and HEAT LEDs. Then, every short pressing of Mode button will scroll between Indoor and Outdoor unit diagnostic modes by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LED s.
Page 50
TROUBLESHOOTING 12.3.2 Indoor unit diagnosis and corrective actions Probable Cause Corrective Action Fault Check sensor connections or Sensor failures of replace sensor. all types Indoor and Outdoor Replace Indoor controller. Communication controllers are with different mismatch Versions. No Communication Communication or grounding Check Indoor to Outdoor wiring is not good.
Page 51
TROUBLESHOOTING 12.3.3 Outdoor Unit Diagnostics Problem OCT is disconnected OCT is shorted CTT is disconnected CTT is shorted HST is disconnected (when enabled) HST is shorted (when enabled) OAT is disconnected (when enabled) OAT is shorted (when enabled) TSUC is disconnected (when enabled) TSUC is shorted (when enabled) IPM Fault Bad EEPROM...
Page 52
TROUBLESHOOTING 12.3.4 Outdoor unit diagnosis and corrective actions Probable Cause Corrective Action Fault Sensors failures of all Check sensors types connections or replace sensors. IPM Fault Electronics HW Check all wiring and problem umper settings, if OK, replace electronics. Bad EEPROM No action, unless special parameters are required for unit operation.
Page 53
TROUBLESHOOTING 12.4 Judgment by MegaTool MegaTool is a special tool to monitor the system states. Using MegaTool requires: • A computer with RS232C port. • A connection wire for MegaTool. • A special MegaTool software. Use MegaTool according to following procedure: •...
Page 54
TROUBLESHOOTING 12.6 Precaution, Advise and Notice Items 12.6.1 High voltage in Outdoor unit controller. Whole controller, including the wires that are connected to the Outdoor unit controller may have the potential hazard voltage when power is on. Touching the Outdoor unit controller may cause an electrical shock.
Page 56
78284 GUYANCOURT Cedex Tél. 33 1 39 44 78 00 Fax 33 1 39 44 11 55 www.airwell.com With a concern for a constant improvement, our products can be modified without notice. Photos non contractual. 1 bis,Avenue du 8 Mai 1945...
Need help?
Do you have a question about the K DCI Series and is the answer not in the manual?
Questions and answers