DOLD MINISTART GF 9016 Manual

DOLD MINISTART GF 9016 Manual

Softstarter and softstop device

Advertisement

Quick Links

Power Electronics
MINISTART
Softstarter And Softstop Device
GF 9016

Product Description

The softstarter and softstop device GF 9016 is a electronic control unit for
the smooth starting and stopping of three-phase asynchronous machines.
The GF 9016 slowly ramps up the current on two phases, therefore
allowing the motor torque to build up slowly. This reduces the mechanical
stress on the machine and prevents damage to conveyed material.
When the motor is up to full speed the power semiconductors in GF 9016
are bridged to prevent internal power losses and heat build up. In addition
GF 9016 allows a softstop function prolonging the stop time of the motor,
preventing high counter torques from abruptly stopping the motor.

Block Diagram

1L1
3L2
5L3
Supply
votlage
Electronic
Trigger pulse
generator
Control
bridging
2T1
4T2
6T3
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
M9816_a
t
t
Ramp control
U start
for
Translation
of the original instructions
Your Advantage
• For soft and shockfree start of your asynchronous motors
• Less wearing and longer life for your motors and components
• Space saving and easy fitting
• Reduce load from supply mains by reducing of starting current
Features
• According to IEC/EN 60947-4-2
• Softstart with softstop
• For motors up to 22 kW
• 2-phase control
• Adjustable start up and deceleration time als well as starting voltage,
optionally with kickstart
• Without auxiliary voltage
• W3 connection is possible
• Up to 15 kW: Width 45 mm
Up to 22 kW: Width 52.5 mm

Approvals and Markings

Applications

• Motors with gear, belt or chain drive
• Fans, pumps, conveyor systems, compresseors
• Packaging machines, door drives
• Start current limiting on 3 phase motors

Connection Terminals

Terminal designation
L1, L2, L3
X4
T1, T2, T3
X1+
X1
Start
X2
X1
X2
Boost
X3
X3
X4
X5, X6
X5
Interference
X7, X8
X6
X7
Bypass
X8
1
Signal description
Phase voltage L1, L2, L3
Motor voltage U, V, W
Output + 24V
Input + 24 V
at variant with wide voltage
Start / Stop
Kickstart 0,5 s
0 V
Indicator output, fault
Indicator output, device bridged
08.05.23 en / 731A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MINISTART GF 9016 and is the answer not in the manual?

Questions and answers

Summary of Contents for DOLD MINISTART GF 9016

  • Page 1 Power Electronics MINISTART Translation Softstarter And Softstop Device of the original instructions GF 9016 Your Advantage • For soft and shockfree start of your asynchronous motors • Less wearing and longer life for your motors and components • Space saving and easy fitting •...
  • Page 2 Function Diagram Troubleshooting In case of a fault, please proceed as follows: X1 / X2 Fault 1: Electronics supply or motor too small (see technical data minimum motor load). Send device to the producer to have it checked. L1/L2/L3 Fault 2: Check the frequency of starts and the starting current and also observe the max.
  • Page 3 Technical Data Technical Data 3 AC 400 V ± 15 % Nominal voltage: (others on request) Interference resistance Electrostatic discharge (ESD): 8 kV (air) IEC/EN 61000-4-2 Nominal frequency: 50 / 60 Hz HF-irradiation Rated current: 80 MHz ... 1.0 GHz: 10 V / m IEC/EN 61000-4-3 Nominal motor power...
  • Page 4 The individual earthing systems, power earth, protective earth, digital earth and analogue earth should be laid separately by suitable neutral point wiring. E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen • Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356 dold-relays@dold.com •...

Table of Contents