1. Connect the AC output power cable to
the AC connector.
2. Connect the AC connector to the AC output port.
NOTE
To remove the AC connector from the SUN2000L, perform the operations in reverse order.
The right figure shows how to remove a plug insert.
3.4
Installing the DC Input Power Cable
Positive metal terminal
Ensure that the cable will not
Negative metal terminal
be extracted after crimped.
Pull the DC input power cable
back to ensure that it is
connected securely.
(Optional) Installing the Battery Cable
3.5
Assemble the blue positive and negative connectors by following the instructions in section 3.4 "Installing the DC Input Power Cable."
Save the
watertight caps for
later use.
3.6
(Optional) Installing the Signal Cable
NOTICE
When laying out signal cables, separate them from power cables to avoid strong signal interference sources.
The protection layer of the signal cable is in the connector. Surplus core wires are cut off from the protection layer. The exposed core wire
is totally inserted into the cable hole and connected securely.
Do not confuse the connector to the COM port and the connector to the ALARM port.
If a connector needs to connect to only one signal cable, block the unused cable hole in the seal using a cap and tighten the cable gland.
If a connector needs to connect to two signal cables, ensure that the cables have the same outer diameter.
Three-Core Cable (L, N, and PE)
Two-Core Cable (L and N)
Positive connector
Negative connector
Pull the DC input power cable
back to ensure that it is
connected securely.
NOTICE
1. Ensure that the PV module output is well insulated to ground.
Click
2. The SUN2000L DC input voltage must always be lower than or equal to 600 V DC.
3. Before installing the DC input power cable, label the cable polarities correctly to ensure
correct cable connections.
4. Use the positive and negative metal terminals and black DC connectors supplied with the
SUN2000L. Using other models of positive and negative metal terminals and DC
connectors may result in serious consequences. The caused device damage is not
covered under any warranty or service agreement.
5. If polarity of the DC input power cable is reversed and the DC switch is ON, do not turn
off the DC switch immediately or unplug positive and negative connectors. The device
may be damaged if you do not follow the instruction. This damage is not covered under
any warranty or service agreement. Wait until the solar irradiance declines at night and
the PV string current reduces to below 0.5 A, and then turn off the DC switch and remove
the positive and negative connectors. Correct the string polarity before reconnecting the
string to the SUN2000L.
Click
Pull the battery cable back to ensure
that it is connected securely.
3
Click
Click
3. Check the route of the AC
Ensure that
the locking nut
is secured.
DANGER
The battery voltage will result in fatal injury. Use dedicated
insulation tools to terminate cables.
Ensure that the battery cable is correctly connected. Avoid
reverse polarity.
output power cable.
Ensure that the
cables are correctly
connected.